Technical information

90
230V FX Series Positioning Drive Reference Manual
In-Position Time
The value entered here is the time (in seconds) that the drive must remain within the In-
Position Range at the end of an index before the End Of Index output will be turned on.
For example:
If user units were degrees, and 5.00° was entered for the In-Position Range value, and 3.000
seconds were entered for the In-Position Time value, the drive must then be held within
±5.00° of the desired end of index position for at least 3.000 seconds.
If the drive moves out of the In Position Range (±5°) before the In-Position Time has elapsed,
the drive will automatically reset the timer back to the In-Position Time value. If the drive
moves back into the In-Position Range before the Maximum Time Limit timer expires, the
In-Position timer will restart from zero.
Maximum Time Limit
If at the end of an index, the drive does not reach this In-Position Window Range for a time
period exceeding the value set in the Maximum Time Limit parameter, the In-Position
Timeout output (output function #31) will be turned on and the drive will consider the index
complete. However, this does not cause the drive to fault; normal operation will continue.
You will need to determine if this is a fault condition and if further action is required.
Input Functions
This screen allows you to view or modify the Input Functions configuration. The left hand
column (Input Assignments) of numbers corresponds directly to the Input lines on the drive.
The next column (Functions) lists all of the input functions available and shows which input
line each function is assigned to on the drive. Any functions assigned to Line Zero are
inactive. In cases where two or more functions are assigned to the same input line, those
functions will appear on the same line in the left column.