User Guide Instruction Manual

34 - Chapter 2. Programming Interface DeviceMaster UP Modbus/TCP User Guide: 2000447 Rev. I
Instance Attributes
2 Socket Port Commands DWORD
1=Reset Socket Port
2=Save in Flash
4=Clear Sequence Counters
8=Clear Statistics Counters
Set/Get
3 Device Socket Enable USINT
0=Disabled
1=Enabled
Set/Get
4 Device Listen Enable USINT
0=Disabled
1=Enabled
Set/Get
5 Device Listen Socket Port UINT 0-65535 Set/Get
6 Device Connect Mode USINT
0=Never
1=Connect Always
2=Connect On Data
Set/Get
7 Device Disconnect Mode USINT
0=Never
1=Disconnect On Idle
Set/Get
8
Device Connect Socket
Port
UINT 0-65535 Set/Get
9
Device Connect IP
Address
UDINT
00000000 Hex to FFFFFFFF Hex
(Mask=255.255.255.255)
Set/Get
10 Device Idle Timeout
UDINT
(msec)
0 to FFFFFFFF Hex Set/Get
11
(Default=0)
Receive Timeout Between
Packets (if no ETX or time
to wait for ETX value)
UINT
(msec)
0 to 65535
(Default = 0)
Set/Get
36 (part 1)
(Default=0)
As defined only for Get/Set All
PLC Transmit STX
Append Length
USINT
0,1,2 (0=No STX)
(Default=0)
Set/Get
37 (part 1)
(Default=0)
As defined only for Get/Set All
PLC Transmit ETX
Append Length
USINT
0,1,2 (0=No STX)
(Default=0)
Set/Get
12 PLC IP Address UDINT
0000000 Hex to FFFFFFFF Hex
(Mask = 255.255.255.255)
Set/Get
13
(Default=3)
Receive (DeviceMaster
UP to PLC) Ethernet
Data Transfer Method
USINT
0=OFF
1=Unsolicited - Write-to-Tag
2=Unsolicited - Write-to-Tag-Synced
3=Polling
(Default=3)
Set/Get
14
(Default=0)
PLC Controller Slot
Number
USINT
0 to Max Slot Number on PLC
(Default = 0)
Set/Get
Attribute
ID
Name
Data
Type
Data Value(s)
Access
Rule