Manual
IO-Link Master 4-EIP User Guide: 2000582 Rev. A Chapter 2. Hardware Installation - 7
Chapter 2. Hardware Installation
Use the following procedures to install the IO-Link Master hardware:
• 2.1. Setting the Rotary Switch
• 2.2. Mounting the IO-Link Master on Page 8
• 2.1. Setting the Rotary Switch on Page 7
• 2.4. Connecting the Power on Page 10
• 2.5. IO-Link Master LEDs on Page 12
After connecting the IO-Link Master to the network, perform the following tasks:
• Configure the network information, refer to Chapter 3. Initial Configuration on Page 13
• Configure the port characteristics, refer to Chapter 5. IO-Link Port Configuration on Page 31
• Connect the IO-Link devices to the IO-Link Master, refer to Chapter 6. Connecting Devices on Page 45.
2.1. Setting the Rotary Switch
You can use the rotary switches under the configuration window on the IO-Link Master to set the lower
3digits (8 bits) of the static IP address.
If the rotary switches are set to a non-default position, the upper 9 digits (24 bits) of the IP address are then
taken from the static network address and DHCP maybe disabled. The switches only take effect during
startup, but the current position is always shown on the Help/SUPPORT web page.
Optionally, you can leave the rotary switch set to the default and use the web interface or PortVision DX to set
the network address.
Note: If you set the network address using the rotary switches, the Rotary Switch setting overrides the network
settings in the web interface.
Switch Setting Node Address
000
(Default setting)
Use the network configuration stored in the flash. The default network
configuration values are:
• IP address = 192.168.1.250
• Subnet mask = 255.255.255.0
• IP gateway = 0.0.0.0
After completing the hardware installation, see Chapter 3. Initial
Configuration on Page 13 to set the network address using the web
interface or PortVision DX.
001-254
This is the last three digits in the IP address. This uses the first three
numbers from the configured static address, which defaults to
192.168.1.xxx.
255-887 Reserved.
888 Reset to factory defaults.
889-997 Use the network configuration values stored in the flash (reserved).
998 Use DHCP addressing.
999 Use the default IP address.