10 - Chapter 2. Hardware Installation IO-Link Master 4-EIP User Guide: 2000582 Rev. A
Connecting the Power
2.4. Connecting the Power
The IO-Link Master provides dual M12 (A-coded) power connectors.
Maximum EMC protection is provided by a low impedance connection between functional earth, the
grounding tabs, and protective earth. The following table contains power-related information about the power
supply.
Note: IO-Link Master requires a UL listed power supply with an output rating of 24VDC.
You can use this procedure to connect the IO-Link Master to a power supply.
1. Securely attach the power cable between the male power connector and the power supply.
2. Either attach a power cable between the female power connector and another device to which you want to
provide power or securely attach a connector cap to prevent dust or liquids from getting into the
connector. Connector caps were shipped with the IO-Link Master.
3. Apply the power and verify that the following LEDs are lit indicating that you are ready to begin
configuration.
•PWR
MS, first the flashing green and red LEDs displays that it is in self-test mode. After the self-test,
depending on whether you set the IP address with the rotary switch one of the following occurs:
- The green LED is flashing to indicate that it is in standby mode.
- The green LED is lit to indicate that it is operational.
NET, first it flashes green and red indicating that it is in self-test mode. After the self-test, depending
on whether you set the IP address with the rotary switch one of the following occurs:
- Off indicates there is no IP address
Pin Input - Male Output - Female
1L+ L+
2L2+ L2+
3L- L-
4L2- L2-
5 Not connected Not connected
Power Supply Voltage/Current Values
Voltage Input Range 20 to 30VDC
Current (for the IO-Link Master) 100mA
Maximum Output Current 1.9A
The total supply of current for all connected IO-Link devices.
Power Supply Voltage/Current Values
Voltage Input Range
Current (for the IO-Link Master)
Maximum Output Current
The total supply of current for all connected IO-Link devices.