70 - Chapter 4. IO-Link Port Configuration IO-Link Master EtherNet/IP Reference Manual: 2000589 Rev. A
EtherNet/IP Settings Parameters
Transfer Mode Settings
PDI Receive Mode(s)
Default: Polling, Class1
Determines which PDI Receive (To PLC) Modes are enabled. Supported
modes are:
•Polling
• Class1
• Write-to-TagOrFile
PDO Transmit Mode
Default: Class 1
Supported modes are:
•Off
• PLC-Writes
• Class1
• Read-from-TagOrFile
Read/Write Tag/File Settings
PLC IP Address
Default: 0.0.0.0
The PLC IP Address is required if either Write-to-TagOrFile or Read-from-
TagOrFile mode are enabled.
Format: xxx.xxx.xxx.xxx
PLC Controller Slot Number
Default: 0
The PLC Controller Slot Number is required if either Write-to-TagOrFile
or Read-from-TagOrFile mode are enabled.
Valid range: 0-64
PLC Type
Default: ControlLogix
Indicates the type of PLC that the tag(s) or file(s) are written to and/or
read from. Supported PLC Types are:
• ControlLogix
•SLC
• PLC-5
• MicroLogix
Write PDI to Tag/File Settings
PDI Tag/File Name
Default: blank
The tag or file name to place the PDI data block.
• ControlLogix family:
- Tags must be same type as PDI Data Format (SINT, INT or DINT).
- Tags must be an array.
- Tags must be at least as long as the PDI Data Block Length.
• SLC/PLC-5/MicroLogix:
- Files must be of INTEGER (16-bit) type.
- Files must be named with standard file name conventions (i.e:
N10:0, N21:30, etc)
- The file must be at least as long as the PDI Data Block Length.
Append PDO to PDI Data
Default: False
If selected, the IO-Link Master appends any PDO data to the end of the
PDI data.
• False = Do not append PDO data
• True = Append PDO data
EtherNet/IP Settings Page (Continued)