Specifications

Schneider Electric 1354 Clifford Ave. Loves Park, IL 61111 1- 8 8 8 -4 4 4-1311 w w w.schneider-electric.com
F-27687-1_short February 2011 ao
© 2011 Schneider Electric. All rights reserved.
VB-7263 Precision Globe Valves
Venta
3
Flow Characteristics
All valves have modified linear flow character-
istics. That is, the flow rate is nominally propor-
tional to the valve plug lift, at a constant differen-
tial pressure.
Temperature Pressure Ratings
Consult the appropriate valve linkage general instruction sheet for the
effect of valve body ambient temperatures on specific actuators. Ratings
conform with published values and disclaimer.
VB-7263-0-x-P (Cast Bronze Body)
Standards: Pressure to ANSI B16.15 Class 250 with 400 psig up to 150°F
decreasing to 310 psig at 340°F
50
(345)
250 (121)
200 (93)
150 (65)
100 (38)
50 (10)
300 (149)
150
(1034)
250
(1724)
350
(2458)
100
(689)
Pressure — psig (kPa)
310 psig
(2137 kPa)
Temperature — °F (°C)
200
(1379)
300
(2068)
400
(2758)
Maximum Media
Temperature
340°F (171°C)
Minimum Fluid
Temperature
20°F (-7°C)
VB-7263-0-4-P
350 (176)
Normal Position of Valve Actuator Assembly
Actuator Series Actuator Type Required Valve Linkage Normal Position
Mx51-710x-xxx Electric None Normally Closed
Mx51-720x-xxx None Normally Closed
M900AR-xx-VB None Normally Closed
M900AE-xx-VB None Normally Open
M900AR-xx AV-821 Normally Closed
M900AE-xx AV-821 Normally Open
MA-521X AV-7600a Normally Closed
MK-2690 Pneumatic AV-7400 Normally Closed
MK-46x1 AV-401 Normally Closed
MK-66x1 AV-430 Normally Closed
MP-521x Electric AV-7600a Normally Closed
MP-541x AV-7600 & AV-601 Normally Closed
MPR-561x Normally Closed
MP-551X Normally Closed
Mx-2223x3, Mx-23xx3 None None
M400A-xx-VB, M800A-xx-VB,
M1500A-xx-VB
None None
M400A-xx, M800A-xx, M1500A-xx AV-821 None
DuraDrive Damper Actuators
b
AV-611 for 1/2" to 1-1/4" Valves Normally Closed, Normally Open, or none
DuraDrive Damper Actuators
b
AV-602 for 1" to 2" Valves Normally Closed, Normally Open, or none
a High ambient temperatures with high media temperatures in the valve may require the use of the AV-601 in addition to the AV-7600.
* Refer to the the AV-611 General Instructions, F-27410 and the AV-602 General Instructions, F-26914 for compatible actuator information
Flow
Stroke
Closed
Open
100%
90%
80%
70%
60%
50%
40%
30%
20%
10%
0%
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%