Specifications

Schneider Electric 1354 Clifford Ave. Loves Park, IL 61111 1- 8 8 8 -4 4 4-1311 w w w.schneider-electric.com
F-27687-1_short February 2011 ao
© 2011 Schneider Electric. All rights reserved.
VB-7263 Precision Globe Valves
Venta
2
Specifications
Action Stem Up Closed
Sizes 1/2” to 2”
ANSI Pressure Class 250 (up to 400 psig below 150°)
ANSI Seat Leakage Designed to ANSI V up to 35 psi (241 kPa), ANSI IV up to 87 psi
(600kPa) with long term seat leakage dependent on proper water condi-
tioning and maintenance of the water system
d
Control Media
Temperature
20 to 340° F (-7 to 171° C) water (up to 60% glycol/water solution),
pressurized treated steam
AllowableP for Water
b
87 psi (600 kPa) Max for normal life.
a
Maximum inlet pressure
saturated steam
100 psig (690 kPa)
Max P for sizing, saturated
steam
80% of inlet pressure up to 15 psig and 42% of absolute inlet pressure
above 15 psig inlet
Max P at close-off, satu-
rated steam
Inlet pressure (actuator must be rated to provide close-off pressure)
Listings/Certifications RoHS Compliant, PED, CRN
Body Pattern NPT Threaded
Valve
Size
Cv Kvs
c
Rangeability Valve Body Part Number
1/2" 0.1 0.09 Over 13 to 1 VB-7263-0-4-31
0.22 0.19 Over 18 to 1 VB-7263-0-4-33
0.4 0.35 Over 100 to 1 VB-7263-0-4-01
0.75 0.65 Over 100 to 1 VB-7263-0-4-34
1 0.87 Over 100 to 1 VB-7263-0-4-36
1.3 1.1 Over 100 to 1 VB-7263-0-4-02
1.8 1.6 Over 100 to 1 VB-7263-0-4-28
2.2 1.9 Over 100 to 1 VB-7263-0-4-03
2.9 2.5 Over 100 to 1 VB-7263-0-4-30
3.25 2.8 Over 100 to 1 VB-7263-0-4-39
4.4 3.8 Over 100 to 1 VB-7263-0-4-04
3/4" 5.5 4.8 Over 100 to 1 VB-7263-0-4-05
6.3 5.4 Over 100 to 1 VB-7263-0-4-41
7.5 6.5 Over 100 to 1 VB-7263-0-4-06
1" 8.2 7.1 Over 100 to 1 VB-7263-0-4-51
9 7.8 Over 100 to 1 VB-7263-0-4-52
10 8.7 Over 100 to 1 VB-7263-0-4-07
12 10 Over 100 to 1 VB-7263-0-4-08
1-1/4" 14 12 Over 100 to 1 VB-7263-0-4-61
16 14 Over 100 to 1 VB-7263-0-4-62
18 16 Over 100 to 1 VB-7263-0-4-63
20 17 Over 100 to 1 VB-7263-0-4-09
1-1/2" 22 19 Over 100 to 1 VB-7263-0-4-71
24 21 Over 100 to 1 VB-7263-0-4-72
28 24 Over 100 to 1 VB-7263-0-4-10
2" 31 27 Over 100 to 1 VB-7263-0-4-81
34 29 Over 100 to 1 VB-7263-0-4-82
40 35 Over 100 to 1 VB-7263-0-4-11
Notes:
a. To minimize noise, ensure the flow rate in the piping is
less than three meters (10ft)/second and the differential
pressure is less than 35 psi (241 kpa). Operating within the
cavitation zone or an operating differential pressure above
35 psi (241 kpa) may result in noise.
b. Maximum recommended differential pressure in
open position. Do not exceed recommended differential
pressure (pressure drop) or integrity of parts may be
affected. Exceeding maximum recommended differential
pressure voids product warranty.
c. kvs = m3/h (P = 100 kPa) Cv = kvs x 1.156
d. Requires properly conditioned waterper EN-205 Water
System Guideline, F-26080. Actuator close off force
recommendations must be observed to meet ANSI Class V.
Materials
Body Bronze
Seat 316 Stainless Steel
Stem 316 Stainless Steel
Plug 316 Stainless Steel
Packing Spring-Loaded TFE/EPDM
Disc PTFE