Specifications
Page 1 of 8
9/25/2013 1:47 PM
,
Notes: 1) BAH to provide a 2" wide flanged 304 stainless steel discharge collar (5" deep). Mechanically fasten collar to unit with
minimum 18-8 SST hardware only.
2)
3) All Interior seams to be caulked with clear FDA approved caulking. The exterior to be caulked with standard caulk.
BAH to provide an MSDS sheet for all caulking used.
4) Caulking must be kept to a minimum and not smeared beyond the seam. Caulking shall be rated for temperatures
above the maximum design temperature of the unit.
5) All doors to have a safety chain to limit door swing to 90°.
6) BAH to provide a 2" wide flanged stucco aluminum inlet collar (5" deep). Mechanically fasten collar to unit.
7) BAH to provide a C6 x 8.2 lb/ft Steel channel sub-base under the unit channel base.
4
- Standard construction (Single-seal type) and Thermal break construction (Dual-seal type)
36 x 36
(2) 260 Ventlok None
12 x 12 Thermal pane
Dual-seal4 18 x 36
(2) 260 VentlokDual-seal1
Dual-seal (2) 260 Ventlok2 24 x 36 None
Size: Dead Lights:
2
- All black steel, including unit base, shall be painted w/ epoxy mastic.
* - Base assembly meets NFPA 90A per UL723
DOORS
3
:
3
- Refer to main assembly drawing for door locations.
Qty: (Qty) Latches:
Type
4
:
Drain Pan Connection Hand: Right Hand -
Drain Pan: 16
stitch-welded and sealed with no
GA IAQ continuously sloped 304 Stainless steel
turned-up perimeter lip.
- Cooling coil & humidifier sections
Floor sheets are
Floor Sht.: 10 GA 304 Stainless steel - Entire unit except the cooling coil & humidifier sections
BASE
2
:
C8 x 11.5 lb/ft Steel Structural Polyurethane foam insul.* 20 GA galv. steel coversheet & removable lifting lugs
Insulation Type: Plain surfaced - Entire unit
1
- Provide level foundation under perimeter of each section.
Unit Installed On
1
:
Housekeeping pad or building floor
Thermal Break Construction: Yes Location: Entire unit
Knockdown Construction: No KD Type:
Exterior Painted: No Paint Finish: Color:
Bulkhead: 16 GA 304 Stainless Steel -
Interior: 18 GA 304 Stainless Steel -
Single wall construction
Entire unit
Exterior: 0.063 In. Stucco Aluminum Fasteners: Exterior Stainless steel Interior Stainless steel
Roof: Flat Environment: Indoor construction
UNIT CONSTRUCTION
CASING :
2" Thick w/ 3 pcf density fiberglass insulation
Design Pressure (+/-)
12 inches W.G.
Mark:
TCS41704A/AHU00407
Project Mgr.: Dave Lewandowski
Cust. PO:
129006
Designer: Ivan Johnson / Malcolm Childress
End User:
BMS
Sales Office: 999 BAH - Home Office
Engineer:
Thomas Engineering, Inc. / Marty Berthold
Sales Rep.: Jim Adamczak
AC2000 Data Sheets, Version 6.30
GENERAL
Customer:
Thomas Engineering, Inc., Hoffman Estates, IL
Qty/Size/Type: 12
BB2AI-DPFHCW6DHHCNO
Job Order:
13331
Revision:
C
Data Sheets
Air Handling Unit Information
Sales Order:
130079-01
Dwg. No.:
E-13331-1