Guide
     (*Do not rotate side outlet in its threads to avoid possible 
leakage.) 
  i.   Replace cover.
  Final checkout of the installation
   After any adjustment, set appliance in operation. Observe 
several complete cycles to ensure that all burner components 
function correctly.
6.  Operation
  Basic opertation
   Knob-A (Figure 3) for manual pilot, 
on-off function, and piezo activation. 
Knob-B (Figure 3) for temperature 
level selection with intergrated 
thermostat providing snap action(on-
off) and modulation control for 
minimum to maximum flow.
  Ignition intrlock
   The interlock device prevents the 
re-establishment of gas flow – when 
no pilot flame is present – until the thermocouple has cooled 
sufficiently.
  Adjusting temperature
   Turn knob-B (Figure 3) toward higher numbers to increase 
temperature, toward lower numbers to decrease. Remote 
control versions contain a motor that activates this knob, or it 
can also be operated manually.
  Optional side-outlet control for 2-burner operation
   Additonal side-mounted manual valve (knob-C, Figure 3) 
primarily for 2-burner gas fireplace applications.
  Lighting procedure
   a.  Turn knob-A (Figure 4) slightly 
left towards the ‘IGN’ position 
until reaching stop, press down 
and hold for five seconds (only 
pilot gas flows).
  b.  Continue pressing down while 
turning further left to activate 
piezo, continue to hold down for 
10 seconds after pilot burner 
has been lit. If pilot does not 
light, steps a. and b. can be 
immediately repeated. (See Note below)
  c.   Upon lighting, release knob and turn further left to ‘ON’ 
position (both pilot and main gas flows).
   Note: If pilot flame is not established, equipment manufacturer 
(OEM) will determine the number of additonal attempts to light 
– and with continued failure the purge time.
  Shut off procedure
   a. Turn knob-A (Figure 4) right until reaching stop.
  b.  Press down slightly and continue turning right from ‘PILOT’ 
position to the ‘OFF’ position.
   When the thermocoupler has cooled sufficiently (time will vary 
based on themocouple type used), pilot lighting procedure can 
be repeated. (See Ignition interlock.)
12
Figure 4
Figure 3
(Shown with cover)
7.   Very high pressure surges in the gas supply line (or as a result 
of exposing the system to high pressure) may result in serious 
internal damage and cause leakage or affect control operation. 
If you suspect tht a Mertik Maxitrol control has been exposed to 
more than 1-1/2 times its maximum inlet pressure, turn off the 
gas and have the system checked by an expert.
8.   The outlet pressure of the control must be measured to make 
sure it is in accordace with intended usage.
9.   Caution should be used to guarantee that there is sufficient 
inlet pressure to achieve the desired outlet pressure and no 
readjustment of the outlet pressure setting should be made 
unless the inlet pressure is within the proper limits for the 
control. Failure to follow this may result in overfiring of the 
appliance or other gas burning device.
10.  A Mertik Maxitrol combination control must be used within its 
ambient temperature range, and not in excess of its maximum 
inlet pressure. The control can be used with all fuel gases.
11.  In case of any doubt, please contact the Service Manager, 
Maxitrol Company, Southfield, MI. Phone: 248/356-1400.
12.  Specifications
  Maximum Operating Inlet Pressure
  1/2 psig (34.5 mbar)
  Ambient Temperature (Control)
  32° to 176° F (0 to 80° C), or 32° to 225° F (0° to 107° C) for 
  “T” Models
  Control Range
  Capacity:  10,000 – 85,000 BTU/hr
  Outlet Pressure:  3” w.c. to 5” w.c. (7.5 to 12 mbar)
      8” w.c. to 12” w.c. (20 to 30 mbar)
  *Piezo & Cable
  Min/Max Spark Gap: 3/4 mm
  Min/Max Operating Temperature: -4° to 392° F (-20° to 200° C)
  Min/Max Lead Lenghs: 150/1000 mm
   (*Piezo wire should not be drawn down parallel against 
lengths of metal –this can result in reduction or loss of power 
to ignitor. When placing the ignition cable/piezo wire, care 
should be taken not to stretch it too tightly. If possible, avoid 
contact with the appliances’s metal parts, especially those with 
sharp edges.)
  Maximum Ambient Temperature (Sensor)
  Control Range 55° – 95° F: Sensor 122° F ( 50° C)
  Control Range 60° – 120° F: Sensor 160° F ( 71° C)
  Control Range 85° – 175° F: Sensor 230° F (110° C)
  Control Range 210° – 640° F: Sensor 715° F (380° C)
  Hardwired Wall Switch
  Use 24 gauge wire or larger for a maximum run of 100 feet
  Ultrasonic Remote Control and Receiver
  Receiver wire to combination control is rated at 350° F
  Optimal remote operating distance 20 feet
   (For best results use fully charged ALKALINE batteries in 
ambient temperatures less than 125° F)










