3.1.13 ID code.
There are 4 bit Dip switch for remote and receiver, the remote ID set must match receiver, If not, the
remote will be can’t control the receiver.
3.1.14 Reset button: The Reset button in left of ID DIP switch, press the Reset button to reset the
remote and initialization, re-select the or again.
3.1.15 High temperature shut down: if the transmitter measures a room temperature exceeding 99
or 37, the LCD will display “HI” and the transmitter will turn off the fireplace. The transmitter
will function on OFF key only until the room temperature has droped below 99 or 37. (for
safety issue)
If the transmitter measures a room temperature less than 40 or 4, the LCD will display “Lo” .
The all keys can operate and can be sent the commands to operate the fireplace.
3.1.16 Backlight: The backlight colour will change according to the current temperature range. If the
room temperature over the 26(78), then the backlight will be Red. If room temperature less than
16(61), the backlight will be Green. Backlight will be Blue if the room temperature is between
16-26. When any key is pressed the backlight will turn on for 8 seconds and then turn off.
3.1.17 Sensor Error: If the temperature sensor circuit is opened, display “E0”. If the temperature
sensor circuit is shorted, display “E1”. Both cases would lock up all keys and shut down all
operating processes until reset its power again. Whenever a sensor error is detected, transmitter must
turn off the flame. (for safety issue)