4.6 Testing the in-room devices
With the network successfully formed, it is now possible to test the devices to ensure proper functionality.
1. Open and close the door.
2. Engage and disengage the deadbolt.
3. Walk around the room to ensure a motion event.
4. Run an event log of the thermostat
using the service device. To make
this, plug the service cable into the
thermostat, choose the
Log
section
under
Readout
in the left part of
the Orion Service window, choose
the applicable
No. of events
and click the
Readout
button.
Ensure that the door and motion
events are logged as shown in the
example in Figure 28.
Figure 28
5. Run a status check by selecting the
Status
section in the left part of the
Orion Service software window,
making sure that the service cable
is plugged into the thermostat and
clicking the
Readout
button. Make
sure that the motion sensor, lock and
thermostat all say ‘Offline: No’; see
Figure 29.
Figure 29
6. Test the range of the motion sensor. First, make sure that the door is open as this will ensure that the
motion sensor is not deactivated by the thermostat.
7. Go to the
Configure device
section
in the left part of the Orion Service
software window and choose the
Motion sensor
tab. Make sure
that the service cable is plugged
into the motion sensor and click the
Activate LED
button; see Figure 30.
Figure 30
8. Walk around the room; the LED of the motion sensor will light up as motion is detected. Ensure that
the range is sufficient to pick up motion in the room. The LED will be active for 10 minutes and then
automatically turn off.
9. The system is now ready for use.