The lock is joined to the thermostat
by using a Discovery card (one of
the ZigBee configuration cards; see
User manual Online option for
information about issuing the card).
For mag/smart locks the card is
inserted into the card reader, and for
RFID locks the card is placed
against the reader. There will
depending on lock model be a green
flash and/or a chirp, indicating that
the lock has been set into discovery
mode. Wait
a few seconds and then present the
Check Status card (one of the
ZigBee configuration cards) at the
lock. If the light flashes the green
light only and/or
a chirp is heard, the lock has
successfully joined the network. If
you instead see a green flash
followed by red flashes, and/or a
beep is heard, the lock has not
joined. In this case, wait a few
seconds and then try the Check
Status card again. If still not
successful, repeat the discovery
process.
7. In order for the lock to send door
events to the thermostats, EMI
events must be enabled. This is
achieved by presenting an Enable
EMI events card (one of the ZigBee
configuration cards) at the lock.
8. If an RF door switch is applicable
instead of a lock, repeat steps 3-5
with the RF door switch; in step 4,
use the
Door switch
tab.
9. Once the devices have been
successfully joined, plug the
service cable into the thermostat.
10. Choose the
Thermostat
tab of the
Configure device
section in Orion
Service. Click the
Forbid Join
button; see Figure 27. Failure to
perform this step will result in
problems when setting up the
network in nearby rooms.
11. Right click on the thermostat
and choose
Get user description
.
Make sure that the description says
‘no’ at ‘Join permitted’.
Figure 27