User's Manual
Ju
ly
5
,
201
2
Page
11
of
49
66 8003 002
-
7
Thermostat deadband
Configurable 1 – 3 ºF; default is 2 ºF
Heat cool switching deadband
Configurable 2 – 4 ºF; default is 3 ºF
Heat / cool switching
Configurable to allow or disallow auto changeover
of heat/cool.
Freeze guard
39 ºF / 4 ºC
Refresh cycle
Optional
Humidity*
Optional
Temperature display
Configurable:
Guest setting or room temperature; default is
room temperature
Intelligent switch
Configurable:
Disabled/use RV output/use G2 output; default
is disabled
Room not occupied timer
Configurable 4 – 30 minutes; default is 8 minutes
Room not sold timer
Configurable 12 – 24 hours; default is 16 hours
Compressor delay (dwell-off time)
5 minutes. The dwell-off time prevents
short-cycling of the compressor; this parameter
cannot be changed
Note:
For information about where in the software to change the parameters, see the tables for basic and
advanced parameters respectively in Daily use manual Orion EMS.
*) These parameters are stored in the thermostat even if the thermostat controller is used
Table 1