User's Manual
Hardware Requirement Specification
(HRS)
Orion Energy Management Doc.No: 61 8003 011
Valid from
Revision
P7
Author(s): Jan Elfstrom Page 9/25
CONFIDENTIAL ©TIMELOX AB
5.1.7.4 The serial communication to/from the service interface shall be with
asynchronous half duplex communication (38400 8N1)
5.1.7.5 The serial communication shall be initiated with an “ACK” (0x06) from the
UI when external power is detected at the service connector
5.1.7.6 The initiation shall be complete in the interval 50 - 200ms after external
power is detected
5.1.7.7 The service device shall answer with “ACK” in the interval 0 - 200ms after
the “ACK” is transmitted
5.1.7.8 The UI shall accept a command-set implemented by AAH
5.1.7.9 The UI shall handle communication through the service connector to the
thermostat or RF module over the module communications interface
5.1.7.10 The service-connector shall be placed at the bottom of the UI (Not visible
from front)
5.1.7.11 The service-connector shall be placed such that it is easily accessible
5.1.7.12 The service-connector shall tolerate voltages in the range 3 – 10VDC
5.1.7.13 Logical high level shall be minimum 3.0V
5.1.7.14 Logical low level shall be maximum 0.5V
5.1.8 Power supply
5.1.8.1 The UI shall be possible to run off three AA 1.5V alkaline cells (3.2 – 4.5V)
5.1.8.2 The UI shall be possible to run on an external fixed +3.2 - +5V supply
(Supplied through the Module Communications Interface) from the TC
5.1.8.3 The UI shall have a maximum average current consumption of 4mA @4.5V
(not including other modules)
5.1.8.4 The UI shall have a maximum current consumption of 150mA @+4.5V (not
including other modules)
5.1.8.5 The supplied voltage shall be possible to read with a minimum resolution of
0.1V
5.1.9 Temperature sensor