User's Manual

Hardware Requirement Specification
(HRS)
Orion Energy Management Doc.No: 61 8003 011
Valid from
Revision
P7
Author(s): Jan Elfstrom Page 18/25
CONFIDENTIAL ©TIMELOX AB
5.2.13.6 When one of the three maintenance parameter values match the total
HVAC run time counter, a notification shall be sent to the server indicating which of the
parameters that triggered the event.
5.2.13.7 The three maintenance run time parameters shall be possible to update
using the EMS GUI or the commissioning tool
5.2.13.8 The maintenance run time parameters shall be updated with an offset added
to the total HVAC run time counter
5.2.13.9 The counters and maintenance parameters shall be stored in non-volatile
memory
5.3 Motion Detector
5.3.1 Introduction
The Motion Detector (MD) is used to detect and report movement in the room. It can also be used
in suite configurations. It is a battery operated device.