Orion Energy Management Doc.No: 61 8003 011
Valid from
Revision
P7
Author(s): Jan Elfstrom Page 15/25
CONFIDENTIAL ©TIMELOX AB
5.2.8.3 ControlBitfield1 – Controls for TC operation
FanMan (bit7) – Manual Speed (1), Auto (0)
FanSat (bit6) – Run when satisfied (1), Stop when satisfied (0)
SetbackEnable (bit5) – Use setback set-point
Thermostat enable (bit4) – 1: Turn on thermostat
MaxFan (bit3-2) – Max allowed fan-speed (if less than three steps)
Fan-speed (bit1-0) – Fan speed 0-2, valid if FanMan = 1
5.2.8.4 ControlBitfield2 – Controls for TC Service
ServiceEnable (bit7) (Disables all outputs for manual control)
BacklighterEnable (bit6) (For test of LED)
REL6Enable (bit5)
REL5Enable (bit4)
REL4Enable (bit3)
REL3Enable (bit2)
REL2Enable (bit1)
REL1Enable (bit0)
5.2.8.5 ActualSetpoint – The TC setpoint 0-99°F
5.2.8.6 ActualDeadbands
Heat/Cool switching (bit7,6,5,4) 2-4°F
Thermostat deadband (bit3,2,1,0) 1-3°F