User's Manual

Hardware Requirement Specification
(HRS)
Orion Energy Management Doc.No: 61 8003 011
Valid from
Revision
P7
Author(s): Jan Elfstrom Page 14/25
CONFIDENTIAL ©TIMELOX AB
5.2.5.5 There shall be a minimum of 32kByte Flash and 500 byte RAM available
for AAH use
5.2.6 Power supply
5.2.6.1 The TC shall be possible to run on a fixed 12 – 30VAC/DC supply
5.2.6.2 The TC shall have a maximum current consumption of 150mA @24VDC
TBD (not including other modules)
5.2.6.3 The power supply inputs shall be protected against reversed polarity
5.2.6.4 The power supply inputs shall have protection against short circuit (non-
permanent, no change of components)
5.2.7 Firmware
5.2.7.1 The TC firmware (FW) shall be possible to upgrade through the 6-pin
Module Communications Connector using the AAH standard bootloader protocol
5.2.7.2 Test-mode
When the TC is put in test-mode by the service-tool, all outputs shall be disabled. All
output and input-states shall be possible to observe on the test-tool.
5.2.7.3 A callback function called 1/s shall be implemented for AAH use.
5.2.7.4 A control structure shall be developed for accessing and controlling
resources in the TC, including external inputs.
5.2.7.5 The responsibility for the actual implementation of different functionality is
AAH
5.2.8 Parameters - CT
The following parameters in NV memory is to control the TC. These values are to be
filled in by AAH and used by Computime.
5.2.8.1 ActualTemperature – The reported temperature (external sensor or UI
sensor)
5.2.8.2 ManualOverrideBitField – Controls for service purposes
Fan-on (bit7) – Turn on the fan
Fan-speed (bit6-5) – Fan speed, 0 - 2
Heat (bit4) – Turn on heating
Cool (bit3) – Turn on cooling
RFU (bit2-0)