User's Manual

Hardware Requirement Specification
(HRS)
Orion Energy Management
Doc.No:
61 8003 011
Valid from
Revision
P7
Author(s): Jan Elfstrom Page 12/25
CONFIDENTIAL
©TIMELOX AB
12- Power out for External Switch
13- Power Supply Common for Thermostat
14- Power Supply for thermostat
5.2.4.7 The I/O connector shall control outputs through potential free switches (e.g.
relay)
5.2.4.8 The I/O connector shall have the same potential for all I/O
5.2.4.9 The TC shall be delivered with a wire-harness fitting the I/O connector with
a wire length of 150mm +/-10mm. (Colors as defined below)
1- W/W2White)
2- Y/W1Yellow
3- G1 – Green
4- G2 – Orange
5- G3 – Dark Blue
6- RV – Violet
7- Emergency Heating - Brown
8- Door Switch –Interior – Gray (not hard requirement)
9- Door Switch – Exterior Orange/Blue (not hard requirement)
10- Extra Input1 (Intput) – Pink (not hard requirement)
11- ground –Black
12- Power out for External Switch – White/Black
13- Power Supply Common for Thermostat – Light Blue
14- Power Supply for thermostat – Red
5.2.4.10 The I/O Connector shall be secured with a friction lock or similar
5.2.4.11 Wires with an area of AWG 22 shall be used
5.2.4.12 A visible label shall be included indicating signals in I/O connector
5.2.5 Module Communications Interface
5.2.5.1 The communication to/from the TC shall be with asynchronous full duplex
communication (38400 8N1)
5.2.5.2 The TC shall accept a command-set implemented by AAH
5.2.5.3 The following pin-out shall be used:
1- VCC (Power out to UI)
2- GND
3- Activate (UI)
4- Wakeup (TC)
5- RxD (To TC)