Computer Gateway User Manual 4-65 5/96
4.7.5
Use information: Store status (applies only to reals and ASCII)
0=store the data value(s) provided
1=store the bad value representation instead
When data type is an array, the store status applies to the whole
array. The bad value representations are NaN for real values and
question mark strings for ASCII.
Content of the field "parameter array pointer/size" depends on
data-type specification. See paragraph 4.7.1 for an explanation of
this field's use with single parameters and with parameter arrays.
This message requires the requesting ACP be connected to its
ACIDP.
This message may be used by one ACP to turn on another ACP by
setting the other's ACIDP PPS parameter to ON.
Sixteen-Character Tagname Form
Header information: Word 1—Transaction Code = 135
Word 2—Number of Words = 31 plus data record size
Word 5—CG Identifier = 2
Message format: Words 1..8—ACIDP name (16 ASCII characters)
Word 9—data access priority (integer) 1=control
2=noncontrol
Word 10—data type (integer) 1=real
2=integer
3=ASCII (24-character string)
4=enumeration/Boolean
5=enumeration ordinal value
7=real array
8=integer array
9=enumeration array
10=ordinal values array
13=internal entity id
14=internal entity id array
17=LCN internal time
18=LCN internal time array
19=ASCII (40-character string)
20=ASCII (40-char. string) array
Word 11—LCN PIN node ID (2 ASCII characters)
Words 12..19—point name (16 ASCII characters)
Word 20—point name index (integer)
Words 21..24—parameter name (8 ASCII characters)
Word 25—parameter index x (integer)
Word 26—parameter index y (future use)
Words 27..31—reserved for future use (fill with integer zeros)
Word 32—start of data record