To configure the device using AMS Trex Communicator, see Configure with Trex
Communicator.
5. Mount the cover and then tighten it.
To avoid depleting the battery, disconnect it when the device is not in use. If you
have configured the device and network but are not ready to commission it,
remove the battery to extend its operating life.
2.1.2
Configuration overview
Note
The specific user interface for performing the configuration varies depending on the host
used. To view the default values, see Configuration defaults.
Procedure
1. Connect to a wired HART interface.
You need to connect to a wired connection to set the wireless credentials.
2. Set the wireless network credentials (Network ID and Join Key) using wired
connection.
The monitor has a default Network ID and Join Key. You can change the network
credentials in the gateway that you used for configuration. All devices should join
the network once the battery is connected.
After the device has joined the network, you can complete the rest of the
configuration steps over a wireless connection.
3.
(Optional)
Name the device (Tag and Device Description).
By default, the tag is VXAABBCC, where AABBCC: is the unique device ID.. The
device joins the network and operates correctly even if no changes are made, but it
is recommended to name the device something meaningful for the specific
application.
4. Specify the units (English, metric, or SI) that will be used for each parameter.
By default, units are set to English, unless the device is shipped to Japan.
User Guide
Configuration
MHM-97927-PBF July 2020