two methods above are also different. Generally, the result in the first method is smaller than that
from the second method.
1) With specific heat value method
While flow transducers installed on water supply pipe, the formulation is as below:
Instantaneous Heater rate qh=qV!pS!(hS-hR)
While flow transducers installed on water return pipe, the formulation is as below:
Instantaneous Heater rate qh=qV!pR!(hS-hR)
Here:
qV: instantaneous volume flow rate
pS: density in water supply temperature
pR: density in water return temperature
hS: specific heat value in water supply temperature
hR: specific heat value in water return temperature
2) With fixed specific heat value method
qh=qV!C!(tS-tR)
Here:
C: Specific heat value of water, the value can be input in M86
tS: temperature of water supply
tR: temperature of water return
Heat totalizer: Q=Qn+qH!
#t
#t=0.5second, which means totalizer time is 0.5s.
In window menu M8., users can select installing point: water supply direction or water return
direction.
The factory default is water supply installing and GB, standard CJ128 specific heat value.
5.2 Wring Connection of PT100 Resistors
TX1 terminal of flow meter is connected to power supply terminal of PT100 RTD in water supply
pipe.
T1 terminal of flow meter is connected to signal terminal of PT100 RTD in water supply pipe.
TX2terminal of flow meter is connected to power supply terminal of PT100 RTD in water return
pipe.
T2 terminal of flow meter is connected to signal terminal of PT100 RTD in water return pipe.
Two piece of PT100 resistors are common-ground, and connected to terminal GND.