Product Manual
Wall Mounted Ultrasonic Flowmeter---User Manual
17
(6)20-0-20mA mode(can only be used with Version-15 flow meter)
(7) 4-20mA corresponding flow velocity
(
8
)
4-20mA corres
p
ondin
g
heat flow rate
M56
4mA or 0mA output value,
Set the value which corresponds to 4mA or 0mA output current (4mA or 0mA is
determined b
y
the settin
g
in M55
)
M57
20mA output value,
Set the value which corres
p
onds to 20mA out
p
ut current
M58
Current loop verification
Check if the current loo
p
is calibrated correctl
y
.
M59 Dis
p
la
y
the
p
resent out
p
ut current of current loo
p
circuit.
M60
Setup system date and time. Press ENT for modification. Use the dot key to skip the digits
that need no modification.
M61
Display Version information and Electronic Serial Number (ESN) that is unique for each
flow meter.
The users ma
y
em
p
lo
y
the ESN for instrumentation mana
g
ement
M62
RS-232/RS485 setup. All the devices connected with flow meter should have matched
serial configuration.
The following parameters can be configured: Baud rate (300 to 19200 bps), parity, data
b
its
(
alwa
y
s is 8
)
, sto
p
bits
(
1
)
.
M63
Select communication protocol.
Factory default is ‘MODBUS ASCII. this is a mode for MODBUS-ASCII, Meter-BUS,
Fuji Extended Ultrasonic flowmeter Protocol
If
y
ou are
g
oin
g
usin
g
MODBUS-RTU
y
ou should select ‘MODBUS
_
RTU’.
M64
AI3 value range.
Used to enter temperature/pressure values that are corresponding to 4mA and 20mA input
current. The dis
p
la
y
values have no unit, so that the
y
can
p
resent an
y
p
h
y
sical
p
arameter.
M65
AI4 value range.
Used to enter temperature/pressure values that are corresponding to 4mA and 20mA input
current.
M66
AI5 value range.
Used to enter temperature/pressure values that are corresponding to 4mA and 20mA input
current.
M67
Windows to setup the frequency range (lower and upper limit) for the frequency output
function. Valid range is 0Hz-9999Hz. Factory default value is 0-1000 Hz.
Please remember to order the module if you need frequency output function.
For Version-15 flow meter, you need to indicate on your orders that you need the
frequency function; Otherwise you will get a flow meter which has no frequency output
circuits.
M68
Window to setup the minimum flow rate value which corresponds to the lower frequency
limit of the fre
q
uenc
y
out
p
ut.
M69
Windows to setup the maximum flow Rate value that corresponds to the upper frequency
limit of the fre
q
uenc
y
out
p
ut.
M70
LCD display backlight control. The entered value indicates how many seconds the
backlight will be on with every key pressing. If the enter value is great than 50000
seconds, It means that the backli
g
ht will alwa
y
s kee
p
in
g
on.