Operating instructions
13-40 Logic Rule Boolean 1
Array [6]
Option: Function:
[22] Comparator 0 Use the result of comparator 0 in the
logic rule.
[23] Comparator 1 Use the result of comparator 1 in the
logic rule.
[24] Comparator 2 Use the result of comparator 2 in the
logic rule.
[25] Comparator 3 Use the result of comparator 3 in the
logic rule.
[26] Logic rule 0 Use the result of logic rule 0 in the logic
rule.
[27] Logic rule 1 Use the result of logic rule 1 in the logic
rule.
[28] Logic rule 2 Use the result of logic rule 2 in the logic
rule.
[29] Logic rule 3 Use the result of logic rule 3 in the logic
rule.
[30] SL Time-out 0 Use the result of timer 0 in the logic
rule.
[31] SL Time-out 1 Use the result of timer 1 in the logic
rule.
[32] SL Time-out 2 Use the result of timer 2 in the logic
rule.
[33] Digital input DI18 Use the value of DI18 in the logic rule
(High = TRUE).
[34] Digital input DI19 Use the value of DI19 in the logic rule
(High = TRUE).
[35] Digital input DI27 Use the value of DI27 in the logic rule
(High = TRUE).
[36] Digital input DI29 Use the value of DI29 in the logic rule
(High = TRUE).
[37] Digital input DI32 Use the value of DI32 in the logic rule
(High = TRUE).
[38] Digital input DI33 Use the value of DI33 in the logic rule
(High = TRUE).
[39] Start command This logic rule is TRUE if the frequency
converter is started by any means
(either via digital input, field bus or
other).
[40] Drive stopped This logic rule is TRUE if the frequency
converter is stopped or coasted by any
means (either via digital input, fieldbus
or other).
[41] Reset Trip This logic rule is TRUE if the frequency
converter is tripped (but not trip-locked)
and the reset button is pressed.
13-40 Logic Rule Boolean 1
Array [6]
Option: Function:
[42] Auto Reset Trip This logic rule is TRUE if the frequency
converter is tripped (but not trip-locked)
and an Automatic Reset is issued.
[43] OK Key This logic rule is TRUE if the OK key on
the LCP is pressed.
[44] Reset Key This logic rule is TRUE if the Reset key
on the LCP is pressed.
[45] Left Key This logic rule is TRUE if the Left key on
the LCP is pressed.
[46] Right Key This logic rule is TRUE if the Right key
on the LCP is pressed.
[47] Up Key This logic rule is TRUE if the Up key on
the LCP is pressed.
[48] Down Key This logic rule is TRUE if the Down key
on the LCP is pressed.
[50] Comparator 4 Use the result of comparator 4 in the
logic rule.
[51] Comparator 5 Use the result of comparator 5 in the
logic rule.
[60] Logic rule 4 Use the result of logic rule 4 in the logic
rule.
[61] Logic rule 5 Use the result of logic rule 5 in the logic
rule.
[70] SL Time-out 3 Use the result of timer 3 in the logic
rule.
[71] SL Time-out 4 Use the result of timer 4 in the logic
rule.
[72] SL Time-out 5 Use the result of timer 5 in the logic
rule.
[73] SL Time-out 6 Use the result of timer 6 in the logic
rule.
[74] SL Time-out 7 Use the result of timer 7 in the logic
rule.
[76] Digital Input x30 2
[77] Digital Input x30 3
[78] Digital Input x30 4
[80] No Flow
[81] Dry Pump
[82] End of Curve
[83] Broken Belt
[90] ECB Drive Mode
[91] ECB Bypass Mode
[92] ECB Test Mode
[100] Fire Mode
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG.11.CA.02 - VLT
®
is a registered Danfoss trademark 97