Operating instructions
13-02 Stop Event
Option: Function:
[6] Current limit See parameter group 5-3* for further
description.
[7] Out of current
range
See parameter group 5-3* for further
description.
[8] Below I low See parameter group 5-3* for further
description.
[9] Above I high See parameter group 5-3* for further
description.
[10] Out of speed
range
[11] Below speed low See parameter group 5-3* for further
description.
[12] Above speed high See parameter group 5-3* for further
description.
[13] Out of feedb.
range
See parameter group 5-3* for further
description.
[14] Below feedb. low See parameter group 5-3* for further
description.
[15] Above feedb. high See parameter group 5-3* for further
description.
[16] Thermal warning See parameter group 5-3* for further
description.
[17] Mains out of range See parameter group 5-3* for further
description.
[18] Reversing See parameter group 5-3* for further
description.
[19] Warning See parameter group 5-3* for further
description.
[20] Alarm (trip) See parameter group 5-3* for further
description.
[21] Alarm (trip lock) See parameter group 5-3* for further
description.
[22] Comparator 0 Use the result of comparator 0 in the
logic rule.
[23] Comparator 1 Use the result of comparator 1 in the
logic rule.
[24] Comparator 2 Use the result of comparator 2 in the
logic rule.
[25] Comparator 3 Use the result of comparator 3 in the
logic rule.
[26] Logic rule 0 Use the result of logic rule 0 in the logic
rule.
[27] Logic rule 1 Use the result of logic rule 1 in the logic
rule.
[28] Logic rule 2 Use the result of logic rule 2 in the logic
rule.
13-02 Stop Event
Option: Function:
[29] Logic rule 3 Use the result of logic rule 3 in the logic
rule.
[30] SL Time-out 0 Use the result of timer 0 in the logic
rule.
[31] SL Time-out 1 Use the result of timer 1 in the logic
rule.
[32] SL Time-out 2 Use the result of timer 2 in the logic
rule.
[33] Digital input DI18 Use the value of DI18 in the logic rule
(High = TRUE).
[34] Digital input DI19 Use the value of DI19 in the logic rule
(High = TRUE).
[35] Digital input DI27 Use the value of DI27 in the logic rule
(High = TRUE).
[36] Digital input DI29 Use the value of DI29 in the logic rule
(High = TRUE).
[37] Digital input DI32 Use the value of DI32 in the logic rule
(High = TRUE).
[38] Digital input DI33 Use the value of DI33 in the logic rule
(High = TRUE).
[39] Start command This event is TRUE if the frequency
converter is started by any means
(either via digital input, fieldbus or
other).
[40] Drive stopped This event is TRUE if the frequency
converter is stopped or coasted by any
means (either via digital input, fieldbus
or other).
[41] Reset Trip This event is TRUE if the frequency
converter is tripped (but not trip-locked)
and the reset button is pressed.
[42] Auto Reset Trip This event is TRUE if the frequency
converter is tripped (but not trip-locked)
and an Automatic Reset is issued.
[43] OK Key This event is TRUE if the OK key on the
LCP is pressed.
[44] Reset Key This event is TRUE if the Reset key on
the LCP is pressed.
[45] Left Key This event is TRUE if the Left key on the
LCP is pressed.
[46] Right Key This event is TRUE if the Right key on
the LCP is pressed.
[47] Up Key This event is TRUE if the Up key on the
LCP is pressed.
[48] Down Key This event is TRUE if the Down key on
the LCP is pressed.
Parameter Description
VLT
®
HVAC Drive Programming Guide
94 MG.11.CA.02 - VLT
®