Operating instructions

10-12 Process Data Config Read
Option: Function:
[1834] Analog Out X42/9 [V]
[1835] Analog Out X42/11 [V]
[1850] Sensorless Readout [unit]
10-13 Warning Parameter
Range: Function:
0
*
[0 - 65535 ] View a DeviceNet-specific Warning word. One bit
is assigned to every warning. Please refer to the
DeviceNet Operating Instructions (MG.33.DX.YY)
for further information.
Bit: Meaning:
0Bus not active
1 Explicit connection timeout
2 I/O connection
3 Retry limit reached
4Actual is not updated
5 CAN bus off
6I/O send error
7 Initialisation error
8 No bus supply
9 Bus off
10 Error passive
11 Error warning
12 Duplicate MAC ID Error
13 RX queue overrun
14 TX queue overrun
15 CAN overrun
10-14 Net Reference
Read only from LCP
Option: Function:
Select the reference source in Instance 21/71 and 20/70.
[0]
*
Off Enables reference via analog/digital inputs.
[1] On Enables reference via the fieldbus.
10-15 Net Control
Read only from LCP
Option: Function:
Select the control source in Instance 21/71 and 20/70.
[0]
*
Off Enables control via analog/digital inputs.
[1] On Enable control via the fieldbus.
3.11.4 10-2* COS Filters
10-20 COS Filter 1
Range: Function:
0
*
[0 - 65535 ] Enter the value for COS Filter 1 to set up the filter
mask for the Status Word. When operating in
COS (Change-Of-State), this function filters out
bits in the Status Word that should not be sent if
they change.
10-21 COS Filter 2
Range: Function:
0
*
[0 - 65535 ] Enter the value for COS Filter 2, to set up the
filter mask for the Main Actual Value. When
operating in COS (Change-Of-State), this
function filters out bits in the Main Actual Value
that should not be sent if they change.
10-22 COS Filter 3
Range: Function:
0
*
[0 - 65535 ] Enter the value for COS Filter 3, to set up the
filter mask for PCD 3. When operating in COS
(Change-Of-State), this function filters out bits in
PCD 3 that should not be sent if they change.
10-23 COS Filter 4
Range: Function:
0
*
[0 - 65535 ] Enter the value for COS Filter 4 to set up the filter
mask for PCD 4. When operating in COS
(Change-Of-State), this function filters out bits in
PCD 4 that should not be sent if they change.
3.11.5 10-3* Parameter Access
Parameter group providing access to indexed parameters and
defining programming set-up.
10-31 Store Data Values
Option: Function:
Parameter values changed via DeviceNet are not
automatically stored in non-volatile memory. Use
this parameter to activate a function that stores
parameter values in the EEPROM non-volatile
memory, so changed parameter values will be
retained at power-down.
[0]
*
Off Deactivates the non-volatile storage function.
[1] Store all
setups
Stores all parameter values from the active set-up
in the non-volatile memory. The selection returns
to Off [0] when all values have been stored.
[2] Store all
setups
Stores all parameter values for all set-ups in the
non-volatile memory. The selection returns to Off
[0] when all parameter values have been stored.
Parameter Description
VLT
®
HVAC Drive Programming Guide
90 MG.11.CA.02 - VLT
®
is a registered Danfoss trademark
3