Operating instructions

9-28 Process Control
Option: Function:
Process control (setting of Control Word, speed
reference, and process data) is possible via either
Profibus or standard fieldbus but not both
simultaneously. Local control is always possible
via the LCP. Control via process control is possible
via either terminals or fieldbus depending on the
settings in par. 8-50 Coasting Select to
par. 8-56 Preset Reference Select.
[0] Disable Disables process control via Profibus, and enables
process control via standard fieldbus or Profibus
Master class 2.
[1]
*
Enable
cyclic
master
Enables process control via Profibus Master Class
1, and disables process control via standard
fieldbus or Profibus Master class 2.
9-53 Profibus Warning Word
Range: Function:
0
*
[0 - 65535 ] This parameter displays Profibus communication
warnings. Please refer to the Profibus Operating
Instructions for further information.
Read only
Bit: Meaning:
0 Connection with DP-master is not ok
1 Not used
2 FDLNDL (Fieldbus Data link Layer) is not ok
3 Clear data command received
4 Actual value is not updated
5 Baudrate search
6 PROFIBUS ASIC is not transmitting
7 Initialisation of PROFIBUS is not ok
8 Frequency converter is tripped
9 Internal CAN error
10 Wrong configuration data from PLC
11 Wrong ID sent by PLC
12 Internal error occured
13 Not configured
14 Timeout active
15 Warning 34 active
9-63 Actual Baud Rate
Option: Function:
This parameter displays the actual
Profibus baud rate. The Profibus
Master automatically sets the baud
rate.
[0] 9,6 kbit/s
[1] 19,2 kbit/s
[2] 93,75 kbit/s
[3] 187,5 kbit/s
9-63 Actual Baud Rate
Option: Function:
[4] 500 kbit/s
[6] 1500 kbit/s
[7] 3000 kbit/s
[8] 6000 kbit/s
[9] 12000 kbit/s
[10] 31,25 kbit/s
[11] 45,45 kbit/s
[255]
*
No baudrate found
9-65 Profile Number
Range: Function:
0
*
[0 - 0 ] This parameter contains the profile identification.
Byte 1 contains the profile number and byte 2 the
version number of the profile.
NOTE
This parameter is not visible via LCP.
9-70 Programming Set-up
Option: Function:
Select the set-up to be edited.
[0] Factory setup Uses default data. This option can be used as
a data source to return the other set-ups to a
known state.
[1] Set-up 1 Edits Set-up 1.
[2] Set-up 2 Edits Set-up 2.
[3] Set-up 3 Edits Set-up 3.
[4] Set-up 4 Edits Set-up 4.
[9]
*
Active Set-up Follows the active set-up selected in
par. 0-10 Active Set-up.
This parameter is unique to LCP and fieldbuses. See also
par. 0-11 Programming Set-up.
9-71 Profibus Save Data Values
Option: Function:
Parameter values changed via Profibus are not
automatically stored in non-volatile memory. Use
this parameter to activate a function that stores
parameter values in the EEPROM non-volatile
memory, so changed parameter values will be
retained at power-down.
[0]
*
Off Deactivates the non-volatile storage function.
[1] Store all
setups
Stores all parameter values for all set-ups in the
non-volatile memory. The selection returns to Off
[0] when all parameter values have been stored.
[2] Store all
setups
Stores all parameter values for all set-ups in the
non-volatile memory. The selection returns to Off
[0] when all parameter values have been stored.
Parameter Description
VLT
®
HVAC Drive Programming Guide
86 MG.11.CA.02 - VLT
®