Operating instructions
8-33 Parity / Stop Bits
Option: Function:
Parity and Stop Bits for the protocol
par. 8-30 Protocol using the FC Port.
For some of the protocols, not all
options will be visible. Default
depends on the protocol selected.
[0]
*
Even Parity, 1 Stop
Bit
[1] Odd Parity, 1 Stop Bit
[2] No Parity, 1 Stop Bit
[3] No Parity, 2 Stop Bits
8-34 Estimated cycle time
Range: Function:
0 ms
*
[0 - 1000000
ms]
In a noisy environments, the interface may
be blocked by due to overload of bad
frames. This parameter specifies the time
between two consecutive frames on the
network. If the interface does not detect
valid frames in that time it flushes the
receive buffer.
8-35 Minimum Response Delay
Range: Function:
Application dependent
*
[Application dependant]
8-36 Maximum Response Delay
Range: Function:
Application dependent
*
[Application dependant]
8-37 Maximum Inter-Char Delay
Range: Function:
Application dependent
*
[Application dependant]
3.9.4 8-4* Telegram Selection
8-40 Telegram Selection
Option: Function:
Enables use of freely configurable
telegrams or standard telegrams for
the FC port.
[1]
*
Standard telegram 1
[101] PPO 1
[102] PPO 2
[103] PPO 3
[104] PPO 4
[105] PPO 5
[106] PPO 6
[107] PPO 7
[108] PPO 8
[200] Custom telegram 1
8-42 PCD write configuration
Option: Function:
[0] None Select the parame-
ters to be assigned to
PCD's telegrams. The
number of available
PCDs depends on the
telegram type. The
values in PCD's will
then be written to
the selected parame-
ters as data values.
[302] Minimum Reference
[303] Maximum Reference
[312] Catch up/slow Down Value
[341] Ramp 1 Ramp up Time
[342] Ramp 1 Ramp Down Time
[351] Ramp 2 Ramp up Time
[352] Ramp 2 Ramp down Time
[380] Jog Ramp Time
[381] Quick Stop Ramp Time
[411] Motor Speed Low Limit [RPM]
[412] Motor Speed Low Limit [Hz]
[413] Motor Speed High Limit [RPM]
[414] Motor Speed High Limit [Hz]
[416] Torque Limit Motor Mode
[417] Torque Limit Generator Mode
[590] Digital & Relay Bus Control
[593] Pulse Out #27 Bus Control
[595] Pulse Out #29 Bus Control
[597] Pulse Out #X30/6 Bus Control
[653] Terminal 42 Output Bus Control
[663] Terminal X30/8 Bus Control
[673] Terminal X45/1 Bus Control
[683] Terminal X45/3 Bus Control
[890] Bus Jog 1 Speed
[891] Bus Jog 2 Speed
[1680] Fieldbus CTW 1
[1682] Fieldbus REF 1
[1685] FC Port CTW 1
[1686] FC Port REF 1
[3310] Synchronization Factor Master (M:S)
[3311] Synchronization Factor Slave (M:S)
[3401] PCD 1 Write to MCO
[3402] PCD 2 Write to MCO
[3403] PCD 3 Write to MCO
[3404] PCD 4 Write to MCO
[3405] PCD 5 Write to MCO
[3406] PCD 6 Write to MCO
[3407] PCD 7 Write to MCO
[3408] PCD 8 Write to MCO
[3409] PCD 9 Write to MCO
[3410] PCD 10 Write to MCO
Parameter Description
VLT
®
HVAC Drive Programming Guide
78 MG.11.CA.02 - VLT
®
is a registered Danfoss trademark
3