Operating instructions
8-05 End-of-Timeout Function
Option: Function:
Select the action after receiving a valid control
word following a time-out. This parameter is
active only when par. 8-04 Control Timeout
Function is set to [Set-up 1-4].
[0] Hold set-up Retains the set-up selected in par. 8-04 Control
Timeout Function and displays a warning, until
par. 8-06 Reset Control Timeout toggles. Then the
frequency converter resumes its original set-up.
[1]
*
Resume
set-up
Resumes the set-up active prior to the time-out.
8-06 Reset Control Timeout
Option: Function:
This parameter is active only when the choice Hold
set-up [0] has been selected in par. 8-05 End-of-
Timeout Function .
[0]
*
Do not
reset
Retains the set-up specified in par. 8-04 Control
Timeout Function, [Select setup 1-4] following a
control time-out.
[1] Do reset Returns the frequency converter to the original set-
up following a control word time-out. When the
value is set to Do reset [1], the frequency converter
performs the reset and then immediately reverts to
the Do not reset [0] setting.
8-07 Diagnosis Trigger
Option: Function:
This parameter has no function for
BACnet.
[0]
*
Disable
[1] Trigger on alarms
[2] Trigger alarm/warn.
3.9.2 8-1* Ctrl. Word Settings
8-10 Control Profile
Option: Function:
Select the interpretation of the control
and status words corresponding to the
installed fieldbus. Only the selections
valid for the fieldbus installed in slot A
will be visible in the LCP display.
[0]
*
FC profile
[1] PROFIdrive profile
[5] ODVA
[7] CANopen DSP 402
8-13 Configurable Status Word STW
Option: Function:
This parameter enables configuration of bits
12 – 15 in the status word.
[0] No function The input is always low.
[1]
*
Profile Default Depended on the profile set in Parameter
8-10.
[2] Alarm 68 Only The input will go high whenever Alarm 68 is
active and will go low whenever no alarm 68
is active
[3] Trip excl Alarm
68
The input will go high whenever Trip on
other Alarms then Alarm 68 is active.
[10] T18 DI status. The input will go high whenever T18 has 24V
and will go low whenever T18 has 0V
[11] T19 DI status. The input will go high whenever T19 has 24V
and will go low whenever T19 has 0V
[12] T27 DI status. The input will go high whenever T27 has 24V
and will go low whenever T27 has 0V
[13] T29 DI status. The input will go high whenever T29 has 24V
and will go low whenever T29 has 0V
[14] T32 DI status. The input will go high whenever T32 has 24V
and will go low whenever T32 has 0V
[15] T33 DI status. The input will go high whenever T33 has 24V
and will go low whenever T33 has 0V
[16] T37 DI status The input will go high whenever T37 has 0V
and will go low whenever T37 has 24V
[21] Thermal
warning
The thermal warning turns on when the
temperature exceeds the limit in the motor,
the frequency converter, the brake resistor,
or the thermistor..
[30] Brake fault
(IGBT)
Will go high when the brake IGBT is short-
circuited.
[40] Out of ref
range
If Comparator 0 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
[60] Comparator 0 If Comparator 0 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
[61] Comparator 1 If Comparator 1 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
[62] Comparator 2 If Comparator 2 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
[63] Comparator 3 If Comparator 3 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
[64] Comparator 4 If Comparator 4 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
[65] Comparator 5 If Comparator 5 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
[70] Logic Rule 0 If Logic Rule 0 is evaluated as TRUE, the input
will go high. Otherwise, it will be low.
[71] Logic Rule 1 If Logic Rule 1 is evaluated as TRUE, the input
will go high. Otherwise, it will be low.
[72] Logic Rule 2 If Logic Rule 2 is evaluated as TRUE, the input
will go high. Otherwise, it will be low.
[73] Logic Rule 3 If Logic Rule 3 is evaluated as TRUE, the input
will go high. Otherwise, it will be low.
[74] Logic Rule 4 If Logic Rule 4 is evaluated as TRUE, the input
will go high. Otherwise, it will be low.
Parameter Description
VLT
®
HVAC Drive Programming Guide
76 MG.11.CA.02 - VLT
®
is a registered Danfoss trademark
3
3