Operating instructions

[20] Above
feedback high
The feedback is above the limit set in
par. 4-57 Warning Feedback High.
[21] Thermal
warning
The thermal warning turns on when the
temperature exceeds the limit in the motor,
the frequency converter, the brake resistor,
or the thermistor.
[25] Reverse Reversing. Logic ‘1’ = relay activated, 24 V DC
when CW rotation of the motor. Logic ‘0’ =
relay not activated, no signal, when CCW
rotation of the motor.
[26] Bus OK Active communication (no time-out) via the
serial communication port.
[27] Torque limit
and stop
Use in performing a coasting stop and in
torque limit condition. If the frequency
converter has received a stop signal and is at
the torque limit, the signal is Logic ‘0’.
[28] Brake, no
warning
The brake is active and there are no
warnings.
[29] Brake ready,
no fault
The brake is ready for operation and there
are no faults.
[30] Brake fault
(IGBT)
The output is Logic ‘1’ when the brake IGBT
is short-circuited. Use this function to
protect the frequency converter if there is a
fault on the brake modules. Use the output/
relay to cut out the main voltage from the
frequency converter.
[35] External
Interlock
External Interlock function has been activa-
ted via one of the digital inputs.
[40] Out of ref
range
[41] Below
reference low
[42] Above
reference high
[45] Bus Ctrl
[46] Bus Ctrl 1 if
timeout
[47] Bus Ctrl 0 if
timeout
[55] Pulse output
[60] Comparator 0 See parameter group 13-1*. If Comparator 0
is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[61] Comparator 1 See parameter group 13-1*. If Comparator 2
is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[62] Comparator 2 See parameter group 13-1*. If Comparator 2
is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[63] Comparator 3 See parameter group 13-1*. If Comparator 3
is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[64] Comparator 4 See parameter group 13-1*. If Comparator 4
is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[65] Comparator 5 See parameter group 13-1*. If Comparator 5
is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[70] Logic Rule 0 See parameter group 13-4*. If Logic Rule 0 is
evaluated as TRUE, the output will go high.
Otherwise, it will be low.
[71] Logic Rule 1 See parameter group 13-4*. If Logic Rule 1 is
evaluated as TRUE, the output will go high.
Otherwise, it will be low.
[72] Logic Rule 2 See parameter group 13-4*. If Logic Rule 2 is
evaluated as TRUE, the output will go high.
Otherwise, it will be low.
[73] Logic Rule 3 See parameter group 13-4*. If Logic Rule 3 is
evaluated as TRUE, the output will go high.
Otherwise, it will be low.
[74] Logic Rule 4 See parameter group 13-4*. If Logic Rule 4 is
evaluated as TRUE, the output will go high.
Otherwise, it will be low.
[75] Logic Rule 5 See parameter group 13-4*. If Logic Rule 5 is
evaluated as TRUE, the output will go high.
Otherwise, it will be low.
[80] SL Digital
Output A
See par. 13-52 SL Controller Action. The input
will go high whenever the Smart Logic
Action [38] Set dig. out. A high is executed.
The input will go low whenever the Smart
Logic Action [32] Set dig. out. A low is
executed.
[81] SL Digital
Output B
See par. 13-52 SL Controller Action. The input
will go high whenever the Smart Logic
Action [39] Set dig. out. Bhigh is executed.
The input will go low whenever the Smart
Logic Action [33] Set dig. out. B low is
executed.
[82] SL Digital
Output C
See par. 13-52 SL Controller Action. The input
will go high whenever the Smart Logic
Action [40] Set dig. out. C high is executed.
The input will go low whenever the Smart
Logic Action [34] Set dig. out. C low is
executed.
[83] SL Digital
Output D
See par. 13-52 SL Controller Action. The input
will go high whenever the Smart Logic
Action [41] Set dig. out. D high is executed.
The input will go low whenever the Smart
Logic Action [35] Set dig. out. D low is
executed.
[84] SL Digital
Output E
See par. 13-52 SL Controller Action. The input
will go high whenever the Smart Logic
Action [42] Set dig. out. E high is executed.
The input will go low whenever the Smart
Logic Action [36] Set dig. out. E low is
executed.
[85] SL Digital
Output F
See par. 13-52 SL Controller Action. The input
will go high whenever the Smart Logic
Action [43] Set dig. out. F high is executed.
The input will go low whenever the Smart
Logic Action [37] Set dig. out. F low is
executed.
Parameter Description
VLT
®
HVAC Drive Programming Guide
62 MG.11.CA.02 - VLT
®
is a registered Danfoss trademark