3.5.6 3-9* Digital Pot.Meter
The digital potentiometer function allows the user to increase
or decrease the actual reference by adjusting the set-up of the
digital inputs using the functions INCREASE, DECREASE or
CLEAR. To activate the function, at least one digital input must
be set up to INCREASE or DECREASE.
3-90 Step Size
Range: Function:
0.10 %
*
[0.01 -
200.00 %]
Enter the increment size required for
INCREASE/DECREASE, as a percentage of
the synchronous motor speed, n
s
. If
INCREASE/ DECREASE is activated the
resulting reference will be increased /
decreased by the amount set in this
parameter.
3-91 Ramp Time
Range: Function:
1.00 s [0.00 -
3600.00 s]
Enter the ramp time, i.e. the time for adjust-
ment of the reference from 0% to 100% of the
specified digital potentiometer function
(INCREASE, DECREASE or CLEAR).
If INCREASE / DECREASE is activated for longer
than the ramp delay period specified in
par. 3-95 Ramp Delay the actual reference will
be ramped up / down according to this ramp
time. The ramp time is defined as the time used
to adjust the reference by the step size
specified in par. 3-90 Step Size.
3-92 Power Restore
Option: Function:
[0]
*
Off Resets the Digital Potentiometer reference to 0% after
power up.
[1] On Restores the most recent Digital Potentiometer
reference at power up.
3-93 Maximum Limit
Range: Function:
100 %
*
[-200 - 200
%]
Set the maximum permissible value for the
resultant reference. This is advisable if the
Digital Potentiometer is used for fine
tuning of the resulting reference.
3-94 Minimum Limit
Range: Function:
0 %
*
[-200 - 200
%]
Set the minimum permissible value for the
resultant reference. This is advisable if the
Digital Potentiometer is used for fine tuning
of the resulting reference.
3-95 Ramp Delay
Range: Function:
Application
dependent
*
[Applica-
tion
dependant]
Enter the delay required from activation
of the digital potentiometer function
until the frequency converter starts to
ramp the reference. With a delay of 0
ms, the reference starts to ramp as soon
as INCREASE / DECREASE is activated.
See also par. 3-91 Ramp Time.
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG.11.CA.02 - VLT
®