Operating instructions

0-79 Clock Fault
Option: Function:
Enables or disables the clock warning, when the
clock has not been set or has been reset due to a
power-down and no backup is installed. If MCB 109
is installed “enabled” is default
[0]
*
Disabled
[1] Enabled
0-81 Working Days
Array with 7 elements [0] - [6] displayed below parameter number
in display. Press OK and step between elements by means of
and
buttons on the LCP.
Option: Function:
Set for each weekday if it is a working day or a non-
working day. First element of the array is Monday. The
working days are used for Timed Actions.
[0]
*
No
[1] Yes
0-82 Additional Working Days
Array with 5 elements [0] - [4] displayed below parameter number
in display. Press OK and step between elements by means of
and
buttons on the LCP.
Range: Function:
Application
dependent
*
[Application
dependant]
Defines dates for additional
working days that normally
would be non-working days
according to
par. 0-81 Working Days.
0-83 Additional Non-Working Days
Array with 15 elements [0] - [14] displayed below parameter
number in display. Press OK and step between elements by means
of
and
buttons on the LCP.
Range: Function:
Application
dependent
*
[Application
dependant]
Defines dates for additional
working days that normally
would be non-working days
according to
par. 0-81 Working Days.
0-89 Date and Time Readout
Range: Function:
0
*
[0 - 0 ] Displays the current date and time. The date and
time is updated continuously.
The clock will not begin counting until a setting
different from default has been made in
par. 0-70 Date and Time.
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG.11.CA.02 - VLT
®
is a registered Danfoss trademark 37