Operating instructions
0-65 Personal Menu Password
Range: Function:
200
*
[0 - 999 ] Define the password for access to the My
Personal Menu via the [Quick Menu] key. If
par. 0-66 Access to Personal Menu w/o Password is
set to Full access [0], this parameter will be
ignored.
0-66 Access to Personal Menu w/o Password
Option: Function:
[0]
*
Full access Disables password defined in par. 0-65 Personal
Menu Password.
[1] Read only Prevents unauthorized editing of My Personal
Menu parameters.
[2] No access Prevents unauthorized viewing and editing of My
Personal Menu parameters.
If par. 0-61 Access to Main Menu w/o Password is set to Full
access [0], this parameter will be ignored.
3.2.8 0-7* Clock Settings
Set the time and date of the internal clock. The internal clock
can be used for e.g. Timed Actions, energy log, Trend Analysis,
date/time stamps on alarms, Logged data and Preventive
Maintenance.
It is possible to program the clock for Daylight Saving Time /
summertime, weekly working days/non-working days includ-
ing 20 exceptions (holidays etc.). Although the clock settings
can be set via the LCP, they can also be set along with timed
actions and preventative maintenance functions using the
MCT 10 software tool.
NOTE
The frequency converter has no back up of the clock
function and the set date/time will reset to default
(2000-01-01 00:00) after a power down unless a Real
Time Clock module with back up is installed. If no
module with back up is installed, it is recommended the
clock function is only used if the frequency converter is
integrated into the BMS using serial communications,
with the BMS maintaining synchronization of control
equipment clock times. In par. 0-79 Clock Fault it is
possible to program for a Warning in case clock has not
been set properly, e.g. after a power down.
NOTE
If mounting an Analog I/O MCB 109 option card, a
battery back-up of the date and time is included.
0-70 Date and Time
Range: Function:
Application
dependent
*
[Application
dependant]
Sets the date and time of the
internal clock. The format to be
used is set in par. 0-71 Date
Format and par. 0-72 Time
Format.
0-71 Date Format
Option: Function:
Sets the date format to be used in the LCP.
[0]
*
YYYY-MM-DD
[1]
*
DD-MM-YYYY
[2] MM/DD/YYYY
0-72 Time Format
Option: Function:
Sets the time format to be used in the LCP.
[0]
*
24 h
[1] 12 h
0-74 DST/Summertime
Option: Function:
Choose how Daylight Saving Time/Summertime
should be handled. For manual DST/Summertime
enter the start date and end date in par. 0-76 DST/
Summertime Start and par. 0-77 DST/Summertime
End.
[0]
*
Off
[2] Manual
0-76 DST/Summertime Start
Range: Function:
Application
dependent
*
[Application
dependant]
Sets the date and time when
summertime/DST starts. The date
is programmed in the format
selected in par. 0-71 Date
Format.
0-77 DST/Summertime End
Range: Function:
Application
dependent
*
[Application
dependant]
Sets the date and time when
summertime/DST ends. The date
is programmed in the format
selected in par. 0-71 Date
Format.
Parameter Description
VLT
®
HVAC Drive Programming Guide
36 MG.11.CA.02 - VLT
®
is a registered Danfoss trademark