Operating instructions

2.1.12 Value, Step-by-Step
Certain parameters can be changed step by step or infinitely
varying. This applies to par. 1-20 Motor Power [kW],
par. 1-22 Motor Voltage and par. 1-23 Motor Frequency.
The parameters are changed both as a group of numeric data
values and as numeric data values infinitely varying.
2.1.13 Read-out and Programming of
Indexed Parameters
Parameters are indexed when placed in a rolling stack.
Par. 15-30 Alarm Log: Error Code to par. 15-33 Alarm Log: Date
and Time contain a fault log which can be read out. Choose a
parameter, press [OK], and use the up/down navigation keys
to scroll through the value log.
Use par. 3-10 Preset Reference as another example:
Choose the parameter, press [OK], and use the up/down
navigation keys keys to scroll through the indexed values. To
change the parameter value, select the indexed value and
press [OK]. Change the value by using the up/down keys. Press
[OK] to accept the new setting. Press [CANCEL] to abort. Press
[Back] to leave the parameter.
2.1.14 Initialisation to Default Settings
Initialise the frequency converter to default settings in two
ways:
Recommended initialisation (via par. 14-22 Operation Mode)
1. Select par. 14-22 Operation Mode
2. Press [OK]
3. Select “initialisation”
4. Press [OK]
5. Cut off the mains supply and wait until the display
turns off.
6. Reconnect the mains supply - the frequency convert-
er is now reset.
7.
Change par. 14-22 Operation Mode back to Normal
Operation.
NOTE
Resets parameters selected in Personal Menu with
default factory setting.
Par. 14-22 Operation Mode initialises all except:
Par. 14-50 RFI Filter
Par. 8-30 Protocol
Par. 8-31 Address
Par. 8-32 Baud Rate
Par. 8-35 Minimum Response Delay
Par. 8-36 Maximum Response Delay
Par. 8-37 Maximum Inter-Char Delay
Par. 15-00 Operating Hours to par. 15-05 Over Volt's
Par. 15-20 Historic Log: Event to par. 15-22 Historic Log: Time
Par. 15-30 Alarm Log: Error Code to par. 15-32 Alarm Log: Time
Manual initialisation
1. Disconnect from mains and wait until the display turns off.
2a. Press [Status] - [Main Menu] - [OK] at the same time while
power up for LCP 102, Graphical Display
2b. Press [Menu] while power up for LCP 101, Numerical Display
3. Release the keys after 5 s.
4. The frequency converter is now programmed according to
default settings.
This procedure initialises all except: Par. 15-00 Operating Hours;
par. 15-03 Power Up's; par. 15-04 Over Temp's; par. 15-05 Over Volt's.
NOTE
When you carry out manual initialisation, you also reset
serial communication, par. 14-50 RFI Filter and fault log
settings.
Removes parameters selected in par. 25-00 Cascade
Controller.
NOTE
After initialisation and power cycling, the display will not
show any information until after a couple of minutes.
How to Programme
VLT
®
HVAC Drive Programming Guide
24 MG.11.CA.02 - VLT
®