Operating instructions
ALARM 32, Motor phase W missing
Motor phase W between the frequency converter and the
motor is missing.
Turn off the frequency converter and check motor phase W.
ALARM 33, Inrush fault
Too many power-ups have occurred within a short time
period. Let unit cool to operating temperature.
WARNING/ALARM 34, Fieldbus communication fault
The fieldbus on the communication option card is not
working.
WARNING/ALARM 35, Out of frequency range:
This warning is active if the output frequency has reached the
high limit (set in par. 4-53) or low limit (set in par. 4-52). In
Process Control, Closed Loop (par. 1-00) this warning is
displayed.
WARNING/ALARM 36, Mains failure
This warning/alarm is only active if the supply voltage to the
frequency converter is lost and par. 14-10 Mains Failure is NOT
set to OFF. Check the fuses to the frequency converter
ALARM 38, Internal fault
It may be necessary to contact your Danfoss supplier. Some
typical alarm messages:
0 Serial port cannot be initialized. Serious hardware failure
256-258 Power EEPROM data is defect or too old
512 Control board EEPROM data is defect or too old
513 Communication time out reading EEPROM data
514 Communication time out reading EEPROM data
515 Application Orientated Control cannot recognize the
EEPROM data
516 Cannot write to the EEPROM because a write command is
on progress
517 Write command is under time out
518 Failure in the EEPROM
519 Missing or invalid Barcode data in EEPROM
783 Parameter value outside of min/max limits
1024-
1279
A can-telegram that has to be sent, couldn't be sent
1281 Digital Signal Processor flash timeout
1282 Power micro software version mismatch
1283 Power EEPROM data version mismatch
1284 Cannot read Digital Signal Processor software version
1299 Option SW in slot A is too old
1300 Option SW in slot B is too old
1302 Option SW in slot C1 is too old
1315 Option SW in slot A is not supported (not allowed)
1316 Option SW in slot B is not supported (not allowed)
1318 Option SW in slot C1 is not supported (not allowed)
1379 Option A did not respond when calculating Platform
Version.
1380 Option B did not respond when calculating Platform
Version.
1536 An exception in the Application Orientated Control is
registered. Debug information written in LCP
1792 DSP watchdog is active. Debugging of power part data
Motor Orientated Control data not transferred correctly
2049 Power data restarted
2064-207
2
H081x: option in slot x has restarted
2080-208
8
H082x: option in slot x has issued a powerup-wait
2096-210
4
H083x: option in slot x has issued a legal powerup-wait
2304 Could not read any data from power EEPROM
2305 Missing SW version from power unit
2314 Missing power unit data from power unit
2315 Missing SW version from power unit