Operating instructions

No. Description Warning Alarm/
Trip
Alarm/Trip Lock Parameter Reference
201 Fire M was Active
202 Fire M Limits Exceeded
203 Missing Motor
204 Locked Rotor
243 Brake IGBT X X
244 Heatsink temp X X X
245 Heatsink sensor X X
246 Pwr.card supply X X
247 Pwr.card temp X X
248 Illegal PS config X X
250 New spare parts X
251 New Type Code X X
Table 4.1: Alarm/Warning code list
(X) Dependent on parameter
1) Can not be Auto reset via par. 14-20 Reset Mode
A trip is the action when an alarm has appeared. The trip will
coast the motor and can be reset by pressing the reset button
or make a reset by a digital input (parameter group 5-1* [1]).
The original event that caused an alarm cannot damage the
frequency converter or cause dangerous conditions. A trip
lock is an action when an alarm occurs, which may cause
damage to frequency converter or connected parts. A Trip
Lock situation can only be reset by a power cycling.
LED indication
Warning yellow
Alarm flashing red
Trip locked yellow and red
Troubleshooting
VLT
®
HVAC Drive Programming Guide
186 MG.11.CA.02 - VLT
®
is a registered Danfoss trademark