Operating instructions
26-53 Terminal X42/9 Bus Control
Range: Function:
0.00 %
*
[0.00 - 100.00 %] Holds the level of terminal X42/9 if
controlled by bus.
26-54 Terminal X42/9 Timeout Preset
Range: Function:
0.00 %
*
[0.00 -
100.00 %]
Holds the preset level of terminal X42/9.
In case of a bus timeout and a timeout
function is selected in par. 26-60 Terminal
X42/11 Output the output will preset to this
level.
3.24.7 26-6* Analog Out X42/11
Parameters for configuring the scaling and output function for
analog output, terminal X42/11.
26-60 Terminal X42/11 Output
Option: Function:
Set the function of terminal X42/11.
[0]
*
No operation
[100] Output freq.
0-100
: 0 - 100 Hz, (0-20 mA)
[101] Reference Min-
Max
: Minimum reference - Maximum
reference, (0-20 mA)
[102] Feedback
+-200%
: -200% to +200% of par. 20-14 Maximum
Reference/Feedb., (0-20 mA)
[103] Motor cur. 0-
Imax
: 0 - Inverter Max. Current (par. 16-37 Inv.
Max. Current), (0-20 mA)
[104] Torque 0-Tlim : 0 - Torque limit (par. 4-16 Torque Limit
Motor Mode), (0-20 mA)
[105] Torque 0-Tnom : 0 - Motor rated torque, (0-20 mA)
[106] Power 0-Pnom : 0 - Motor rated power, (0-20 mA)
[107] Speed 0-
HighLim
: 0 - Speed High Limit (par. 4-13 Motor
Speed High Limit [RPM] and
par. 4-14 Motor Speed High Limit [Hz]),
(0-20 mA)
[113] Ext. Closed Loop
1
: 0 - 100%, (0-20 mA)
[114] Ext. Closed Loop
2
: 0 - 100%, (0-20 mA)
[115] Ext. Closed Loop
3
: 0 - 100%, (0-20 mA)
[139] Bus ctrl. : 0 - 100%, (0-20 mA)
[141] Bus ctrl t.o. : 0 - 100%, (0-20 mA)
26-61 Terminal X42/11 Min. Scale
Range: Function:
0.00
%
*
[0.00 -
200.00 %]
Scale the minimum output of the selected
analog signal at terminal X42/11, as a percent-
age of the maximum signal level. E.g. if a 0 V
is desired at 25% of the maximum output
value. Then programme 25%. Scaling values
up to 100% can never be higher than the
corresponding setting in par. 26-62 Terminal
X42/11 Max. Scale.
See principle graph for par. 6-51 Terminal 42 Output Min
Scale.
26-62 Terminal X42/11 Max. Scale
Range: Function:
100.00
%
*
[0.00 -
200.00
%]
Scale the maximum output of the selected analog
signal at terminal X42/9. Set the value to the
maximum value of the voltage signal output.
Scale the output to give a voltage lower than 10V
at full scale; or 10V at an output below 100% of
the maximum signal value. If 10V is the desired
output current at a value between 0-100% of the
full-scale output, programme the percentage
value in the parameter, i.e. 50% = 10V. If a voltage
between 0 and 10V is desired at maximum
output, calculate the percentage as follows:
(
10
V
desired
maximum
voltage
)
x
100 %
i.e.
5
V
:
10
V
5
V
x
100 % = 200 %
See principle graph for par. 6-52 Terminal 42 Output Max
Scale.
26-63 Terminal X42/11 Bus Control
Range: Function:
0.00 %
*
[0.00 - 100.00 %] Holds the level of terminal X42/11 if
controlled by bus.
26-64 Terminal X42/11 Timeout Preset
Range: Function:
0.00 %
*
[0.00 - 100.00
%]
Holds the preset level of terminal
X42/11.
In case a bus time-out and a time-out
function are selected, the output will
preset to this level.
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG.11.CA.02 - VLT
®
is a registered Danfoss trademark 183
3