Operating instructions

Parameter [Units]
Par. 0-01 Language
Par. 1-20 Motor Power [kW] [kW]
Par. 1-21 Motor Power [HP] [HP]
Par. 1-22 Motor Voltage*[V]
Par. 1-23 Motor Frequency [Hz]
Par. 1-24 Motor Current [A]
Par. 1-25 Motor Nominal Speed [RPM]
Par. 1-28 Motor Rotation Check [Hz]
Par. 3-41 Ramp 1 Ramp Up Time [s]
Par. 3-42 Ramp 1 Ramp Down Time [s]
Par. 4-11 Motor Speed Low Limit [RPM] [RPM]
Par. 4-12 Motor Speed Low Limit [Hz]*[Hz]
Par. 4-13 Motor Speed High Limit [RPM] [RPM]
Par. 4-14 Motor Speed High Limit [Hz]*[Hz]
Par. 3-19 Jog Speed [RPM] [RPM]
Par. 3-11 Jog Speed [Hz]*[Hz]
Par. 5-12 Terminal 27 Digital Input
Par. 5-40 Function Relay**
Table 2.1: Quick Setup parameters
*The display showing depends on choices made in
par. 0-02 Motor Speed Unit and par. 0-03 Regional Settings. The
default settings of par. 0-02 Motor Speed Unit and
par. 0-03 Regional Settings depend on which region of the
world the frequency converter is supplied to but can be re-
programmed as required.
** Par. 5-40 Function Relay, is an array, where one may choose
between Relay1 [0] or Relay2 [1]. Standard setting is Relay1 [0]
with the default choice Alarm [9].
See the parameter description in the section Commonly Used
Parameters.
For a detailed information about settings and programming,
please see the VLT HVAC Drive Programming Guide, MG.
11.CX.YY
x=version number
y=language
NOTE
If [No Operation] is selected in par. 5-12 Terminal 27
Digital Input, no connection to +24 V on terminal 27 is
necessary to enable start.
If [Coast Inverse] (factory default value) is selected in
par. 5-12 Terminal 27 Digital Input, a connection to +24V
is necessary to enable start.
How to Programme
VLT
®
HVAC Drive Programming Guide
18 MG.11.CA.02 - VLT
®