Operating instructions
3.23 Main Menu - Cascade Controller -
Group 25
Parameters for configuring the Basic Cascade Controller for
sequence control of multiple pumps. For a more application
oriented description and wiring examples, see Chapter
Application Examples, item Basic Cascade Controller in the
Design Guide.
To configure the Cascade Controller to the actual system and
the desired control strategy, it is recommended to follow the
below sequence, starting with parameter group 25-0* System
Settings and next parameter group 25-5* Alternation Settings.
These parameter can normally be set in advance.
Parameters in 25-2* Bandwidth Settings and 25-4* Staging
settings, will often be dependent on the dynamic of the
system and final adjustment to be done at the commissioning
of the plant.
NOTE
The Cascade Controller is supposed to operate in closed
loop controlled by the built-in PI controller (Closed Loop
selected in Configuration Mode, par. 1-00 Configuration
Mode). If Open Loop is selected in par. 1-00 Configuration
Mode, all fixed speed pumps will be destaged, but the
variable speed pump will still be controlled by the
frequency converter, now as an open loop configura-
tion:
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG.11.CA.02 - VLT
®
is a registered Danfoss trademark 167