Operating instructions

24-02 Fire Mode Unit
Option: Function:
[70] mbar
[71] bar
[72] Pa
[73] kPa
[74] m WG
[75] mm Hg
[80] kW
[120] GPM
[121] gal/s
[122] gal/min
[123] gal/h
[124] CFM
[125] ft/s
[126] ft/min
[127] ft/h
[130] lb/s
[131] lb/min
[132] lb/h
[140] ft/s
[141] ft/min
[145] ft
[160] °F
[170] psi
[171] lb/in
[172] in WG
[173] ft WG
[174] in Hg
[180] HP
24-03 Fire Mode Min Reference
Range: Function:
Application
depend-
ent
*
[Applica-
tion
dependant]
Minimum value for the reference/set
point (limiting the sum of value in
par. 24-05 Fire Mode Preset Reference
and value of signal on input selected in
par. 24-06 Fire Mode Reference Source).
If running in Open loop when Fire Mode
is active, the unit is chosen by the
setting of par. 0-02 Motor Speed Unit.
For closed loop, the unit is selected in
par. 24-02 Fire Mode Unit .
24-04 Fire Mode Max Reference
Range: Function:
Application
depend-
ent
*
[Applica-
tion
dependant]
Maximum value for the reference/set
point (limiting the sum of value in
par. 24-05 Fire Mode Preset Reference
and value of signal on input selected in
par. 24-06 Fire Mode Reference Source).
If running in Open loop when Fire Mode
is active, the unit is chosen by the
setting of par. 0-02 Motor Speed Unit.
For closed loop, the unit is selected in
par. 24-02 Fire Mode Unit.
24-05 Fire Mode Preset Reference
Range: Function:
0.00 %
*
[-100.00 -
100.00 %]
Enter the required preset reference/set
point as a percentage of the Fire Mode
Max Reference set in par. 24-04 Fire Mode
Max Reference. The set value will be added
to the value represented by the signal on
the analog input selected in par. 24-06 Fire
Mode Reference Source.
24-06 Fire Mode Reference Source
Option: Function:
Select the external reference input to
be used for the Fire Mode. This signal
will be added to the value set in
par. 24-06 Fire Mode Reference Source.
[0]
*
No function
[1] Analog input 53
[2] Analog input 54
[7] Pulse input 29
[8] Pulse input 33
[20] Digital pot.meter
[21] Analog input X30/11
[22] Analog input X30/12
[23] Analog Input X42/1
[24] Analog Input X42/3
[25] Analog Input X42/5
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG.11.CA.02 - VLT
®
is a registered Danfoss trademark 163