Operating instructions

23-61 Continuous Bin Data
Range: Function:
0
*
[0 -
4294967295 ]
Array with 10 elements ([0]-[9] below parame-
ter number in display). Press OK and step
between elements by means of
and
buttons on the LCP.
10 counters with the frequency of occurrence
for the operating variable monitored, sorted
according to the following intervals:
Counter [0]: 0% - <10%
Counter [1]: 10% - <20%
Counter [2]. 20% - <30%
Counter [3]: 30% - <40%
Counter [4]: 40% - <50%
Counter [5]: 50% - <60%
Counter [6]. 60% - <70%
Counter [7]: 70% - <80%
Counter [8]. 80% - <90%
Counter [9]: 90% - <100% or Max
The above minimum limits for the intervals are
the default limits. These can be changed in
par. 23-65 Minimum Bin Value.
Starts to count when the frequency converter
is powered up for the first time. All counters
can be reset to 0 in par. 23-66 Reset Continuous
Bin Data.
23-62 Timed Bin Data
Range: Function:
0
*
[0 -
4294967295 ]
Array with 10 elements ([0]-[9] below parame-
ter number in display). Press OK and step
between elements by means of
and
buttons on the LCP.
10 counters with the frequency of occurrence
for the operating data monitored sorted
according to the intervals as for
par. 23-61 Continuous Bin Data.
Starts to count at the date/time programmed
in par. 23-63 Timed Period Start, and stops at
the time/date programmed in
par. 23-64 Timed Period Stop. All counters can
be reset to 0 in par. 23-67 Reset Timed Bin
Data.
23-63 Timed Period Start
Range: Function:
Application
dependent
*
[Application
dependant]
Set the date and time at which the
Trending starts the update of the
Timed Bin counters.
Date format will depend on setting
in par. 0-71 Date Format, and time
format on setting in par. 0-72 Time
Format.
NOTE
The frequency converter has no back up of the clock
function and the set date/time will reset to default
(2000-01-01 00:00) after a power down unless a Real
Time Clock module with back up is installed.
Consequently the logging will be stopped until date/
time is readjusted in par. 0-70 Date and Time. In
par. 0-79 Clock Fault it is possible to program for a
Warning in case clock not has been set properly, e.g.
after a power down.
NOTE
When mounting an Analog I/O MCB 109 option card, a
battery back up of the date and time is included.
23-64 Timed Period Stop
Range: Function:
Application
dependent
*
[Application
dependant]
Set the date and time at which the
Trend Analyses must stop update of
the Timed Bin counters.
Date format will depend on setting in
par. 0-71 Date Format, and time
format on setting in par. 0-72 Time
Format.
NOTE
When mounting an Analog I/O MCB 109 option card, a
battery back up of the date and time is included.
23-65 Minimum Bin Value
Range: Function:
Applica-
tion
depend-
ent
*
[Applica-
tion
depend-
ant]
Array with 10 elements ([0]-[9] below
parameter number in display). Press OK
and step between elements by means of
and
buttons on the LCP.
Set the minimum limit for each interval in
par. 23-61 Continuous Bin Data and
par. 23-62 Timed Bin Data. Example: if
selecting counter [1] and changing setting
from 10% to 12%, counter [0] will be
based on the interval 0 - <12% and
counter [1] on interval 12% - <20%.
Parameter Description
VLT
®
HVAC Drive Programming Guide
158 MG.11.CA.02 - VLT
®
is a registered Danfoss trademark