Operating instructions
23-61 Continuous Bin Data
Range: Function:
0
*
[0 -
4294967295 ]
Array with 10 elements ([0]-[9] below parame-
ter number in display). Press OK and step
between elements by means of
▲
and
▼
buttons on the LCP.
10 counters with the frequency of occurrence
for the operating variable monitored, sorted
according to the following intervals:
Counter [0]: 0% - <10%
Counter [1]: 10% - <20%
Counter [2]. 20% - <30%
Counter [3]: 30% - <40%
Counter [4]: 40% - <50%
Counter [5]: 50% - <60%
Counter [6]. 60% - <70%
Counter [7]: 70% - <80%
Counter [8]. 80% - <90%
Counter [9]: 90% - <100% or Max
The above minimum limits for the intervals are
the default limits. These can be changed in
par. 23-65 Minimum Bin Value.
Starts to count when the frequency converter
is powered up for the first time. All counters
can be reset to 0 in par. 23-66 Reset Continuous
Bin Data.
23-62 Timed Bin Data
Range: Function:
0
*
[0 -
4294967295 ]
Array with 10 elements ([0]-[9] below parame-
ter number in display). Press OK and step
between elements by means of
▲
and
▼
buttons on the LCP.
10 counters with the frequency of occurrence
for the operating data monitored sorted
according to the intervals as for
par. 23-61 Continuous Bin Data.
Starts to count at the date/time programmed
in par. 23-63 Timed Period Start, and stops at
the time/date programmed in
par. 23-64 Timed Period Stop. All counters can
be reset to 0 in par. 23-67 Reset Timed Bin
Data.
23-63 Timed Period Start
Range: Function:
Application
dependent
*
[Application
dependant]
Set the date and time at which the
Trending starts the update of the
Timed Bin counters.
Date format will depend on setting
in par. 0-71 Date Format, and time
format on setting in par. 0-72 Time
Format.
NOTE
The frequency converter has no back up of the clock
function and the set date/time will reset to default
(2000-01-01 00:00) after a power down unless a Real
Time Clock module with back up is installed.
Consequently the logging will be stopped until date/
time is readjusted in par. 0-70 Date and Time. In
par. 0-79 Clock Fault it is possible to program for a
Warning in case clock not has been set properly, e.g.
after a power down.
NOTE
When mounting an Analog I/O MCB 109 option card, a
battery back up of the date and time is included.
23-64 Timed Period Stop
Range: Function:
Application
dependent
*
[Application
dependant]
Set the date and time at which the
Trend Analyses must stop update of
the Timed Bin counters.
Date format will depend on setting in
par. 0-71 Date Format, and time
format on setting in par. 0-72 Time
Format.
NOTE
When mounting an Analog I/O MCB 109 option card, a
battery back up of the date and time is included.
23-65 Minimum Bin Value
Range: Function:
Applica-
tion
depend-
ent
*
[Applica-
tion
depend-
ant]
Array with 10 elements ([0]-[9] below
parameter number in display). Press OK
and step between elements by means of
▲
and
▼
buttons on the LCP.
Set the minimum limit for each interval in
par. 23-61 Continuous Bin Data and
par. 23-62 Timed Bin Data. Example: if
selecting counter [1] and changing setting
from 10% to 12%, counter [0] will be
based on the interval 0 - <12% and
counter [1] on interval 12% - <20%.
Parameter Description
VLT
®
HVAC Drive Programming Guide
158 MG.11.CA.02 - VLT
®
is a registered Danfoss trademark