Operating instructions
NOTE
For choices [32] - [43], see also parameter group 5-3*,
Digital Outputs and 5-4*, Relays.
23-02 OFF Time
Array [10]
Range: Function:
Application
dependent
*
[Application
dependant]
Sets the OFF time for the Timed
Action.
NOTE
The frequency converter has
no back up of the clock
function and the set date/time
will reset to default
(2000-01-01 00:00) after a
power down unless a Real
Time Clock module with back
up is installed. In
par. 0-79 Clock Fault it is
possible to program for a
Warning in case clock has not
been set properly, e.g. after a
power down.
23-03 OFF Action
Array [10]
Option: Function:
Select the action during OFF Time.
See par. 13-52 SL Controller Action for
descriptions of the options.
[0]
*
Disabled
[1]
*
No action
[2] Select set-up 1
[3] Select set-up 2
[4] Select set-up 3
[5] Select set-up 4
[10] Select preset ref 0
[11] Select preset ref 1
[12] Select preset ref 2
[13] Select preset ref 3
[14] Select preset ref 4
[15] Select preset ref 5
[16] Select preset ref 6
[17] Select preset ref 7
[18] Select ramp 1
[19] Select ramp 2
[22] Run
[23] Run reverse
[24] Stop
[26] DC Brake
[27] Coast
[32] Set digital out A low
[33] Set digital out B low
23-03 OFF Action
Array [10]
Option: Function:
[34] Set digital out C low
[35] Set digital out D low
[36] Set digital out E low
[37] Set digital out F low
[38] Set digital out A high
[39] Set digital out B high
[40] Set digital out C high
[41] Set digital out D high
[42] Set digital out E high
[43] Set digital out F high
[60] Reset Counter A
[61] Reset Counter B
[80] Sleep Mode
23-04 Occurrence
Array [10]
Option: Function:
Select which day(s) the Timed Action
applies to. Specify working/non-working
days in par. 0-81 Working Days,
par. 0-82 Additional Working Days and
par. 0-83 Additional Non-Working Days.
[0]
*
All days
[1] Working days
[2] Non-working days
[3] Monday
[4] Tuesday
[5] Wednesday
[6] Thursday
[7] Friday
[8] Saturday
[9] Sunday
23-08 Timed Actions Mode
Used to enable and disable automatic timed actions.
Option: Function:
[0]
*
Timed Actions Auto Enable timed actions.
[1] Timed Actions
Disabled
Disable timed actions, normal
operation according to control
commands.
[2] Constant On Actions Disable timed actions. Constant On
Actions activated.
[3] Constant Off Actions Disable timed actions. Constant Off
Actions activated.
23-09 Timed Actions Reactivation
Option: Function:
[0] Disabled
[1]
*
Enabled
Parameter Description
VLT
®
HVAC Drive Programming Guide
152 MG.11.CA.02 - VLT
®
is a registered Danfoss trademark
3
3