Operating instructions
3.21 Main Menu - Time-based
Functions - Group 23
3.21.1 23-0* Timed Actions
Use Timed Actions for actions needing to be performed on a
daily or weekly basis, e.g. different references for working
hours / non-working hours. Up to 10 Timed Actions can be
programmed in the frequency converter. The Timed Action
number is selected from the list when entering parameter
group 23-0* from the LCP. Par. 23-00 ON Time –
par. 23-04 Occurrence then refer to the selected Timed Action
number. Each Timed Action is divided into an ON time and an
OFF time, in which two different actions may be performed.
The actions programmed in Timed Actions are merged with
corresponding actions from digital inputs, control work via
bus and Smart Logic Controller, according to merge rules set
up in parameter group 8-5*, Digital/Bus.
NOTE
The clock (parameter group 0-7*) must be correctly
programmed for Timed Actions to function correctly.
NOTE
When mounting an Analog I/O MCB 109 option card, a
battery back up of the date and time is included.
NOTE
The PC-based Configuration Tool MCT 10 comprise a
special guide for easy programming of Timed Actions.
23-00 ON Time
Array [10]
Range: Function:
Application
dependent
*
[Application
dependant]
Sets the ON time for the Timed
Action.
NOTE
The frequency converter has
no back up of the clock
function and the set date/time
will reset to default
(2000-01-01 00:00) after a
power down unless a Real
Time Clock module with back
up is installed. In
par. 0-79 Clock Fault it is
possible to program for a
Warning in case clock has not
been set properly, e.g. after a
power down.
23-01 ON Action
Arra [10]
Option: Function:
Select the action during ON Time. See
par. 13-52 SL Controller Action for
descriptions of the options.
[0]
*
Disabled
[1] No action
[2] Select set-up 1
[3] Select set-up 2
[4] Select set-up 3
[5] Select set-up 4
[10] Select preset ref 0
[11] Select preset ref 1
[12] Select preset ref 2
[13] Select preset ref 3
[14] Select preset ref 4
[15] Select preset ref 5
[16] Select preset ref 6
[17] Select preset ref 7
[18] Select ramp 1
[19] Select ramp 2
[22] Run
[23] Run reverse
[24] Stop
[26] DC Brake
[27] Coast
[32] Set digital out A low
[33] Set digital out B low
[34] Set digital out C low
[35] Set digital out D low
[36] Set digital out E low
[37] Set digital out F low
[38] Set digital out A high
[39] Set digital out B high
[40] Set digital out C high
[41] Set digital out D high
[42] Set digital out E high
[43] Set digital out F high
[60] Reset Counter A
[61] Reset Counter B
[80] Sleep Mode
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG.11.CA.02 - VLT
®
is a registered Danfoss trademark 151