Operating instructions
NOTE
This parameter is only available when using pressure to
temperature feedback conversion.
If the choice Linear [0] is selected in par. 20-01 Feedback
1 Conversion, then the setting of any choice in
par. 20-02 Feedback 1 Source Unit does not matter as
conversion will be one-to-one.
20-03 Feedback 2 Source
Option: Function:
See par. 20-00 Feedback 1 Source for
details.
[0]
*
No function
[1] Analog input 53
[2] Analog input 54
[3] Pulse input 29
[4] Pulse input 33
[7] Analog input X30/11
[8] Analog input X30/12
[9] Analog Input X42/1
[10] Analog Input X42/3
[11] Analog Input X42/5
[15] Analog Input X48/2
[100] Bus feedback 1
[101] Bus feedback 2
[102] Bus feedback 3
20-04 Feedback 2 Conversion
Option: Function:
See par. 20-01 Feedback 1 Conver-
sion for details.
[0]
*
Linear
[1] Square root
[2] Pressure to temperature
[3] Pressure to flow
[4] Velocity to flow
20-05 Feedback 2 Source Unit
Option: Function:
See par. 20-02 Feedback 1 Source Unit for details.
20-06 Feedback 3 Source
Option: Function:
See par. 20-00 Feedback 1 Source for
details.
[0]
*
No function
[1] Analog input 53
[2] Analog input 54
[3] Pulse input 29
[4] Pulse input 33
[7] Analog input X30/11
[8] Analog input X30/12
[9] Analog Input X42/1
[10] Analog Input X42/3
20-06 Feedback 3 Source
Option: Function:
[11] Analog Input X42/5
[15] Analog Input X48/2
[100] Bus feedback 1
[101] Bus feedback 2
[102] Bus feedback 3
20-07 Feedback 3 Conversion
Option: Function:
See par. 20-01 Feedback 1 Conver-
sion for details.
[0]
*
Linear
[1] Square root
[2] Pressure to temperature
[3] Pressure to flow
[4] Velocity to flow
20-08 Feedback 3 Source Unit
Option: Function:
See par. 20-02 Feedback 1 Source Unit for details.
20-12 Reference/Feedback Unit
Option: Function:
See par. 20-02 Feedback 1 Source Unit for details.
20-13 Minimum Reference/Feedb.
Range: Function:
0.000
ProcessCtr-
lUnit
*
[Applica-
tion
depend-
ant]
Enter the desired minimum value for
the remote reference when operating
with par. 1-00 Configuration Mode set
for Closed Loop [3] operation. Units are
set in par. 20-12 Reference/Feedback
Unit.
Minimum feedback will be -200% of
either the value set in
par. 20-13 Minimum Reference/Feedb. or
in par. 20-14 Maximum Reference/
Feedb., which ever numeric value is the
highest.
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG.11.CA.02 - VLT
®
is a registered Danfoss trademark 123
3
3