Operating instructions
16-39 Control Card Temp.
Range: Function:
0 C
*
[0 - 100 C] View the temperature on the control card,
stated in °C.
16-40 Logging Buffer Full
Option: Function:
View whether the logging buffer is full (see parameter
group 15-1*). The logging buffer will never be full when
par. 15-13 Logging Mode is set to Log always [0].
[0]
*
No
[1] Yes
16-43 Timed Actions Status
View the timed actions mode.
Option: Function:
[0]
*
Timed Actions Auto
[1] Timed Actions Disabled
[2] Constant On Actions
[3] Constant Off Actions
16-49 Current Fault Source
Range: Function:
0
*
[0 - 8 ] Value indicates source of current fault, including:
short circuit, over current and phase imbalance (from
left): [1-4] Inverter, [5-8] Rectifier, [0] No fault
recorded
After a short circuit alarm (imax2) or over current alarm (imax1
or phase imbalance) this will contain the power card number
associated with the alarm. It only holds one number so it will
indicate the highest priority power card number (master first).
The value will persist on power cycle but if a new alarm occurs
it will be overwritten with the new power card number (even if
it a lower priority number). The value will only be cleared
when the alarm log is cleared (i.e. a 3-finger reset would reset
the readout to 0).
3.16.4 16-5* Ref. & Feedb.
Parameters for reporting the reference and feedback input.
16-50 External Reference
Range: Function:
0.0
*
[-200.0 - 200.0 ] View the total reference, the sum of digital,
analog, preset, bus and freeze references,
plus catch-up and slow-down.
16-52 Feedback [Unit]
Range: Function:
0.000
ProcessCtr-
lUnit
*
[-999999.999 -
999999.999
ProcessCtrlU-
nit]
View value of resulting feedback
value after processing of Feedback
1-3 (see par. 16-54 Feedback 1 [Unit],
par. 16-55 Feedback 2 [Unit] and par.
16-56) in the feedback manager.
See par. 20-0* Feedback.
The value is limited by settings in
par. 20-13 and par. 20-14. Units as
set in par. 20-12 Reference/Feedback
Unit.
16-53 Digi Pot Reference
Range: Function:
0.00
*
[-200.00 - 200.00 ] View the contribution of the Digital
Potentiometer to the actual reference.
16-54 Feedback 1 [Unit]
Range: Function:
0.000
ProcessCtrlU-
nit
*
[-999999.999 -
999999.999
ProcessCtrlUnit]
View value of Feedback 1, see par.
20-0* Feedback.
The value is limited by settings in
par. 20-13 Minimum Reference/
Feedb. and par. 20-14 Maximum
Reference/Feedb.. Units as set in
par. 20-12 Reference/Feedback
Unit.
16-55 Feedback 2 [Unit]
Range: Function:
0.000
ProcessCtrlU-
nit
*
[-999999.999 -
999999.999
ProcessCtrlUnit]
View value of Feedback 2, see
par. 20-0* Feedback.
The value is limited by settings in
par. 20-13 and par. 20-14. Units as
set in par. 20-12 Reference/
Feedback Unit.
16-56 Feedback 3 [Unit]
Range: Function:
0.000
ProcessCtrlU-
nit
*
[-999999.999 -
999999.999
ProcessCtrlUnit]
View value of Feedback 3, see
parameter group 20-0* Feedback.
The value is limited by settings in
par. 20-13 Minimum Reference/
Feedb. and par. 20-14 Maximum
Reference/Feedb.. Units as set in
par. 20-12 Reference/Feedback
Unit.
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG.11.CA.02 - VLT
®
is a registered Danfoss trademark 115