Operating instructions
3.16 Main Menu - Data Readouts -
Group 16
3.16.1 16-0* General Status
16-00 Control Word
Range: Function:
0
*
[0 - 65535 ] View the Control word sent from the frequency
converter via the serial communication port in
hex code.
16-01 Reference [Unit]
Range: Function:
0.000
Reference-
FeedbackU-
nit
*
[-999999.000 -
999999.000
ReferenceFeed-
backUnit]
View the present reference value
applied on impulse or analog
basis in the unit resulting from
the configuration selected in
par. 1-00 Configuration Mode (Hz,
Nm or RPM).
16-02 Reference [%]
Range: Function:
0.0 %
*
[-200.0 - 200.0
%]
View the total reference. The total
reference is the sum of digital, analog,
preset, bus, and freeze references, plus
catch-up and slow-down.
16-03 Status Word
Range: Function:
0
*
[0 - 65535 ] View the Status word sent from the frequency
converter via the serial communication port in
hex code.
16-05 Main Actual Value [%]
Range: Function:
0.00 %
*
[-100.00 - 100.00
%]
View the two-byte word sent with the
Status word to the bus Master report-
ing the Main Actual Value.
16-09 Custom Readout
Range: Function:
0.00 Custom-
ReadoutUnit
*
[-999999.99 -
999999.99
CustomReadou-
tUnit]
View the user-defined readouts
as defined in par. 0-30 Custom
Readout Unit, par. 0-31 Custom
Readout Min Value and
par. 0-32 Custom Readout Max
Value.
3.16.2 16-1* Motor Status
Parameters for reading the motor status values.
16-10 Power [kW]
Range: Function:
0.00
kW
*
[0.00 -
10000.00
kW]
Displays motor power in kW. The value
shown is calculated on the basis of the
actual motor voltage and motor current.
The value is filtered, and therefore approx.
30 ms may pass from when an input value
changes to when the data read-out values
change. The resolution of read-out value on
fieldbus is in 10 W steps.
16-11 Power [hp]
Range: Function:
0.00
hp
*
[0.00 -
10000.00 hp]
View the motor power in HP. The value
shown is calculated on the basis of the
actual motor voltage and motor current.
The value is filtered, and therefore approx-
imately 30 ms may pass from when an
input value changes to when the data
read-out values change.
16-12 Motor Voltage
Range: Function:
0.0 V
*
[0.0 - 6000.0 V] View the motor voltage, a calculated
value used for controlling the motor.
16-13 Frequency
Range: Function:
0.0 Hz
*
[0.0 - 6500.0 Hz] View the motor frequency, without
resonance dampening.
16-14 Motor Current
Range: Function:
0.00 A
*
[0.00 -
10000.00 A]
View the motor current measured as a
mean value, IRMS. The value is filtered,
and thus approximately 30 ms may pass
from when an input value changes to
when the data read-out values change.
16-15 Frequency [%]
Range: Function:
0.00 %
*
[-100.00 -
100.00 %]
View a two-byte word reporting the actual
motor frequency (without resonance
dampening) as a percentage (scale
0000-4000 Hex) of par. 4-19 Max Output
Frequency. Set par. 9-16 PCD Read Configu-
ration index 1 to send it with the Status
Word instead of the MAV.
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG.11.CA.02 - VLT
®
is a registered Danfoss trademark 113