Operating instructions

3.15.4 15-3* Alarm Log
Parameters in this group are array parameters, where up to 10
fault logs can be viewed. [0] is the most recent logged data,
and [9] the oldest. Error codes, values, and time stamp can be
viewed for all logged data.
15-30 Alarm Log: Error Code
Array [10]
Range: Function:
0
*
[0 - 255 ] View the error code and look up its meaning in the
Troubleshooting chapter.
15-31 Alarm Log: Value
Array [10]
Range: Function:
0
*
[-32767 - 32767 ] View an extra description of the error. This
parameter is mostly used in combination
with alarm 38 ‘internal fault’.
15-32 Alarm Log: Time
Array [10]
Range: Function:
0 s
*
[0 - 2147483647 s] View the time when the logged event
occurred. Time is measured in seconds
from frequency converter start-up.
15-33 Alarm Log: Date and Time
Range: Function:
Application
dependent
*
[Application
dependant]
Array parameter; Date & Time
0 - 9: This parameter shows at
which time the logged event
occurred.
3.15.5 15-4* Drive Identification
Parameters containing read only information about the
hardware and software configuration of the frequency
converter.
15-40 FC Type
Range: Function:
0
*
[0 - 0 ] View the FC type. The read-out is identical to the
frequency converter series power field of the type
code definition, characters 1-6.
15-41 Power Section
Range: Function:
0
*
[0 - 0 ] View the FC type. The read-out is identical to the
frequency converter series power field of the type
code definition, characters 7-10.
15-42 Voltage
Range: Function:
0
*
[0 - 0 ] View the FC type. The read-out is identical to the
frequency converter series power field of the type
code definition, characters 11-12.
15-43 Software Version
Range: Function:
0
*
[0 - 0 ] View the combined SW version (or ‘package version’)
consisting of power SW and control SW.
15-44 Ordered Typecode String
Range: Function:
0
*
[0 - 0 ] View the type code string used for re-ordering the
frequency converter in its original configuration.
15-45 Actual Typecode String
Range: Function:
0
*
[0 - 0 ] View the actual type code string.
15-46 Frequency Converter Ordering No
Range: Function:
0
*
[0 - 0 ] View the 8-digit ordering number used for re-
ordering the frequency converter in its original
configuration.
15-47 Power Card Ordering No
Range: Function:
0
*
[0 - 0 ] View the power card ordering number.
15-48 LCP Id No
Range: Function:
0
*
[0 - 0 ] View the LCP ID number.
15-49 SW ID Control Card
Range: Function:
0
*
[0 - 0 ] View the control card software version number.
15-50 SW ID Power Card
Range: Function:
0
*
[0 - 0 ] View the power card software version number.
15-51 Frequency Converter Serial Number
Range: Function:
0
*
[0 - 0 ] View the frequency converter serial number.
15-53 Power Card Serial Number
Range: Function:
0
*
[0 - 0 ] View the power card serial number.
15-59 CSIV Filename
Range: Function:
Application dependent
*
[0 - 0 ] CSIV Filename readout.
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG.11.CA.02 - VLT
®
is a registered Danfoss trademark 111
3