VLT® HVAC Drive Programming Guide Contents Contents 1 Introduction 3 1.1.1 Copyright, Limitation of Liability and Revision Rights 4 1.1.2 Approvals 4 1.1.3 Symbols 4 1.1.4 Abbreviations 5 1.1.6 Definitions 6 2 How to Programme 10 2.1 Local Control Panel 10 2.1.1 How to Operate Graphical LCP (GLCP) 10 2.1.2 How to Operate Numeric LCP (NLCP) 14 2.1.5 Quick Menu Mode 16 2.1.6 Function Set-ups 19 2.1.7 Main Menu Mode 22 3 Parameter Description 25 3.1 Parameter Selection 25 3.1.
VLT® HVAC Drive Programming Guide Contents 3.23 Main Menu - Cascade Controller - Group 25 167 3.24 Main Menu - Analog I/O Option MCB 109 - Group 26 177 4 Troubleshooting 184 4.1.1 Alarm Words 188 4.1.2 Warning Words 189 4.1.3 Extended Status Words 190 4.1.4 Fault Messages 191 5 Parameter Lists 198 5.1 Parameter Options 198 5.1.1 Default settings 198 5.1.2 0-** Operation and Display 199 5.1.3 1-** Load / Motor 201 5.1.4 2-** Brakes 202 5.1.5 3-** Reference / Ramps 202 5.1.
Introduction VLT® HVAC Drive Programming Guide 1 1 1 Introduction VLT HVAC Drive FC 100 Series Software version: 3.4.x This guide can be used with all VLT HVAC Drive frequency converters with software version 3.4.x. The actual software version number can be read from par. 15-43 Software Version. MG.11.CA.
1 1 Introduction VLT® HVAC Drive Programming Guide 1.1.1 Copyright, Limitation of Liability and Revision Rights This publication contains information proprietary to Danfoss. By accepting and using this manual the user agrees that the information contained herein will be used solely for operating equipment from Danfoss or equipment from other vendors provided that such equipment is intended for communication with Danfoss equipment over a serial communication link.
VLT® HVAC Drive Programming Guide Introduction 1.1.
1 1 VLT® HVAC Drive Programming Guide Introduction 1.1.6 Definitions PM,N Rated motor power (nameplate data in kW or HP). Frequency converter: IVLT,MAX Maximum output current. TM,N Rated torque (motor). IVLT,N Rated output current supplied by the frequency converter. UVLT, MAX Maximum output voltage. Input: Control command Start and stop the connected motor by means of LCP and digital inputs. Functions are divided into two groups. UM Instantaneous motor voltage.
Introduction VLT® HVAC Drive Programming Guide RefMAX Determines the relationship between the reference input at 100% full scale value (typically 10 V, 20mA) and the resulting reference. The maximum reference value set in par. 3-03 Maximum Reference. RefMIN Determines the relationship between the reference input at 0% value (typically 0V, 0mA, 4mA) and the resulting reference. The minimum reference value set in par. 3-02 Minimum Reference.
1 1 VLT® HVAC Drive Programming Guide Introduction FC Standard Bus Includes RS 485 bus with FC protocol or MC protocol. See par. 8-30 Protocol. The frequency converters' built-in DC coils produce a high power factor, which minimizes the imposed load on the mains supply. Thermistor: A temperature-dependent resistor placed where the temperature is to be monitored (frequency converter or motor). 1.1.7 Safety Precautions Trip A state entered in fault situations, e.g.
Introduction VLT® HVAC Drive Programming Guide Warning against unintended start 1. The motor can be brought to a stop by means of digital commands, bus commands, references or a local stop, while the frequency converter is connected to mains. If personal safety considerations (e.g. risk of personal injury caused by contact with moving machine parts following an unintentional start) make it necessary to ensure that no unintended start occurs, these stop functions are not sufficient.
2 2 VLT® HVAC Drive Programming Guide How to Programme 2 How to Programme 2.1 Local Control Panel 2.1.1 How to Operate Graphical LCP (GLCP) The following instructions are valid for the GLCP (LCP 102). The GLCP is divided into four functional groups: 1. Graphical display with Status lines. 2. Menu keys and indicator lights (LED's) - selecting mode, changing parameters and switching between display functions. 3. Navigation keys and indicator lights (LEDs). 4.
How to Programme VLT® HVAC Drive Programming Guide Several values or measurements can be linked to each of the displayed operating variables. The values / measurements to be displayed can be defined via par. 0-20 Display Line 1.1 Small, par. 0-21 Display Line 1.2 Small, par. 0-22 Display Line 1.3 Small, par. 0-23 Display Line 2 Large and par. 0-24 Display Line 3 Large, which can be accessed via [QUICK MENU], "Q3 Function Setups", "Q3-1 General Settings", "Q3-13 Display Settings".
2 2 How to Programme VLT® HVAC Drive Programming Guide GLCP keys Menu keys The menu keys are divided into functions. The keys below the display and indicator lamps are used for parameter set-up, including choice of display indication during normal operation. [Status] indicates the status of the frequency converter and/or the motor. 3 different readouts can be chosen by pressing the [Status] key: 5 line readouts, 4 line readouts or Smart Logic Control.
How to Programme VLT® HVAC Drive Programming Guide Navigation Keys The four navigation arrows are used to navigate between the different choices available in [Quick Menu], [Main Menu] and [Alarm Log]. Use the keys to move the cursor. NOTE [OK] is used for choosing a parameter marked by the cursor and for enabling the change of a parameter. [Off] stops the connected motor. The key can be selected as Enable [1] or Disable [0] via par. 0-41 [Off] Key on LCP.
2 2 How to Programme VLT® HVAC Drive Programming Guide 2.1.2 How to Operate Numeric LCP (NLCP) The following instructions are valid for the NLCP (LCP 101). The control panel is divided into four functional groups: 1. Numeric display. 2. Menu key and indicator lights (LEDs) - changing parameters and switching between display functions. 3. Navigation keys and indicator lights (LEDs). 4. Operation keys and indicator lights (LEDs).
VLT® HVAC Drive Programming Guide How to Programme Menu key [Menu] Select one of the following modes: • • • [Hand on] enables control of the frequency converter via the LCP. [Hand on] also starts the motor and it is now possible to enter the motor speed data by means of the arrow keys. The key can be selected as Enable [1] or Disable [0] via par. 0-40 [Hand on] Key on LCP. Status Quick Setup Main Menu Main Menu is used for programming all parameters.
How to Programme VLT® HVAC Drive Programming Guide 2.1.3 Quick Transfer of Parameter Settings between Multiple Frequency Converters 2 2 Once the set-up of a frequency converter is complete, we recommend that you store the data in the LCP or on a PC via MCT 10 Set-up Software Tool. Data transfer from LCP to frequency converter: 1. Go to par. 0-50 LCP Copy 2. Press the [OK] key 3. Select “All from LCP” 4.
VLT® HVAC Drive Programming Guide How to Programme Example of changing parameter data Assume parameter 22-60 is set to [Off]. However, you want to monitor the fan-belt condition - non- broken or broken according to the following procedure: Example of using the Quick Setup option: Assume you want to set the Ramp Down Time to 100 seconds: 1. Select [Quick Setup]. The first par. 0-01 Language in Quick Setup appears 2. Press [▼] repeatedly until par.
2 2 VLT® HVAC Drive Programming Guide How to Programme Parameter [Units] Par. 0-01 Language Par. 1-20 Motor Power [kW] [kW] Par. 1-21 Motor Power [HP] [HP] Par. 1-22 Motor Voltage* [V] Par. 1-23 Motor Frequency [Hz] Par. 1-24 Motor Current [A] Par. 1-25 Motor Nominal Speed [RPM] Par. 1-28 Motor Rotation Check [Hz] Par. 3-41 Ramp 1 Ramp Up Time [s] Par. 3-42 Ramp 1 Ramp Down Time [s] Par. 4-11 Motor Speed Low Limit [RPM] [RPM] Par. 4-12 Motor Speed Low Limit [Hz]* [Hz] Par.
VLT® HVAC Drive Programming Guide How to Programme 2.1.6 Function Set-ups The Function set-up provides quick and easy access to all parameters required for the majority of VLT HVAC Drive applications including most VAV and CAV supply and return fans, cooling tower fans, Primary, Secondary and Condenser Water Pumps and other pump, fan and compressor applications. 2 2 How to access Function set-up - example Illustration 2.9: Step 4: Function set-ups choices appear. Choose Q3-1 General Settings.
VLT® HVAC Drive Programming Guide How to Programme Function Set-ups parameters The Function Set-ups parameters are grouped in the following way: 2 2 Q3-1 General Settings Q3-10 Adv. Motor Settings Q3-11 Analog Output Q3-12 Clock Settings Q3-13 Display Settings Par. 1-90 Motor Thermal Protec- Par. 6-50 Terminal 42 Output Par. 0-70 Date and Time Par. 0-20 Display Line 1.1 Small tion Par. 1-93 Thermistor Source Par. 6-51 Terminal 42 Output Min Par. 0-71 Date Format Par. 0-21 Display Line 1.
VLT® HVAC Drive Programming Guide How to Programme Q3-3 Closed Loop Settings Q3-30 Single Zone Int. Set Point Q3-31 Single Zone Ext. Set Point Q3-32 Multi Zone / Adv Par. 1-00 Configuration Mode Par. 1-00 Configuration Mode Par. 1-00 Configuration Mode Par. 20-12 Reference/Feedback Unit Par. 20-12 Reference/Feedback Unit Par. 3-15 Reference 1 Source Par. 20-13 Minimum Reference/Feedb. Par. 20-13 Minimum Reference/Feedb. Par. 3-16 Reference 2 Source Par. 20-14 Maximum Reference/Feedb. Par.
2 2 How to Programme VLT® HVAC Drive Programming Guide Q3-4 Application Settings Q3-40 Fan Functions Q3-41 Pump Functions Q3-42 Compressor Functions Par. 22-60 Broken Belt Function Par. 22-20 Low Power Auto Set-up Par. 1-03 Torque Characteristics Par. 22-61 Broken Belt Torque Par. 22-21 Low Power Detection Par. 1-71 Start Delay Par. 22-62 Broken Belt Delay Par. 22-22 Low Speed Detection Par. 22-75 Short Cycle Protection Par. 4-64 Semi-Auto Bypass Set-up Par. 22-23 No-Flow Function Par.
VLT® HVAC Drive Programming Guide How to Programme 2.1.8 Parameter Selection 2.1.10 Changing a Text Value In the Main Menu mode, the parameters are divided into groups. You select a parameter group by means of the navigation keys. The following parameter groups are accessible: If the selected parameter is a text value, change the text value by means of the [▲] [▼] navigation keys. The up key increases the value, and the down key decreases the value.
2 2 VLT® HVAC Drive Programming Guide How to Programme 2.1.12 Value, Step-by-Step Par. 14-22 Operation Mode initialises all except: Par. 14-50 RFI Filter Certain parameters can be changed step by step or infinitely varying. This applies to par. 1-20 Motor Power [kW], par. 1-22 Motor Voltage and par. 1-23 Motor Frequency. The parameters are changed both as a group of numeric data values and as numeric data values infinitely varying. Par. 8-30 Protocol Par. 8-31 Address Par. 8-32 Baud Rate Par.
VLT® HVAC Drive Programming Guide Parameter Description 3 Parameter Description 3.1 Parameter Selection 3 3 3.1.1 Main Menu Structure Parameters for the frequency converter are grouped into various parameter groups for easy selection of the correct parameters for optimized operation of the frequency converter. The vast majority of VLT HVAC Drive applications can be programmed using the Quick Menu button and selecting the parameters under Quick Setup and Function Setups.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 0-01 Language 3.2 Main Menu - Operation and Display - Group 0 Parameters related to the fundamental functions of the frequency converter, function of the LCP buttons and configuration of the LCP display. Option: Function: [48] Polski Part of Language package 1 [49] Russian Part of Language package 1 [50] Thai Part of Language package 2 [51] Bahasa Indonesia Part of Language package 2 [52] Hrvatski 3.2.
VLT® HVAC Drive Programming Guide Parameter Description 0-04 Operating State at Power-up Option: Function: Select the operating mode upon reconnection of the frequency converter to mains voltage after power down when operating in Hand (local)mode. [0] * Resume Resumes operation of the frequency converter maintaining the same local reference and the same start/stop condition (applied by [Hand On]/ [Off] on the LCP or Hand Start via a digital input as before the frequency converter was powered down.
Parameter Description VLT® HVAC Drive Programming Guide 0-11 Programming Set-up 0-12 This Set-up Linked to Option: Option: Function: Function: Select the set-up to be edited (i.e. program- par. 0-12 This Set-up Linked to to Set-up 1 [1]. This med) during operation; either the active set-up will start the linking (synchronising) process. or one of the inactive set-ups. The set-up 3 3 number being edited is displayed in the LCP in (brackets).
VLT® HVAC Drive Programming Guide Parameter Description 0-13 Readout: Linked Set-ups 0-20 Display Line 1.1 Small Array [5] Option: Range: 0* [0 - [38] Function: Function: Display Text 2 read via serial communication. 255 ] par. 0-12 This Set-up Linked to. The parameter has one index for each parameter set-up.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 0-20 Display Line 1.1 Small 0-20 Display Line 1.1 Small Option: Option: [1609] Function: Custom View the user-defined readouts as Readout defined in par. 0-30 Custom Readout Unit, par. 0-31 Custom Readout Min Value and par. 0-32 Custom Readout Max Value. [1610] Power [kW] Actual power consumed by the motor in kW. [1611] Power [hp] [1636] [1637] [1638] Actual power consumed by the motor in HP. [1639] Function: Inv. Nom.
VLT® HVAC Drive Programming Guide Parameter Description 0-20 Display Line 1.1 Small 0-20 Display Line 1.1 Small Option: Option: [1669] [1670] [1671] Function: Pulse Output Actual value of pulses applied to #27 [Hz] terminal 27 in digital output mode. Pulse Output Actual value of pulses applied to #29 [Hz] terminal 29 in digital output mode. Relay Output View the setting of all relays.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 0-20 Display Line 1.1 Small 0-25 My Personal Menu Option: Array [20] [2581] [3110] Function: Pump Status Status for the operation of each individ- Range: ual pump controlled by the Cascade Application Controller depend- Function: [0 - Define up to 20 parameters to appear in 9999 ] the Q1 Personal Menu, accessible via the ent* Bypass Status [Quick Menu] key on the LCP.
VLT® HVAC Drive Programming Guide Parameter Description The relation will depend on the type of unit selected in par.
Parameter Description VLT® HVAC Drive Programming Guide 3.2.5 0-4* LCP Keypad 0-37 Display Text 1 Range: 0* Function: [0 - In this parameter it is possible to write an individual text 0] string for display in the LCP or to be read via serial communication. If to be displayed permanently select 3 3 Display Text 1 in par. 0-20 Display Line 1.1 Small, par. 0-21 Display Line 1.2 Small, par. 0-22 Display Line 1.3 Small, par. 0-23 Display Line 2 Large or par.
VLT® HVAC Drive Programming Guide Parameter Description 0-42 [Auto on] Key on LCP 0-50 LCP Copy Option: Option: [0] Function: Disabled No function [3] Function: Size indep. Copies only the parameters that are independ- from LCP ent of the motor size. The latter selection can be [1] * Enabled [Auto on] Key is enabled [2] Avoid unauthorized start in Auto mode. ers with the same function without disturbing If par. 0-42 [Auto on] Key on LCP is motor data which are already set.
VLT® HVAC Drive Programming Guide Parameter Description 0-65 Personal Menu Password 0-70 Date and Time Range: Range: 200* Function: [0 - 999 ] Define the password for access to the My Personal Menu via the [Quick Menu] key. If 3 3 Application dependent* Function: [Application dependant] used is set in par. 0-71 Date set to Full access [0], this parameter will be Format and par. 0-72 Time ignored. Format.
VLT® HVAC Drive Programming Guide Parameter Description 0-79 Clock Fault Option: Function: Enables or disables the clock warning, when the clock has not been set or has been reset due to a power-down and no backup is installed. If MCB 109 3 3 is installed “enabled” is default [0] * Disabled [1] Enabled 0-81 Working Days Array with 7 elements [0] - [6] displayed below parameter number in display. Press OK and step between elements by means of ▲ and ▼ buttons on the LCP.
3 3 Parameter Description VLT® HVAC Drive Programming Guide 1-03 Torque Characteristics 3.3 Main Menu - Load and Motor Group 1 Option: Function: 15Hz but in addition the AEO feature will adapt the voltage exactly to the current load situation, thereby reducing energy consumption and 3.3.1 1-0* General Settings audible noise from the motor. To obtain optimal performance, the motor power factor cos phi Define whether the frequency converter operates in open loop or closed loop.
VLT® HVAC Drive Programming Guide Parameter Description 3.3.2 1-2* Motor Data NOTE Parameter group 1-2* comprises input data from the nameplate on the connected motor. This parameter cannot be adjusted while the motor is running. 1-24 Motor Current NOTE Range: Changing the value of these parameters affects the setting of other parameters. Application dependent* Function: [Application dependant] Enter the nominal motor current value from the motor nameplate data.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 3.3.3 1-3* Adv. Motor Data Mains power must be removed before disconnecting motor phase cables. 1-29 Automatic Motor Adaptation (AMA) Option: Function: The AMA function optimizes dynamic motor performance by automatically optimizing the advanced motor parameters par. 1-30 Stator Resistance (Rs) to par. 1-35 Main Reactance (Xh)) while the motor is stationary.
VLT® HVAC Drive Programming Guide Parameter Description 1-35 Main Reactance (Xh) 1-39 Motor Poles Range: Range: Applica- Function: [Applica- tion tion depend- depend- ent* ant] Function: Set the main reactance of the motor using depend- This parameter cannot be adjusted while the one of these methods: ent* motor is running. 1. Run an AMA on a cold motor. The frequency converter will 3 3 3.3.4 1-5* Load Indep. Setting measure the value from the motor. 2.
VLT® HVAC Drive Programming Guide Parameter Description 1-58 Flystart Test Pulses Current 1-61 High Speed Load Compensation Range: Range: 30 %* Function: [0 - 200 Control the percentage of the magnetizing %] 100 %* [0 - 300 Enter the % value to compensate voltage in current for the pulses used to detect the motor 3 3 Function: %] relation to load when the motor is running at direction. Reducing this value will reduce the high speed and obtain the optimum U/f charac- generated torque.
VLT® HVAC Drive Programming Guide Parameter Description 3.3.6 1-7* Start Adjustments 1-82 Min Speed for Function at Stop [Hz] Range: Parameters for setting special motor start features. Range: 0.0 s* Application dependent* 1-71 Start Delay Function: [Application Set the output frequency at dependant] which to activate par. 1-80 Function at Stop. Function: [0.0 - 120.0 s] 3 3 The function selected in par. 1-80 Function at Stop is active in the delay period. 3.3.
3 3 VLT® HVAC Drive Programming Guide Parameter Description NOTE 1-90 Motor Thermal Protection This parameter is only available if par. 0-02 Motor Speed Unit is set to [RPM]. Option: [4] * ETR trip 1 [5] 1-87 Trip Speed Low [Hz] Range: Application dependent* [6] ETR trip 2 If the Trip Speed is set to 0, the function is not active.
Parameter Description VLT® HVAC Drive Programming Guide 1-93 Thermistor Source Option: In order to maintain PELV, all connections made to the control terminals must be PELV, e.g. thermistor must be reinforced/ double insulated Function: Select the input to which the thermistor (PTC sensor) should be connected. An analog input option [1] or [2] cannot be selected if the analog input is already in use NOTE as a reference source (selected in Danfoss recommends using 24 VDC as thermistor supply voltage.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 2-03 DC Brake Cut In Speed [RPM] 3.4 Main Menu - Brakes - Group 2 Range: Function: Application 3.4.1 2-0* DC-Brakes [Application dependent* Set the DC brake cut-in speed dependant] for activation of the DC braking current set in par. 2-01 DC Brake Current, upon a stop command. Parameter group for configuring the DC brake and DC hold functions.
VLT® HVAC Drive Programming Guide Parameter Description 2-12 Brake Power Limit (kW) 2-15 Brake Check Range: Option: Function: Application dependent* Function: [Application Set the monitoring limit of the brake dependant] Select type of test and monitoring function to power transmitted to the resistor. check the connection to the brake resistor, or The monitoring limit is a product of whether a brake resistor is present, and then the maximum duty cycle (120 sec.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 2-17 Over-voltage Control 3-04 Reference Function Option: Option: Function: Over-voltage control (OVC) reduces the risk of the Function: [0] * Sum frequency converter tripping due to an over voltage on the DC link caused by generative power from the load. [0] [1] External/ Use either the preset or the external Preset reference source. Disabled No OVC required. [2] * Enabled Sums both external and preset reference sources.
VLT® HVAC Drive Programming Guide Parameter Description 3 3 3-11 Jog Speed [Hz] Range: Function: Application dependent* [Application dependant] The jog speed is a fixed output speed at which the frequency converter is running when the jog function is activated. See also par. 3-80 Jog Ramp Time. [Application Application dependent* 3-15 Reference 1 Source dependant] Option: 3-13 Reference Site Option: Function: Select the reference input to be used for the first reference signal.
VLT® HVAC Drive Programming Guide Parameter Description 3-16 Reference 2 Source Option: 3-17 Reference 3 Source Function: Option: Select the reference input to be used for the second reference signal. 3 3 Function: [32] Ext. Closed Loop 3 par. 3-15 Reference 1 Source, 3-19 Jog Speed [RPM] par. 3-16 Reference 2 Source and Range: par. 3-17 Reference 3 Source define up to three different reference signals.
VLT® HVAC Drive Programming Guide Parameter Description NOTE 3-47 Ramp 1 S-ramp Ratio at Decel. Start If S-ramp [1] is selected and the reference during ramping is changed the ramp time may be prolonged in order to realize a jerk free movement which may result in a longer start or stop time. Additional adjustment of the S-ramp ratios or switching initiators may be necessary. Range: 50 %* Function: [Application dependant] Enter the proportion of the total rampdown time (par.
VLT® HVAC Drive Programming Guide Parameter Description 3-55 Ramp 2 S-ramp Ratio at Accel. Start 3-80 Jog Ramp Time Range: Range: 50 %* Function: [Application dependant] Function: Enter the proportion of the total ramp-up depend- signal via the control panel, a selected digital time (par. 3-51 Ramp 2 Ramp up Time) in ent* input, or the serial communication port. which the acceleration torque increases. 3 3 par . 3 − 80 = The larger the percentage value, the tjog × nnorm par .
VLT® HVAC Drive Programming Guide Parameter Description Par . 3 − 81 = tQstop s x ns RPM Δ jog ref ( par . 3 − 19) RPM 3-95 Ramp Delay Range: Application 3.5.6 3-9* Digital Pot.Meter Function: [Applica- dependent* tion dependant] The digital potentiometer function allows the user to increase or decrease the actual reference by adjusting the set-up of the digital inputs using the functions INCREASE, DECREASE or CLEAR.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 4-13 Motor Speed High Limit [RPM] 3.6 Main Menu - Limits/Warnings Group 4 3.6.1 4-1* Motor Limits Range: Application Function: [Application ent* dependant] be set to correspond to the manufacturSpeed High Limit must exceed the Function: Selects the motor speed direction required. Use this parameter to prevent unwanted reversing. Clockwise Only operation in clockwise direction will be allowed.
VLT® HVAC Drive Programming Guide Parameter Description NOTE 4-19 Max Output Frequency Max. output frequency cannot exceed 10% of the inverter switching frequency (par. 14-01 Switching Frequency). 4-16 Torque Limit Motor Mode Range: Range: Applica- Function: [1.0 - Enter the maximum output frequency tion 1000.0 value. Par.
VLT® HVAC Drive Programming Guide Parameter Description 4-51 Warning Current High 4-56 Warning Feedback Low Range: Range: Application dependent* Function: [Application Enter the IHIGH value. When the motor dependant] 3 3 ProcessCtrlU- display reads CURRENT HIGH. The nit* limit, the display reads Feedb Low. The signal outputs can be programmed to produce a status or 29 and on relay output 01 or 02. signal on terminal 27 or 29 and on Refer to the drawing in this section. relay output 01 or 02.
VLT® HVAC Drive Programming Guide Parameter Description frequencies registered when pressing OK will be stored in par. 4-60 Bypass Speed From [RPM] or par. 4-61 Bypass Speed From [Hz]. 4-61 Bypass Speed From [Hz] Array [4] Range: Function: Application dependent* [Application dependant] 6. Some systems call for avoiding When the motor has ramped down to stop, press OK. The par. 4-64 Semi-Auto Bypass Set-up will automatically reset to Off.
3 3 Parameter Description VLT® HVAC Drive Programming Guide 3.7.2 5-1* Digital Inputs 3.7 Main Menu - Digital In/Out - Group 5 3.7.1 5-0* Digital I/O Mode Parameters for configuring the input and output using NPN and PNP. Parameters for configuring the input functions for the input terminals. The digital inputs are used for selecting various functions in the frequency converter.
VLT® HVAC Drive Programming Guide Parameter Description 3.7.3 5-1* Digital Inputs continued par. 22-00 External Interlock Delay, External Interlock Time. After applying a signal to the All = Terminals 18, 19, 27, 29, 32, 33, X30/2, X30/3, X30/4. X30/ are the terminals on MCB 101. input, the reaction described above will be Functions dedicated to only one digital input are stated in the associated parameter. delayed with the time set in par. 22-00 External Interlock Delay.
Parameter Description VLT® HVAC Drive Programming Guide NOTE change always follows ramp 2 (par. 3-51 Ramp 2 Ramp Up Time and par. 3-52 Ramp 2 Ramp Down If no Run Permissive signal is applied but either Run, Jog or Freeze commands is activated, the status line in the display will show either Run Requested, Jog Requested or Freeze Requested. Time) in the range 0 - par. 1-23 Motor Frequency. NOTE When Freeze output is active, the frequency converter cannot be stopped via a low ‘start [13]’ signal.
Parameter Description VLT® HVAC Drive Programming Guide 3.7.4 5-3* Digital Outputs 5-10 Terminal 18 Digital Input Same options and functions as 5-1*, except for Pulse input. Option: [8] * Function: Start 5-11 Terminal 19 Digital Input Same options and functions as 5-1*, except for Pulse input. Option: [0] * Function: Parameters for configuring the output functions for the output terminals. The 2 solid-state digital outputs are common for terminals 27 and 29.
3 3 Parameter Description VLT® HVAC Drive Programming Guide [20] Above The feedback is above the limit set in feedback high par. 4-57 Warning Feedback High. [21] Thermal warning [25] Reverse The thermal warning turns on when the temperature exceeds the limit in the motor, [65] Comparator 5 [70] Logic Rule 0 high. Otherwise, it will be low. evaluated as TRUE, the output will go high. or the thermistor. Otherwise, it will be low. Reversing.
Parameter Description VLT® HVAC Drive Programming Guide [160] No alarm The output is high when no alarm is present. [161] Running The output is high when the frequency ted again before a new start is initiated and the frequency converter speed is zero during converter is running counter clockwise (the the receiving of start signal. Par. 1-71 Start logical product of the status bits ‘running’ AND ‘reverse’). Delay can be used in order to delay the motor start.
VLT® HVAC Drive Programming Guide Parameter Description Setting in Par. 5-3* Setting in par. 25-06 Number of Pumps [0] No [200] Pump 1 [1] Yes Controlled by RELAY1 Frequency Converter Running controlled [201] Pump 2 Controlled by RELAY2 Controlled by RELAY1 Running 3 3 5-40 Function Relay Array [8] (Relay 1 [0], Relay 2 [1] Option MCB 105: Relay 7 [6], Relay 8 [7] and Relay 9 [8]). Select options to define the function of the relays.
VLT® HVAC Drive Programming Guide Parameter Description 5-40 Function Relay 5-42 Off Delay, Relay Array [8] Array [9] (Relay 1 [0], Relay 2 [1], Relay 3 [2], Relay 4 [3], Relay 5 [4], (Relay 1 [0], Relay 2 [1] Relay 6 [5], Relay 7 [6], Relay 8 [7], Relay 9 [8]) Option MCB 105: Relay 7 [6], Relay 8 [7] and Relay 9 [8]). Select options to define the function of the relays. The selection of each mechanical relay is realised in an array Range: 0.01 s* Function: [0.01 - 600.
VLT® HVAC Drive Programming Guide Parameter Description 5-51 Term. 29 High Frequency 5-57 Term. 33 Low Ref./Feedb. Value Range: Range: 100 Hz* Function: [0 - 110000 Enter the high frequency limit Hz] corresponding to the high motor shaft 3 3 0.000* Function: [-999999.999 - Enter the low reference value [RPM] 999999.999 ] for the motor shaft speed. This is also speed (i.e. high reference value) in the low feedback value, see also par. 5-53 Term. 29 High Ref./Feedb. par. 5-52 Term.
VLT® HVAC Drive Programming Guide Parameter Description Options for readout output variables: 5-66 Terminal X30/6 Pulse Output Variable Select the variable for read-out on terminal X30/6. [0] No operation This parameter cannot be adjusted while the motor is running. [45] Bus ctrl. This parameter is active when option module MCB 101 is installed [48] Bus ctrl., timeout in the frequency converter. [100] Output frequency Same options and functions as parameter group 5-6*.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 3.7.8 5-9*Bus Controlled 5-96 Pulse Out #29 Timeout Preset Range: This parameter group selects digital and relay outputs via a fieldbus setting. 0.00 %* Function: [0.00 - 100.
VLT® HVAC Drive Programming Guide Parameter Description 6-01 Live Zero Timeout Function 3.8 Main Menu - Analog In/Out - Group 6 Option: Function: [0] * Off [1] Freeze output 3.8.1 6-0* Analog I/O Mode Parameter group for setting up the analog I/O configuration. The frequency converter is equipped with 2 analog inputs: Terminal 53 and 54. The analog inputs can freely be allocated to either voltage (0 - 10 V) or current input (0/4 - 20 mA) [2] Stop [3] Jogging [4] 3 3 Max.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 3.8.2 6-1* Analog Input 1 6-16 Terminal 53 Filter Time Constant Range: Parameters for configuring the scaling and limits for analog input 1 (terminal 53). Function: 0.001 s* [0.001 10.000 s] Enter the time constant. This is a first-order digital low pass filter time constant for suppressing electrical noise in terminal 53.
VLT® HVAC Drive Programming Guide Parameter Description 3.8.4 6-3* Analog Input 3 MCB 101 6-23 Terminal 54 High Current Range: Function: 20.00 mA* [Application dependant] Enter the high current value corresponding to the high reference/ feedback value set in par. 6-25 Terminal 54 High Ref./Feedb. Value. Parameter group for configuring the scale and limits for analog input 3 (X30/11) placed on option module MCB 101. 6-30 Terminal X30/11 Low Voltage Range: 0.07 V* 6-24 Terminal 54 Low Ref./Feedb.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 3.8.5 6-4* Analog Input 4 MCB 101 3.8.6 6-5* Analog Output 1 Parameter group for configuring the scale and limits for analog input 4 (X30/12) placed on option module MCB 101. Parameters for configuring the scaling and limits for analog output 1, i.e. Terminal 42. Analog outputs are current outputs: 0/4 – 20 mA.
VLT® HVAC Drive Programming Guide Parameter Description 6-50 Terminal 42 Output Option: Function: [139] Bus ctrl. 0 - 100%, (0-20 mA) [140] Bus ctrl. 4-20 mA 0 - 100% [141] Bus ctrl t.o. 0 - 100%, (0-20 mA) [142] Bus ctrl t.o. 0 - 100% [143] Ext. CL 1 4-20mA 0 - 100% [144] Ext. CL 2 4-20mA 0 - 100% [145] Ext.
3 3 VLT® HVAC Drive Programming Guide Parameter Description EXAMPLE 3: Variable value= REFERENCE, range= Min ref - Max ref Range needed for output= Min ref (0%) - Max ref (100%), 0-10 mA Output signal 0 or 4 mA is needed at Min ref - set par. 6-51 Terminal 42 Output Min Scale to 0% Output signal 10 mA is needed at Max ref (100% of range) - set par. 6-52 Terminal 42 Output Max Scale to 200% (20 mA / 10 mA x 100%=200%). 6-61 Terminal X30/8 Min. Scale Range: Function: 0.00 %* [0.
VLT® HVAC Drive Programming Guide Parameter Description 8-03 Control Timeout Time 3.9 Main Menu - Communications and Options - Group 8 3.9.1 8-0* General Settings Range: Application Function: [1.0 - Enter the maximum time expected to pass 18000.0 s] between the reception of two consecutive depend- telegrams. If this time is exceeded, it ent* indicates that the serial communication has stopped. The function selected in 8-01 Control Site par.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 8-05 End-of-Timeout Function 8-13 Configurable Status Word STW Option: Option: Function: This parameter enables configuration of bits Select the action after receiving a valid control 12 – 15 in the status word. word following a time-out. This parameter is [0] active only when par. 8-04 Control Timeout [0] Function is set to [Set-up 1-4]. [1] * Profile Default Depended on the profile set in Parameter 8-10.
VLT® HVAC Drive Programming Guide Parameter Description 8-13 Configurable Status Word STW 8-30 Protocol Option: Option: Function: [75] Logic Rule 5 If Logic Rule 5 is evaluated as TRUE, the input [2] will go high. Otherwise, it will be low. [80] SL Digital Output A Modbus Communication according to the Modbus RTU RTU protocol as described in the VLT HVAC Drive Design Guide, RS485 Installation and Set-up . SL Controller Action.
VLT® HVAC Drive Programming Guide Parameter Description 8-33 Parity / Stop Bits 8-42 PCD write configuration Option: Function: Option: Parity and Stop Bits for the protocol 3 3 [0] None ters to be assigned to For some of the protocols, not all PCD's telegrams. The options will be visible. Default number of available depends on the protocol selected. PCDs depends on the telegram type.
VLT® HVAC Drive Programming Guide Parameter Description 8-43 PCD read configuration Option: [0] None 8-43 PCD read configuration Function: Option: Select the parameters to be [1668] Freq. Input #33 [Hz] assigned to PCD's of the [1669] Pulse Output #27 [Hz] telegrams. The number of [1670] Pulse Output #29 [Hz] available PCDs depends on [1671] Relay Output [bin] the telegram type. PCDs [1672] Counter A contain the actual data values [1673] Counter B of the selected parameters.
3 3 Parameter Description VLT® HVAC Drive Programming Guide 3.9.5 8-5* Digital/Bus 8-53 Start Select Option: Parameters for configuring the control word Digital/Bus merging. Select control of the frequency converter start function via the terminals (digital input) and/or via the fieldbus. 8-50 Coasting Select Option: Function: [0] Select control of the coasting function via the terminals (digital input) and/or via the bus.
VLT® HVAC Drive Programming Guide Parameter Description 8-55 Set-up Select NOTE Option: This parameter is active only when par. 8-30 Protocol is set to [9] FC Option. Function: Select control of the frequency converter set-up selection via the terminals (digital input) and/or 8-73 MS/TP Max Info Frames via the fieldbus. [0] Digital Activates the set-up selection via a digital input. input [1] Bus Activates the set-up selection via the serial communication port or fieldbus option.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 8-82 Slave Messages Rcvd Range: 0* Function: [0 - 0 ] This parameter shows the number of valid telegrams addressed to the slave, sent by the frequency converter. 8-83 Slave Error Count Range: 0* Function: [0 - 0 ] This parameter shows the number of error telegrams, which could not be executed by the frequency converter. 8-84 Slave Messages Sent Range: Function: 0* [0 - 0 ] 8-85 Slave Timeout Errors Range: Function: 0* [0 - 0 ] 3.9.
Parameter Description VLT® HVAC Drive Programming Guide 9-15 PCD Write Configuration 3.10 Main Menu - Profibus - Group 9 Array [10] Option: 9-15 PCD Write Configuration [2653] Terminal X42/9 Bus Control Array [10] [2663] Terminal X42/11 Bus Control Option: Function: Select the parameters to be assigned to PCD 3 to 10 of the telegrams. The Array [10] Option: number of available PCDs depends on the telegram assigned to PCD 3 to 10 of the type. The values in PCD 3 telegrams.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 9-16 PCD Read Configuration 9-22 Telegram Selection Array [10] Option: Option: Function: Select a standard Profibus telegram Function: [1654] Feedback 1 [Unit] configuration for the frequency [1655] Feedback 2 [Unit] converter, as an alternative to using the freely configurable telegrams in [1656] Feedback 3 [Unit] par. 9-15 PCD Write Configuration [1660] Digital Input and par.
Parameter Description VLT® HVAC Drive Programming Guide 9-23 Parameters for Signals 9-23 Parameters for Signals Array [1000] Array [1000] Option: Function: Option: Function: [895] Bus Feedback 2 [1676] Analog In X30/12 [896] Bus Feedback 3 [1677] Analog Out X30/8 [mA] [1500] Operating Hours [1680] Fieldbus CTW 1 [1501] Running Hours [1682] Fieldbus REF 1 [1502] kWh Counter [1684] Comm.
VLT® HVAC Drive Programming Guide Parameter Description 9-28 Process Control 9-63 Actual Baud Rate Option: Option: Function: 3 3 Process control (setting of Control Word, speed [4] 500 kbit/s reference, and process data) is possible via either [6] 1500 kbit/s Profibus or standard fieldbus but not both [7] 3000 kbit/s simultaneously. Local control is always possible [8] 6000 kbit/s via the LCP.
Parameter Description VLT® HVAC Drive Programming Guide 9-72 ProfibusDriveReset 9-90 Changed Parameters (1) Option: Array [116] Function: No LCP access [0] * No action [1] [3] Power-on Resets frequency converter upon power-up, as reset for power-cycle.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 10-07 Readout Bus Off Counter 3.11 Main Menu - CAN Fieldbus - Group 10 Range: 0* Function: [0 - 255 ] View the number of Bus Off events since the last power-up. 3.11.1 10-** DeviceNet and CAN Fieldbus 3.11.3 10-1* DeviceNet Parameter group for DeviceNet CAN fieldbus parameters. Parameters specific to the DeviceNet fieldbus. 3.11.
VLT® HVAC Drive Programming Guide Parameter Description 10-11 Process Data Config Write 10-12 Process Data Config Read Option: Function: Option: [381] Quick Stop Ramp Time [1613] Frequency [382] Starting Ramp Up Time [1614] Motor Current [411] Motor Speed Low Limit [RPM] [1615] Frequency [%] [413] Motor Speed High Limit [RPM] [1616] Torque [Nm] [416] Torque Limit Motor Mode [1617] Speed [RPM] [417] Torque Limit Generator Mode [1618] Motor Thermal [590] Digital & Relay Bus Control
3 3 VLT® HVAC Drive Programming Guide Parameter Description 3.11.4 10-2* COS Filters 10-12 Process Data Config Read Option: Function: 10-20 COS Filter 1 [1834] Analog Out X42/9 [V] Range: [1835] Analog Out X42/11 [V] [1850] Sensorless Readout [unit] 0* mask for the Status Word.
VLT® HVAC Drive Programming Guide Parameter Description 10-33 Store Always 11-18 LonWorks Revision Option: Range: Function: [0] * Off Deactivates non-volatile storage of data. [1] 0* Function: [0 - 0 ] This parameter contains the software version of the application program on the Neuron C chip on the On Stores parameter data received via DeviceNet in LON option. EEPROM non-volatile memory as default. 3 3 11-21 Store Data Values 3.
3 3 Parameter Description VLT® HVAC Drive Programming Guide 3.13.2 13-0* SLC Settings 3.13 Main Menu - Smart Logic - Group 13 3.13.1 13-** Prog. Features Prog. Features Smart Logic Control (SLC) is essentially a sequence of user defined actions (see par. 13-52 SL Controller Action [x]) executed by the SLC when the associated user defined event (see par. 13-51 SL Controller Event [x]) is evaluated as TRUE by the SLC. Events and actions are each numbered and linked together in pairs.
VLT® HVAC Drive Programming Guide Parameter Description 13-01 Start Event Option: [18] Reversing 13-01 Start Event Function: Option: See parameter group 5-3* for further [42] Auto Reset Trip description. [19] Warning Alarm (trip) Alarm (trip lock) [43] [23] Comparator 0 Comparator 1 Comparator 2 Comparator 3 [26] [27] [28] Logic rule 0 Logic rule 1 Logic rule 2 Logic rule 3 Use the result of logic rule 1 in the logic rule.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 13-02 Stop Event Option: [6] Current limit 13-02 Stop Event Function: Option: See parameter group 5-3* for further [29] Logic rule 3 description. [7] [8] Out of current See parameter group 5-3* for further range description.
VLT® HVAC Drive Programming Guide Parameter Description 13-02 Stop Event 13-10 Comparator Operand Option: [50] [51] [60] [61] Function: Comparator 4 Array [4] Use the result of comparator 4 in the Comparator 5 Logic rule 4 Logic rule 5 Use the result of comparator 5 in the the comparator. logic rule. [0] * DISABLED Use the result of logic rule 4 in the logic [1] Reference rule.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 13-12 Comparator Value 13-40 Logic Rule Boolean 1 Array [6] Array [6] Range: Application dependent* Function: [-100000.000 - Enter the ‘trigger level’ for the 100000.000 ] Option: [0] * False variable that is monitored by this comparator. This is an array parameter containing logic rule. [1] True This parameter group consists of timer parameters. Use the result (TRUE or FALSE) from timers directly to define an event (see par.
VLT® HVAC Drive Programming Guide Parameter Description 13-40 Logic Rule Boolean 1 13-40 Logic Rule Boolean 1 Array [6] Array [6] Option: [22] Comparator 0 Function: Option: Use the result of comparator 0 in the [42] Auto Reset Trip logic rule. [23] Comparator 1 converter is tripped (but not trip-locked) [25] Comparator 2 Comparator 3 [43] Use the result of comparator 2 in the logic rule.
VLT® HVAC Drive Programming Guide Parameter Description 13-41 Logic Rule Operator 1 13-42 Logic Rule Boolean 2 Array [6] Array [6] Option: 3 3 [0] * DISABLED [1] AND Function: Option: Select the first logical operator to use on the [14] Below feedb. low Boolean inputs from par. 13-40 Logic Rule [15] Above feedb. high Boolean 1 and par. 13-42 Logic Rule Boolean [16] Thermal warning 2.
VLT® HVAC Drive Programming Guide Parameter Description 13-42 Logic Rule Boolean 2 13-44 Logic Rule Boolean 3 Array [6] Array [6] Option: Function: Option: [90] ECB Drive Mode [9] [91] ECB Bypass Mode [10] Out of speed range [92] ECB Test Mode [11] Below speed low [12] Above speed high [100] Fire Mode 13-43 Logic Rule Operator 2 Array [6] Option: Function: par. 13-40 Logic Rule Boolean 1, [19] Warning par. 13-41 Logic Rule Operator 1, and [20] Alarm (trip) par.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 13-44 Logic Rule Boolean 3 13-51 SL Controller Event Array [6] Array [20] Option: [78] Function: Option: Digital Input x30 4 [27] Logic rule 1 [80] No Flow [28] Logic rule 2 [81] Dry Pump [29] Logic rule 3 [82] End of Curve [30] SL Time-out 0 [83] Broken Belt [31] SL Time-out 1 [90] ECB Drive Mode [32] SL Time-out 2 [91] ECB Bypass Mode [33] Digital input DI18 [92] ECB Test Mode [34] Digital input DI19 [35]
VLT® HVAC Drive Programming Guide Parameter Description 13-52 SL Controller Action 13-52 SL Controller Action Array [20] Array [20] Option: Function: Option: Select the action corresponding to the [28] Freeze output SLC event. Actions are executed when the corresponding event (defined in par. 13-51 SL Controller Event) is frequency converter. [29] Start timer 0 [0] * Disabled [1] No action [2] Select set-up 1 Select set-up 2 Select set-up 3 Select set-up 4 Starts timer 1, see par.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 13-52 SL Controller Action 14-03 Overmodulation Array [20] Option: Option: [90] [0] Function: Off Selects no over-modulation of the output voltage in order to avoid torque ripple on the motor shaft.
VLT® HVAC Drive Programming Guide Parameter Description 3 3 Illustration 3.2: Controlled Ramp down - short mains failure. Ramping down to stop followed by ramping up to Illustration 3.5: Kinetic Back-up, longer mains failure. The reference. motor is coasted as soon as the energy in the system is too low. 3.14.
3.14.4 14-2* Trip Reset 14-22 Operation Mode Option: Parameters for configuring auto reset handling, special trip handling and control card self test or initialisation. [0] Normal Select Normal operation [0] for normal operation * operation of the frequency converter with the motor in the selected application. 14-20 Reset Mode Option: Function: [1] Select the reset function after tripping.
VLT® HVAC Drive Programming Guide Parameter Description 3.14.5 14-3* Current Limit Control 14-22 Operation Mode Option: [2] Function: Initialisa- Select Initialisation [2] to reset all parameter values tion to default settings, except for par. 15-03 Power Up's, par. 15-04 Over Temp's and par. 15-05 Over Volt's. The frequency converter will reset during the next power-up. Par. 14-22 Operation Mode will also revert to the default setting Normal operation [0].
VLT® HVAC Drive Programming Guide Parameter Description 14-41 AEO Minimum Magnetisation 14-52 Fan Control Range: Option: Function: Application [40 - 75 dependent* Function: Enter the minimum allowable magnet- %] isation for AEO. Selection of a low value reduces energy loss in the 3 3 Select the minimum speed of the main fan.
Parameter Description VLT® HVAC Drive Programming Guide 3.14.9 No Trip at Inverter Overload 14-61 Function at Inverter Overload Option: In some pump systems, the frequency converter has not been sized properly to yield the current needed in all points of the operational flow-head characteristic. At these points, the pump will need a current higher than the rated current of the frequency converter. The frequency converter can yield 110% of the rated current continuously for 60 sec.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 15-06 Reset kWh Counter 3.15 Main Menu - Drive Information Group 15 Parameter group containing frequency converter information such as operating data, hardware configuration and software versions. [0] * Do not reset [1] Reset counter Select Reset [1] and press [OK] to reset the kWh counter to zero (see par. 15-02 kWh Counter).
VLT® HVAC Drive Programming Guide Parameter Description 15-10 Logging Source 15-12 Trigger Event Array [4] Option: Option: Function: Selects the trigger event. When the Function: [1613] Frequency trigger event occurs, a window is [1614] Motor Current applied to freeze the log. The log will then retain a specified percentage of [1616] Torque [Nm] samples before the occurrence of the [1617] Speed [RPM] trigger event (par. 15-14 Samples [1618] Motor Thermal Before Trigger).
Parameter Description VLT® HVAC Drive Programming Guide 15-13 Logging Mode 15-21 Historic Log: Value Option: Array [50] Function: [0] * Log always [1] 3 3 Select Log always [0] for continuous logging. Log once on Select Log once on trigger [1] to conditionally trigger start and stop logging using Range: 0* Function: [0 - View the value of the logged event. Interpret 2147483647 ] par. 15-12 Trigger Event and the event values according to this table: Digtal input par.
VLT® HVAC Drive Programming Guide Parameter Description 3.15.4 15-3* Alarm Log 15-42 Voltage Range: Parameters in this group are array parameters, where up to 10 fault logs can be viewed. [0] is the most recent logged data, and [9] the oldest. Error codes, values, and time stamp can be viewed for all logged data. 0* Function: [0 - 0 ] View the FC type. The read-out is identical to the frequency converter series power field of the type code definition, characters 11-12.
3 3 Parameter Description VLT® HVAC Drive Programming Guide 3.15.6 15-6* Option Ident. 15-75 Slot C0 Option SW Version Range: This read-only parameter group contains information about the hardware and software configuration of the options installed in slots A, B C0 and C1. 0* Function: [0 - 0 ] View the software version for the option installed in slot C. 15-60 Option Mounted 15-76 Option in Slot C1 Range: Range: 0* [0 - 0 ] Function: View the installed option type.
VLT® HVAC Drive Programming Guide Parameter Description 3.16.2 16-1* Motor Status 3.16 Main Menu - Data Readouts Group 16 Parameters for reading the motor status values. 16-10 Power [kW] Range: 3.16.1 16-0* General Status [0.00 - Displays motor power in kW. The value kW* 10000.00 shown is calculated on the basis of the kW] actual motor voltage and motor current. 16-00 Control Word Range: 0* Function: 0.00 The value is filtered, and therefore approx.
VLT® HVAC Drive Programming Guide Parameter Description 3.16.3 16-3* Drive Status 16-16 Torque [Nm] Range: 0.0 Function: [-30000.0 - View the torque value with sign, applied to Nm* 30000.0 the motor shaft. Linearity is not exact Nm] between 110% motor current and torque in 3 3 16-30 DC Link Voltage Range: 0 V* Function: [0 - 10000 V] View a measured value. The value is filtered relation to the rated torque. Some motors with an 30 ms time constant. supply more than 160% torque.
VLT® HVAC Drive Programming Guide Parameter Description 16-39 Control Card Temp. 16-52 Feedback [Unit] Range: Range: 0 C* Function: [0 - 100 C] View the temperature on the control card, stated in °C. 0.000 [-999999.999 - View value of resulting feedback ProcessCtr- 999999.999 value after processing of Feedback lUnit* ProcessCtrlU- 1-3 (see par. 16-54 Feedback 1 [Unit], nit] par. 16-55 Feedback 2 [Unit] and par. 16-40 Logging Buffer Full Option: Function: 16-56) in the feedback manager.
VLT® HVAC Drive Programming Guide Parameter Description 16-58 PID Output [%] Range: 0.0 %* 16-62 Analog Input 53 Function: Range: [0.0 - 100.0 %] This parameter returns the Drive Closed 0.000* Function: [-20.000 - 20.000 ] View the actual value at input 53. Loop PID controller output value in 16-63 Terminal 54 Switch Setting percent. 3 3 Option: Function: View the setting of input terminal 54. Current = 3.16.5 16-6* Inputs and Outputs 0; Voltage = 1.
VLT® HVAC Drive Programming Guide Parameter Description 3.16.6 16-8* Fieldbus & FC Port 16-71 Relay Output [bin] Range: [0 - 511 ] Parameters for reporting the BUS references and control words. View the settings of all relays. Readout choice (Par. 16-71): Relay output (bin): 0 0 0 0 0 bin 130BA195.10 0* Function: 16-80 Fieldbus CTW 1 Range: 0* 3 3 Function: [0 - 65535 ] View the two-byte Control word (CTW) received from the Bus-Master.
VLT® HVAC Drive Programming Guide Parameter Description 3.16.7 16-9* Diagnosis Read-Outs 16-90 Alarm Word Range: 0* Function: [0 - 4294967295 ] View the alarm word sent via the serial 3 3 communication port in hex code. 16-91 Alarm Word 2 Range: 0* Function: [0 - 4294967295 ] View the alarm word 2 sent via the serial communication port in hex code. 16-92 Warning Word Range: 0* Function: [0 - 4294967295 ] View the warning word sent via the serial communication port in hex code.
VLT® HVAC Drive Programming Guide Parameter Description 18-03 Maintenance Log: Date and Time 3.17 Main Menu - Data Readouts 2 Group 18 3.17.1 18-0* Maintenance Log Array [10] Range: Application Function: [Applica- dependent* tion dependant] Shows when the logged event occurred. 3 3 NOTE This requires that the date and time is programmed in par. 0-70 Date and Time. This group contains the last 10 Preventive Maintenance events. Maintenance Log 0 is the latest and Maintenance Log 9 the oldest.
VLT® HVAC Drive Programming Guide Parameter Description 18-11 Fire Mode Log: Time 18-33 Analog Out X42/7 [V] Range: Range: 0 s* Function: [0 - 2147483647 s] This parameter contains an array with 0.000* 10 elements. The parameter shows at 3 3 Function: [0.000 - 30.000 ] Read out of the value of the signal applied to terminal X42/7 on the Analog I/O Card. which time the logged event occurred. The value shown reflects the selection in Time is measured in seconds since the par.
VLT® HVAC Drive Programming Guide Parameter Description 3.18.1 20-0* Feedback 3.18 Main Menu - FC Closed Loop Group 20 This parameter group is used for configuring the closed loop PID Controller, that controls the output frequency of the frequency converter. 20-00 Feedback 1 Source Option: This parameter group is used to configure the feedback signal for the frequency converter’s closed loop PID Controller.
3 3 Parameter Description VLT® HVAC Drive Programming Guide NOTE 20-02 Feedback 1 Source Unit If a feedback is not used, its source must be set to No Function [0]. Par. 20-20 Feedback Function determines how the three possible feedbacks will be used by the PID Controller. 20-01 Feedback 1 Conversion Option: [0] Linear Function: root [10] RPM [12] Pulse/s [20] l/s [21] l/min [22] l/h [23] m3/s applied to Feedback 1. [24] m3/min Linear [0] has no effect on the feedback.
VLT® HVAC Drive Programming Guide Parameter Description NOTE 20-06 Feedback 3 Source This parameter is only available when using pressure to temperature feedback conversion. If the choice Linear [0] is selected in par. 20-01 Feedback 1 Conversion, then the setting of any choice in par. 20-02 Feedback 1 Source Unit does not matter as conversion will be one-to-one.
3 3 VLT® HVAC Drive Programming Guide Parameter Description NOTE 20-20 Feedback Function If operating with par. 1-00 Configuration Mode set for Open Loop [0], par. 3-02 Minimum Reference must be used. Option: Function: The sum of Setpoint 1 and any other references that are enabled (see par. group 3-1*) will be used as the PID Controller’s set-point reference. 20-14 Maximum Reference/Feedb. Range: 100.
Parameter Description VLT® HVAC Drive Programming Guide 20-20 Feedback Function 20-20 Feedback Function Option: Option: [5] Function: Multi Multi-setpoint minimum [5] sets up the PID NOTE Setpoint Controller to calculate the difference between Min Feedback 1 and Setpoint 1, Feedback 2 and If only two feedback signals are used, the feedback that is not to be used must be set to No Function in par. 20-00 Feedback 1 Source, par. 20-03 Feedback 2 Source or par. 20-06 Feedback 3 Source.
VLT® HVAC Drive Programming Guide Parameter Description 3 3 Example 2 – Multi zone, multi setpoint The previous example can be used to illustrate the use of multi zone, multi setpoint control. If the zones require different pressures for each VAV box, each setpoint may be specified in par. 20-21 Setpoint 1, par. 20-22 Setpoint 2 and par. 20-23 Setpoint 3. By selecting Multi setpoint minimum, [5], in par.
VLT® HVAC Drive Programming Guide Parameter Description 3.18.3 20-3* Feedback Adv. Conversion 20-34 Fan 1 Area [m2] Range: Function: In air conditioning compressor applications it is often useful to control the system based on the temperature of the refrigerant. However, it is generally more convenient to directly measure its pressure. This parameter group allows the frequency converter’s PID Controller to convert refrigerant pressure measurements into temperature values.
VLT® HVAC Drive Programming Guide Parameter Description 3.18.5 20-7* PID autotuning 20-38 Air Density Factor [%] Range: 100 %* Function: [50 - 150 %] Set the air density factor for conversion from pressure to flow in % relative to the air density at sea level at 20 °C (100% ~ 1,2 kg/ 3 3 m3). The frequency converter PID Closed Loop controller (parameters 20-**, FCDrive Closed Loop) can be auto-tuned, simplifying and saving time during commissioning, whilst ensuring accurate PID control adjustment.
VLT® HVAC Drive Programming Guide Parameter Description 20-70 Closed Loop Type 20-74 Maximum Feedback Level Option: Range: Function: Function: This parameter defines the application 999999.000 response. The default mode should be ProcessCtrlU- tion [Applica- The maximum allowable feedback sufficient for most applications. If the nit* dependant] units as defined in level should be entered here in User application response speed is known, it can par. 20-12 Reference/Feedback Unit.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 3.18.7 20-9* PID Controller 20-82 PID Start Speed [RPM] Range: Applica- Function: [Applica- When the frequency converter is first tion tion started, it initially ramps up to this output depend- depend- speed in Open Loop Mode, following the ent* ant] active Ramp Up Time.
Parameter Description VLT® HVAC Drive Programming Guide NOTE 20-96 PID Diff. Gain Limit Always set the desired for par. 20-14 Maximum Reference/Feedb. before setting the values for the PID controller in parameter group 20-9*. Range: 5.0* [1.0 50.0 ] Function: The differential function of a PID Controller responds to the rate of change of the feedback.
3 3 Parameter Description VLT® HVAC Drive Programming Guide 3.19 Main Menu - Extended Closed Loop - Group 21 The FC 102 offers 3 Extended Closed Loop PID controllers in addition to the PID Controller. These can be configured independently to control either external actuators (valves, dampers etc.) or be used together with the internal PID Controller to improve the dynamic responses to setpoint changes or load disturbances.
VLT® HVAC Drive Programming Guide Parameter Description 21-02 PID Output Change 21-09 PID Autotuning Range: Option: 0.10* Function: [0.01 - This parameter sets the magnitude of step 0.50 ] [3] change during autotuning. The value is a Function: Enabled Ext CL 3 PID percentage of full operating range. I.e. if maximum analog output voltage is set to 10 V, 0.10 is 10% of 10 V, which is 1 V. This parameter 3 3 3.19.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 21-10 Ext. 1 Ref./Feedback Unit 21-13 Ext. 1 Reference Source Option: Option: Function: Function: [75] mm Hg X30/12 refer to inputs on the General [80] kW Purpose I/O. [120] GPM [0] * No function [121] gal/s [1] [122] gal/min [2] Analog input 54 [123] gal/h [7] Pulse input 29 [124] CFM [8] Pulse input 33 [125] ft3/s [20] Digital pot.
VLT® HVAC Drive Programming Guide Parameter Description 21-17 Ext. 1 Reference [Unit] Range: 21-22 Ext. 1 Integral Time Function: 0.000 Function: Readout of the This ensures that the deviation (error) 999999.999 reference value for the approaches zero. ExtPID1Unit] Closed Loop 1 Control- Quick response on any deviation is ler. obtained when the integral time is set to a [-999999.999 - ExtPID1Unit* Range: low value. Setting it too low, however, 21-18 Ext.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 21-30 Ext. 2 Ref./Feedback Unit 21-33 Ext. 2 Reference Source Option: Option: Function: Function: [31] kg/min See par. 21-13 Ext. 1 Reference Source [32] kg/h for details. [33] t/min [0] * No function [34] t/h [1] [40] m/s [2] Analog input 54 [41] m/min [7] Pulse input 29 [45] m [8] Pulse input 33 [60] °C [20] Digital pot.
VLT® HVAC Drive Programming Guide Parameter Description 21-38 Ext. 2 Feedback [Unit] 21-50 Ext. 3 Ref./Feedback Unit Range: Function: 0.000 [-999999.999 - Option: See par. 21-18 Ext. 1 [23] m3/s 999999.999 Feedback [Unit] for [24] m3/min ExtPID2Unit] details. [25] m3/h [30] kg/s 21-39 Ext. 2 Output [%] [31] kg/min Range: [32] kg/h [33] t/min ExtPID2Unit* Function: 0 %* [0 - 100 %] See par. 21-19 Ext. 1 Output [%] for details. 3.19.5 21-4* Closed Loop 2 PID 21-40 Ext.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 21-53 Ext. 3 Reference Source 21-58 Ext. 3 Feedback [Unit] Option: Range: Function: Function: See par. 21-13 Ext. 1 Reference Source 0.000 for details. ExtPID3Unit* [-999999.999 - [0] * No function [1] Analog input 53 [2] Analog input 54 [7] Pulse input 29 [8] Pulse input 33 See par. 21-18 Ext. 1 999999.999 Feedback [Unit] for ExtPID3Unit] details. 21-59 Ext. 3 Output [%] Range: 0 %* Function: [0 - 100 %] See par.
VLT® HVAC Drive Programming Guide Parameter Description 22-01 Power Filter Time 3.20 Main Menu - Application Functions - Group 22 Range: 0.50 s* Function: [0.02 - 10.00 s] This group contains parameters used for monitoring VLT HVAC Drive applications. 3 3 22-00 External Interlock Delay Range: 0 s* [0 - 600 s] Function: Only relevant if one of the digital inputs in parameter group 5-1* has been programmed for External Interlock [7].
Parameter Description VLT® HVAC Drive Programming Guide NOTE Carry out No Flow tuning before setting the PI controller parameters! 3 3 No Flow Detection is based on the measurement of speed and power. For a certain speed the frequency converter calculates the power at no flow. This coherence is based on the adjustment of two sets of speed and associated power at no flow.
VLT® HVAC Drive Programming Guide Parameter Description 22-20 Low Power Auto Set-up 22-23 No-Flow Function Start of auto set-up of power data for No-Flow Power tuning. Common actions for Low Power Detection and Low Speed Option: Detection (Individual selections not possible). Function: Option: [0] * Off [1] Enabled When set for Enabled, an auto set up sequence is activated, automatically setting speed to approx.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 3.20.2 22-3* No-Flow Power Tuning 22-26 Dry Pump Function Select desired action for dry pump operation. Option: Tuning Sequence, if not choosing Auto Set Up in par. 22-20 Low Power Auto Set-up: Function: [0] * Off [1] Warning The drive will continue to run, but activate a Dry pump warning [W93]. A drive digital 1. Close the main valve to stop flow output or a serial communication bus can 2.
VLT® HVAC Drive Programming Guide Parameter Description 22-32 Low Speed [RPM] Range: Application dependent* 22-37 High Speed [Hz] Function: Range: [Application To be used if par. 0-02 Motor Speed dependant] Unit has been set for RPM (parameter Application dependent* [Application To be used if par. 0-02 Motor Speed dependant] not visible if RPM selected). Set used speed for the 85% level.
3 3 Parameter Description VLT® HVAC Drive Programming Guide NOTE If Sleep Mode is to be based on No Flow Detection/ Minimum Speed, remember to choose Sleep Mode [1] in par. 22-23 No-Flow Function. If par. 25-26 Destage At No-Flow is set for Enabled, activating Sleep Mode will send a command to the cascade controller (if enabled) to start de-staging of lag pumps (fixed speed) before stopping the lead pump (variable speed).
VLT® HVAC Drive Programming Guide Parameter Description When low power or low speed is detected the motor is stopped, but the reference signal (fref) from the external controller is still monitored and because of the low pressure created, the controller will increase the reference signal to gain pressure. When the reference signal has reached a set value fwake the motor restarts. The speed is set manually by an external reference signal (Remote Reference).
VLT® HVAC Drive Programming Guide Parameter Description 3.20.4 22-5* End of Curve 22-43 Wake-up Speed [Hz] Range: Function: Application [Applica- To be used if par. 0-02 Motor Speed Unit, depend- tion has been set for Hz (parameter not ent* dependant] visible if RPM selected). Only to be used 3 3 if par. 1-00 Configuration Mode, is set for Open Loop and speed reference is applied by an external controller controlling the pressure.
VLT® HVAC Drive Programming Guide Parameter Description NOTE NOTE Automatic restart will reset the alarm and start the system again. Do not set par. 14-20 Reset Mode, to [13] Infinite auto reset, when par. 22-60 Broken Belt Function is set to [2] Trip. Doing so will cause the drive to continuously cycle between running and stopping when a broken belt condition is detected. NOTE Do not set par. 14-20 Reset Mode, to [13] Infinite auto reset, when par. 22-50 End of Curve Function is set to [2] Alarm.
VLT® HVAC Drive Programming Guide Parameter Description 22-76 Interval between Starts Range: Function: Application dependent* [Application dependant] Sets the time desired as minimum time between two starts. Any normal start command (Start/Jog/ 3 3 Freeze) will be disregarded until the timer has expired. 22-77 Minimum Run Time Range: 0 s* Function: [Application Sets the time desired as minimum run time dependant] after a normal start command (Start/Jog/ Freeze).
VLT® HVAC Drive Programming Guide Parameter Description 22-80 Flow Compensation 22-82 Work Point Calculation Option: Option: Function: achieved allows the speed at the no flow point to be [0] * Disabled [0] Disabled: Set-Point compensation not active. [1] Enabled Function: identified. [1] Enabled:Set-Point compensation is active. Adjustment of par.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 22-83 Speed at No-Flow [RPM] 22-86 Speed at Design Point [Hz] Range: Range: Applica- Function: [Applica- Resolution 1 RPM. Application The speed of the motor at which flow Is depend- tion ent* dependant] tion tion depend- dependant] zero and minimum pressure HMIN is ent* Function: [Applica- Resolution 0.033 Hz. Only visible when par. 22-82 Work Point Calculation is set to Disable.
VLT® HVAC Drive Programming Guide Parameter Description 23-01 ON Action 3.21 Main Menu - Time-based Functions - Group 23 Arra [10] Option: Function: Select the action during ON Time. See par. 13-52 SL Controller Action for 3.21.1 23-0* Timed Actions 3 3 descriptions of the options. Use Timed Actions for actions needing to be performed on a daily or weekly basis, e.g. different references for working hours / non-working hours. Up to 10 Timed Actions can be programmed in the frequency converter.
3 3 VLT® HVAC Drive Programming Guide Parameter Description NOTE 23-03 OFF Action For choices [32] - [43], see also parameter group 5-3*, Digital Outputs and 5-4*, Relays. Array [10] 23-02 OFF Time Function: [35] Set digital out D low Array [10] [36] Set digital out E low Range: Function: Application dependent* Option: [34] Set digital out C low [37] Set digital out F low [Application Sets the OFF time for the Timed dependant] [38] Set digital out A high Action.
Parameter Description VLT® HVAC Drive Programming Guide 3.21.2 23-1* Maintenance • Maintenance Time Base (e.g. “Running Hours” or a specific date and time) Wear and tear calls for periodic inspection and service of elements in the application, e.g. motor bearings, feedback sensors and seals or filters. With Preventive Maintenance the service intervals may be programmed into the frequency converter. The frequency converter will give a message when maintenance is required.
VLT® HVAC Drive Programming Guide Parameter Description 23-10 Maintenance Item Option: 23-12 Maintenance Time Base Function: Option: Array with 20 elements displayed Select the time base to be associated with the below parameter number in the Preventive Maintenance Event. display. Press [OK] and step between 3 3 Function: elements by means of and buttons on [0] * Disabled Preventive Maintenance Event. the LCP.
VLT® HVAC Drive Programming Guide Parameter Description 3.21.3 23-5* Energy Log 23-14 Maintenance Date and Time Range: Function: Applica- [Applica- Set the date and time for next mainte- tion tion nance occurrence if the Preventive depend- depend- Maintenance Event is based on date/time. ent* ant] Date format depends on the setting in par. 0-71 Date Format while the time format depends on the setting in par. 0-72 Time Format.
The contents of counters can be displayed as bars on LCP. Select Quick Menu, Loggings, Energy Log: Trending Continued Bin / Trending Timed Bin / Trending Comparison. NOTE When mounting an Analog I/O MCB 109 option card, a battery back up of the date and time is included. 23-50 Energy Log Resolution Option: 23-53 Energy Log Function: Select the desired type of period for logging of Range: Function: or Day of Month [2].
VLT® HVAC Drive Programming Guide Parameter Description 3.21.4 23-6* Trending Trending is used to monitor a process variable over a period of time and record how often the data falls into each of ten userdefined data ranges. This is a convenient tool to get a quick overview indicating where to put focus for improvement of operation.
VLT® HVAC Drive Programming Guide Parameter Description 23-61 Continuous Bin Data 23-63 Timed Period Start Range: Range: 0* [0 4294967295 ] Function: Array with 10 elements ([0]-[9] below parame- Application ter number in display). Press OK and step dependent* between elements by means of 3 3 Function: [Application Set the date and time at which the dependant] ▲ and ▼ Trending starts the update of the Timed Bin counters. buttons on the LCP.
VLT® HVAC Drive Programming Guide Parameter Description 23-66 Reset Continuous Bin Data Option: Function: Select Do reset [1] to reset all values in par. 23-61 Continuous Bin Data. After pressing OK the setting of the parameter value will automatically change to Do not reset [0].
VLT® HVAC Drive Programming Guide Parameter Description 23-80 Power Reference Factor Range: 100 %* Function: [0 - 100 Set the percentage of the rated motor size (set %] in par. 1-20 Motor Power [kW] or par. 1-21 Motor Power [HP]) which is supposed to represent the 3 3 average power yielded at the time running with fixed speed (before upgrade with variable speed control). Must be set to a value different from zero to start counting. 23-81 Energy Cost Range: 1.00* Function: [0.00 999999.
VLT® HVAC Drive Programming Guide Parameter Description converter’s normal protective functions. These could be ventilation fans in tunnels or stairwells for instance, where continued operation of the fan facilitates safe evacuation of personnel in the event of a fire. Some selections of Fire Mode Function cause alarms and trip conditions to be disregarded, enabling the motor to run without interruption. 3.22 Main Menu - Application Functions 2 - Group 24 3.22.
3 3 VLT® HVAC Drive Programming Guide Parameter Description NOTE 24-01 Fire Mode Configuration During Fire Mode operation all stop commands to the frequency converter will be ignored, including Coast/ Coast inverse and External Interlock. However, if your frequency converter incorporates “Safe-Stop”, this function is still active. See Section “How to Order / Ordering Form Type Code”. Option: [0] * Open When Fire Mode is active, the motor will run with a Loop fixed speed based on a Reference set.
VLT® HVAC Drive Programming Guide Parameter Description 24-02 Fire Mode Unit 24-04 Fire Mode Max Reference Option: Range: Function: Function: [70] mbar Application [71] bar depend- tion [Applica- Maximum value for the reference/set point (limiting the sum of value in [72] Pa ent* dependant] par. 24-05 Fire Mode Preset Reference [73] kPa and value of signal on input selected in [74] m WG par. 24-06 Fire Mode Reference Source).
VLT® HVAC Drive Programming Guide Parameter Description 24-07 Fire Mode Feedback Source Option: No: Function: Select the feed back input to be used for the Fire Mode feed back signal [0] * [1] Analog input 54 Pulse input 29 [4] Pulse input 33 [7] Analog input X30/11 [8] Analog input X30/12 [9] Analog Input X42/1 [10] Analog Input X42/3 [11] Analog Input X42/5 [15] Analog Input X48/2 x If the motor also is controlled by the x built in PID controller when in normal 9 Inverter overloa
Parameter Description VLT® HVAC Drive Programming Guide 24-11 Drive Bypass Delay Time Range: 0 s* [0 - Function: Programmable in 1 s increments. Once the Bypass 600 s] Function is activated in accordance with the setting in par. 24-10 Drive Bypass Function, the Bypass Delay Timer begins to operate. If the frequency converter has been set for a number of restart attempts, the timer will continue to run while the frequency converter tries to restart.
3 3 Parameter Description VLT® HVAC Drive Programming Guide 24-95 Locked Rotor Function Option: Function: Select the action to be taken if the motor current is above the limit calculated as a function of the output frequency. The function is used for detecting e.g. a locked rotor in multi-motor applications. [0] * Off [1] Warning 24-96 Locked Rotor Coefficient 1 Range: 0.0000* Function: [-10.0000 - 10.0000 ] 24-97 Locked Rotor Coefficient 2 Range: 0.0000* Function: [-100.0000 - 100.
Parameter Description VLT® HVAC Drive Programming Guide 3.23 Main Menu - Cascade Controller Group 25 Parameters for configuring the Basic Cascade Controller for sequence control of multiple pumps. For a more application oriented description and wiring examples, see Chapter Application Examples, item Basic Cascade Controller in the Design Guide.
3 3 Parameter Description VLT® HVAC Drive Programming Guide 3.23.1 25-0* System Settings 25-05 Fixed Lead Pump Option: Parameters related to control principles and configuration of the system. Fixed Lead Pump means that the variable speed pump is connected directly to the frequency converter and if a contactor is applied between frequency converter and 25-00 Cascade Controller Option: pump, this contactor will not be controlled by the Function: frequency converter.
VLT® HVAC Drive Programming Guide Parameter Description 3.23.2 25-2* Bandwidth Settings 25-21 Override Bandwidth Range: Parameters for setting the bandwidth within which the pressure will be allowed to operate before staging/destaging fixed speed pumps. Also includes various timers to stabilize the control. Function: dependant] 3 3 25-20 Staging Bandwidth Range: 10 %* Function: Set the staging bandwidth (SBW) percentage to [Applica- accommodate normal system pressure fluctuation.
VLT® HVAC Drive Programming Guide Parameter Description 25-23 SBW Staging Delay Range: Function: 15 [1 - s* 3000 desirable when a momentary pressure drop in the s] system exceeds the Staging Bandwidth (SBW). 3 3 Immediate staging of a fixed speed pump is not Staging is delayed by the length of time programmed. If the pressure increases to within the SBW before the timer has elapsed, the timer is reset.
Parameter Description VLT® HVAC Drive Programming Guide 3.23.3 25-4* Staging Settings 25-29 Destage Function Option: Function: The Destage Function ensures that the lowest numbers of pumps are running to save energy and to avoid dead head water circulation in the variable speed pump. If the Destage Function is set to Disabled [0], the par. 25-30 Destage Function Time will not be activated. [0] Parameters determining conditions for staging/destaging the pumps. 25-40 Ramp Down Delay Range: 10.
VLT® HVAC Drive Programming Guide Parameter Description 3 3 NOTE 25-42 Staging Threshold Range: Function: Applica- When adding a fixed speed pump, in order to tion [Applica- prevent an overshoot of pressure, the depend- tion variable speed pump ramps down to a lower ent* depend- speed. When the variable speed pump ant] reaches the “Staging Speed” the fixed speed pump is staged on.
VLT® HVAC Drive Programming Guide Parameter Description 25-46 Destaging Speed [RPM] Range: 0 RPM* Function: [0 - 0 Readout of the below calculated value for Destag- RPM] ing Speed. When removing a fixed speed pump, in order to prevent an undershoot of pressure, the variable speed pump ramps up to a higher speed. When the variable speed pump reaches the “Destaging Speed” the fixed speed pump is destaged.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 3.23.4 25-5* Alternation Settings 25-51 Alternation Event Option: Parameters for defining the conditions for alternation of the variable speed pump (lead), if selected as part of the control strategy. [3] Function: Predefined Alternation takes place at a defined time of the Time day. If par. 25-54 Alternation Predefined Time, is set, the alternation is carried out every day at the specified time.
Parameter Description VLT® HVAC Drive Programming Guide NOTE 25-58 Run Next Pump Delay Only valid if par. 25-50 Lead Pump Alternation is different from Off [0]. Range: 0.1 s* Function: [0.1 - This parameter is only active if the option selected 5.0 s] in par. 25-50 Lead Pump Alternation, is different 25-56 Staging Mode at Alternation from Off [0]. Option: This parameter sets the time between stopping [0] * Slow Function: This parameter is only active if the option selected in par.
VLT® HVAC Drive Programming Guide Parameter Description 3.23.6 25-9* Service 25-83 Relay Status Array [2] Range: 0* Function: [0 - 0 ] Read out of the status for each of the relays assigned 3 3 Parameters used in case of service on one or more of the pumps controlled. to control the pumps. Every element in the array 25-90 Pump Interlock represents a relay. If a relay is activated, the Array [2] corresponding element is set to “On”.
Parameter Description VLT® HVAC Drive Programming Guide 3.24 Main Menu - Analog I/O Option MCB 109 - Group 26 The Analog I/O Option MCB 109 extends the functionality of VLT HVAC Drive frequency converters, by adding a number of additional, programmable analog inputs and outputs. This could be especially useful in Building Management System installations where the frequency converter may be used as de-central I/O, obviating the need for an outstation and thus reducing cost.
3 3 VLT® HVAC Drive Programming Guide Parameter Description NOTE The maximum current for the analog outputs 0-10V is 1mA. NOTE Where Live Zero Monitoring is used, it is important that any analog inputs not being used for the frequency controller, i.e. being used as part of the Building Management System decentral I/O, should have their Live Zero function disabled. Terminal Parameters Terminal Parameters Analog inputs X42/1 Analog inputs Par.
VLT® HVAC Drive Programming Guide Parameter Description 3.24.1 26-0* Analog I/O Mode 26-02 Terminal X42/5 Mode Option: Function: Parameter group for setting up the analog I/O configuration. The option is equipped with 3 analog inputs. These analog inputs can be freely allocated to either voltage (0V - +10V), Pt 1000 or Ni 1000 temperature sensor input.
VLT® HVAC Drive Programming Guide Parameter Description 26-15 Term. X42/1 High Ref./Feedb. Value 26-24 Term. X42/3 Low Ref./Feedb. Value Range: Range: Function: 100.000* [-999999.999 - Enter the analog input scaling 999999.999 ] 0.000* value that corresponds to the high 3 3 Function: [-999999.999 - Enter the analog input scaling value 999999.999 ] that corresponds to the low voltage voltage value set in value set in par. 26-20 Terminal X42/3 par. 26-11 Terminal X42/1 High Low Voltage.
VLT® HVAC Drive Programming Guide Parameter Description 3.24.5 26-4* Analog Out X42/7 26-31 Terminal X42/5 High Voltage Range: 10.00 V* Function: [Application Enter the high voltage value. This dependant] analog input scaling value should correspond to the high reference/ feedback value set in par. 26-35 Term. X42/5 High Ref./Feedb. Value. Parameters for configuring the scaling and output function for analog output, terminal X42/7. 26-40 Terminal X42/7 Output Option: 26-34 Term. X42/5 Low Ref.
VLT® HVAC Drive Programming Guide Parameter Description 26-42 Terminal X42/7 Max. Scale 26-50 Terminal X42/9 Output Range: Option: Function: 100.00 [0.00 - Scale the maximum output of the selected analog %* 200.00 signal at terminal X42/7. Set the value to the %] maximum value of the voltage signal output.
VLT® HVAC Drive Programming Guide Parameter Description 26-53 Terminal X42/9 Bus Control 26-61 Terminal X42/11 Min. Scale Range: Range: 0.00 %* Function: [0.00 - 100.00 %] Holds the level of terminal X42/9 if controlled by bus. Function: 0.00 [0.00 - %* 200.00 %] Scale the minimum output of the selected analog signal at terminal X42/11, as a percentage of the maximum signal level. E.g. if a 0 V 26-54 Terminal X42/9 Timeout Preset is desired at 25% of the maximum output Range: value.
4 4 Troubleshooting VLT® HVAC Drive Programming Guide If an alarm cannot be reset, the reason may be that its cause has not been rectified, or the alarm is trip-locked (see also table on following page). 4 Troubleshooting A warning or an alarm is signalled by the relevant LED on the front of the frequency converter and indicated by a code on the display. A warning remains active until its cause is no longer present. Under certain circumstances operation of the motor may still be continued.
VLT® HVAC Drive Programming Guide Troubleshooting No.
4 4 Troubleshooting No. Description VLT® HVAC Drive Programming Guide Warning Alarm/ Trip Alarm/Trip Lock Parameter Reference 201 Fire M was Active 202 Fire M Limits Exceeded 203 Missing Motor 204 Locked Rotor 243 Brake IGBT X X 244 Heatsink temp X X X 245 Heatsink sensor X X 246 Pwr.card supply X X 247 Pwr.card temp X X 248 Illegal PS config X X 250 New spare parts X 251 New Type Code X X Table 4.
VLT® HVAC Drive Programming Guide Troubleshooting Alarm Word and Extended Status Word Bit Hex Dec Alarm Word Warning Word Extended Status Word 0 00000001 1 1 00000002 2 Brake Check Brake Check Ramping Pwr. Card Temp Pwr. Card Temp 2 00000004 4 Earth Fault AMA Running Earth Fault Start CW/CCW 3 00000008 8 Ctrl.Card Temp Ctrl.Card Temp Slow Down 4 00000010 16 Ctrl. Word TO Ctrl.
VLT® HVAC Drive Programming Guide Troubleshooting 4.1.1 Alarm Words Alarm word 2, par. 16-91 Alarm Word 2 Bit Alarm word, par. 16-90 Alarm Word 188 Alarm Word 2 (par. 16-91 Alarm Word 2) Alarm Word 00000001 Service Trip, read / Write (par. 16-90 Alarm Word) 00000002 Reserved 00000001 Brake check 00000004 Service Trip, Typecode / Sparepart 00000002 Power card over temperature 00000008 Reserved 00000004 Earth fault 00000010 Reserved 00000008 Ctrl.
VLT® HVAC Drive Programming Guide Troubleshooting 4.1.2 Warning Words Warning word 2, par. 16-93 Warning Word 2 Warning word, par. 16-92 Warning Word Bit (Hex) Warning Word 2 (par. 16-93 Warning Word 2) Warning Word 00000001 Start Delayed (par. 16-92 Warning Word) 00000002 Stop Delayed 00000001 Brake check 00000004 Clock Failure 00000002 Power card over temperature 00000008 Reserved 00000004 Earth fault 00000010 Reserved 00000008 Ctrl.
VLT® HVAC Drive Programming Guide Troubleshooting 4.1.3 Extended Status Words Extended status word 2, par. 16-95 Ext. Status Word 2 Extended status word, par. 16-94 Ext. Status Word Status Word 2) 00000001 (par. 16-94 Ext.
Troubleshooting VLT® HVAC Drive Programming Guide 4.1.4 Fault Messages WARNING 1, 10 volts low The control card voltage is below 10 V from terminal 50. Remove some of the load from terminal 50, as the 10 V supply is overloaded. Max. 15 mA or minimum 590 Ω. This condition can be caused by a short in a connected potentiometer or improper wiring of the potentiometer. WARNING/ALARM 7, DC overvoltage If the intermediate circuit voltage exceeds the limit, the frequency converter trips after a time.
4 4 Troubleshooting VLT® HVAC Drive Programming Guide WARNING/ALARM 10, Motor overload temperature According to the electronic thermal protection (ETR), the motor is too hot. Select whether the frequency converter gives a warning or an alarm when the counter reaches 100% in par. 1-90 Motor Thermal Protection. The fault is that the motor is overloaded by more than 100% for too long. Troubleshooting: This fault may be caused by shock loading or fast acceleration with high inertia loads.
Troubleshooting VLT® HVAC Drive Programming Guide WARNING/ALARM 17, Control word timeout There is no communication to the frequency converter. The warning will only be active when par. 8-04 Control Timeout Function is NOT set to OFF. If par. 8-04 Control Timeout Function is set to Stop and Trip, a warning appears and the frequency converter ramps down until it trips, while giving an alarm. Troubleshooting: Check connections on the serial communication cable. Increase par.
4 4 Troubleshooting VLT® HVAC Drive Programming Guide ALARM 32, Motor phase W missing Motor phase W between the frequency converter and the motor is missing. Turn off the frequency converter and check motor phase W. ALARM 33, Inrush fault Too many power-ups have occurred within a short time period. Let unit cool to operating temperature. WARNING/ALARM 34, Fieldbus communication fault The fieldbus on the communication option card is not working.
VLT® HVAC Drive Programming Guide Troubleshooting 2316 Missing io_statepage from power unit 2324 Power card configuration is determined to be incorrect at power up 2330 Power size information between the power cards does 2561 No communication from DSP to ATACD not match 2562 No communication from ATACD to DSP (state running) 2816 Stack overflow Control board module 2817 Scheduler slow tasks 2818 Fast tasks 2819 Parameter thread 2820 LCP Stack overflow 2821 Serial port overflow 2822
4 4 Troubleshooting VLT® HVAC Drive Programming Guide WARNING 64, Voltage limit The load and speed combination demands a motor voltage higher than the actual DC link voltage. WARNING/ALARM/TRIP 65, Control card over temperature Control card over temperature: The cutout temperature of the control card is 80° C. WARNING 66, Heatsink temperature low This warning is based on the temperature sensor in the IGBT module.
VLT® HVAC Drive Programming Guide Troubleshooting ALARM 243, Brake IGBT This alarm is only for F Frame drives. It is equivalent to Alarm 27. The report value in the alarm log indicates which power module generated the alarm: ALARM 246, Power card supply This alarm is only for F Frame drives. It is equivalent to Alarm 46. The report value in the alarm log indicates which power module generated the alarm: 1 = left most inverter module. 1 = left most inverter module.
5 5 VLT® HVAC Drive Programming Guide Parameter Lists 'All set-up': the parameter can be set individually in each of the four set-ups, i. e. one single parameter can have four different data values. ’1 set-up’: data value will be the same in all set-ups. 5 Parameter Lists 5.1 Parameter Options SR: Size related 5.1.
VLT® HVAC Drive Programming Guide Parameter Lists 5.1.2 0-** Operation and Display Par. No.
Parameter Lists Par. No.
VLT® HVAC Drive Programming Guide Parameter Lists 5.1.3 1-** Load / Motor Par. No. Parameter description Default value 4-set-up Change during Conver- operation sion index TRUE - Uint8 # Type 1-0* General Settings 1-00 Configuration Mode null All set-ups [3] Auto Energy Optim.
5 5 Parameter Lists VLT® HVAC Drive Programming Guide 5.1.4 2-** Brakes Par. No. # Parameter description Default value 4-set-up Change during Conver- operation sion index Type 2-0* DC-Brake 2-00 DC Hold/Preheat Current 50 % All set-ups TRUE 0 Uint8 2-01 DC Brake Current 50 % All set-ups TRUE 0 Uint16 2-02 DC Braking Time 10.
Parameter Lists VLT® HVAC Drive Programming Guide 5.1.6 4-** Limits / Warnings Par. No.
5 5 VLT® HVAC Drive Programming Guide Parameter Lists 5.1.7 5-** Digital In / Out Par. No.
VLT® HVAC Drive Programming Guide Parameter Lists 5.1.8 6-** Analog In / Out Par. No. # Parameter description Default value 4-set-up Change during Conver- operation sion index Type 6-0* Analog I/O Mode 6-00 Live Zero Timeout Time 10 s All set-ups TRUE 0 Uint8 6-01 Live Zero Timeout Function [0] Off All set-ups TRUE - Uint8 6-02 Fire Mode Live Zero Timeout Function [0] Off All set-ups TRUE - Uint8 6-1* Analog Input 53 6-10 Terminal 53 Low Voltage 0.
5 5 Parameter Lists VLT® HVAC Drive Programming Guide 5.1.9 8-** Communication and Options Par. No.
Parameter Lists VLT® HVAC Drive Programming Guide 5.1.10 9-** Profibus Par. No.
5 5 Parameter Lists VLT® HVAC Drive Programming Guide 5.1.11 10-** CAN Fieldbus Par. No.
Parameter Lists VLT® HVAC Drive Programming Guide 5.1.13 13-** Smart Logic Controller Par. No.
5 5 VLT® HVAC Drive Programming Guide Parameter Lists 5.1.14 14-** Special Functions Par. No.
VLT® HVAC Drive Programming Guide Parameter Lists 5.1.15 15-** Drive Information Par. No.
5 5 Parameter Lists VLT® HVAC Drive Programming Guide Par. No.
Parameter Lists VLT® HVAC Drive Programming Guide 5.1.16 16-** Data Readouts Par. No. Parameter description # Default value 4-set-up Change during operation Conversion index Type 0 N/A All set-ups FALSE 0 V2 backUnit All set-ups FALSE -3 Int32 0.0 % All set-ups FALSE -1 Int16 16-0* General Status 16-00 Control Word 0.000 ReferenceFeed16-01 Reference [Unit] 16-02 Reference [%] 16-03 Status Word 0 N/A All set-ups FALSE 0 V2 16-05 Main Actual Value [%] 0.
5 5 Parameter Lists Par. No.
VLT® HVAC Drive Programming Guide Parameter Lists 5.1.17 18-** Info & Readouts Par. No.
5 5 Parameter Lists VLT® HVAC Drive Programming Guide 5.1.18 20-** FC Closed Loop Par. No.
VLT® HVAC Drive Programming Guide Parameter Lists 5.1.19 21-** Ext. Closed Loop Par. No. # Parameter description Default value 4-set-up Change during operation Conversion index Type Uint8 21-0* Ext. CL Autotuning 21-00 Closed Loop Type [0] Auto 2 set-ups TRUE - 21-01 PID Performance [0] Normal 2 set-ups TRUE - Uint8 21-02 PID Output Change 0.10 N/A 2 set-ups TRUE -2 Uint16 21-03 Minimum Feedback Level -999999.
Parameter Lists Par. No. # Parameter description VLT® HVAC Drive Programming Guide Default value 4-set-up Change during operation Conversion index Type [0] Normal All set-ups TRUE - Uint8 21-6* Ext. CL 3 PID 21-60 Ext. 3 Normal/Inverse Control 21-61 Ext. 3 Proportional Gain 21-62 Ext. 3 Integral Time 21-63 Ext. 3 Differentation Time 21-64 Ext. 3 Dif. Gain Limit 0.01 N/A All set-ups TRUE -2 Uint16 10000.00 s All set-ups TRUE -2 Uint32 0.
VLT® HVAC Drive Programming Guide Parameter Lists 5.1.20 22-** Application Functions Par. No. Parameter description # Default value 4-set-up Change during operation Conversion index Type 22-0* Miscellaneous 22-00 External Interlock Delay 22-01 Power Filter Time 0s All set-ups TRUE 0 Uint16 0.
Parameter Lists Par. No. Parameter description # VLT® HVAC Drive Programming Guide Default value 4-set-up Change during operation Conversion index Type 22-85 Speed at Design Point [RPM] SR All set-ups TRUE 67 Uint16 22-86 Speed at Design Point [Hz] SR All set-ups TRUE -1 Uint16 22-87 Pressure at No-Flow Speed 22-88 Pressure at Rated Speed 22-89 22-90 0.000 N/A All set-ups TRUE -3 Int32 999999.999 N/A All set-ups TRUE -3 Int32 Flow at Design Point 0.
Parameter Lists VLT® HVAC Drive Programming Guide 5.1.21 23-** Time Based Funtions Par. No.
5 5 Parameter Lists VLT® HVAC Drive Programming Guide 5.1.22 24-** Application Functions 2 Par. No.
Parameter Lists VLT® HVAC Drive Programming Guide 5.1.23 25-** Cascade Pack Controller Par. No.
5 5 Parameter Lists VLT® HVAC Drive Programming Guide 5.1.24 26-** Analog I / O Option MCB 109 Par. No. # Parameter description Default value 4-set-up Change during Conver- operation sion index Type 26-0* Analog I/O Mode 26-00 Terminal X42/1 Mode [1] Voltage All set-ups TRUE - Uint8 26-01 Terminal X42/3 Mode [1] Voltage All set-ups TRUE - Uint8 26-02 Terminal X42/5 Mode [1] Voltage All set-ups TRUE - Uint8 26-1* Analog Input X42/1 26-10 Terminal X42/1 Low Voltage 0.
Index VLT® HVAC Drive Programming Guide Brake Function 2-10 Index Brake Power " "i-am" Service 8-74 81 Abbreviations Ac Brake Max.
Index VLT® HVAC Drive Programming Guide Csiv Filename 15-59 111 Current Fault Source 16-49 115 Current Lim Ctrl, Filter Time 14-32 105 E Current Lim Ctrl, Integration Time 14-31 105 End Of Curve Current Lim Ctrl, Proportional Gain 14-30 105 End Of Curve Delay 22-51 147 55 End Of Curve Function 22-50 146 Current Limit Control 105 End-of-timeout Function 8-05 Custom Readout 16-09 113 Energy Cost 23-81 Current Limit 4-18 146 76 160 Custom Readout Max Value 0-32 33 Energy Log Cust
Index VLT® HVAC Drive Programming Guide F G [Fan 1 Area In2] 20-35 127 General Warning 4 [Fan 1 Area M2] 20-34 127 Graphical Display 10 [Fan 2 Area In2] 20-37 127 [Fan 2 Area M2] 20-36 127 Fan Control 14-52 106 H Fan Monitor 14-53 106 [Hand On] Key On Lcp 0-40 Fault Messages 191 Heatsink Temp.
Index VLT® HVAC Drive Programming Guide Logging Buffer Full 16-40 115 Minimum Reference/feedb.
Index VLT® HVAC Drive Programming Guide Operation Mode 14-22 104 Pressure At Rated Speed 22-88 Option Ident.
Index VLT® HVAC Drive Programming Guide Readout: Linked Set-ups 0-13 29 Slot B Option Sw Version 15-73 112 Readout: Prog.
Index VLT® HVAC Drive Programming Guide Terminal 27 Mode 5-01 58 Timed Actions Reactivation 23-09 152 Terminal 29 Mode 5-02 58 Timed Actions Status 16-43 115 Terminal 29 Pulse Output Variable 5-63 67 Timed Bin Data 23-62 158 Terminal 42 Output 6-50 72 Timed Period Start 23-63 158 Terminal 42 Output Bus Control 6-53 74 Timed Period Stop 23-64 158 Terminal 42 Output Max Scale 6-52 73 [Torque %] 16-22 114 Terminal 42 Output Min Scale 6-51 73 Torque Characteristics 1-03 Terminal 42