User guide

NT® INTEGRATED FLOW CONTROLLER WITH DEVICENET™ COMMUNICATION USER GUIDE
32 Customer Service Tel. 763-502-0200 Customer Service Fax 763-502-0300 ENTEGRIS, INC.
Instances 1-n
ATTRIBUTES 4.N - INSTANCE ATTRIBUTES - ASSEMBLY OBJECT
ACCESS
ATT. ID REQUIRED SUPPORTED RULE NAME ATTRIBUTE DESCRIPTION
3 Required Yes Get Data The I/O Assembly DATA attribute is formatted
as a structure of data elements with the First
element (elements are listed in the "Instance
Identifiers" table) ordered first. All data
components are encoded with the Low-
ordered Byte first; (i.e., the Least Significant
Byte, LSB, is in the Low-ordered Index,
Address) also known as Little Endian.
SERVICES 4.N - INSTANCE SERVICES - ASSEMBLY OBJECT
PARAMETER
CODE REQUIRED SUPPORTED NAME PARAMETERS DESCRIPTION VALUES
0E
hex
Required Yes Get_Attribute_ Attribute ID Retrieves an 1–255
Single (USINT) attribute value
Connection Object (05
hex
)
Class
ATTRIBUTES 5.0 - CLASS ATTRIBUTES - CONNECTION OBJECT
ACCESS DATA ATTRIBUTE
ATT. ID REQUIRED SUPPORTED RULE NAME TYPE DESCRIPTION VALUES
1 Optional Yes Get Revision UINT Object revision = 01
SERVICES 5.0 - CLASS SERVICES - CONNECTION OBJECT
PARAMETER
CODE REQUIRED SUPPORTED NAME PARAMETERS DESCRIPTION VALUES
0E
hex
Required Yes Get_Attribute_ Attribute ID Retrieves an 1–255
Single (USINT) attribute value