Service manual

6.3.1 Quick Start
Before any detail check of UPS, please check the components listed in the following table. This
action could help you find problem quickly and make following debug procedures go smoothly.
Related Circuit Block Components to be checked Component Type Fail condition
BAT FUSE 1K/3K:F1/F2; 2K:F1 Fuse Open
I/P FUSE (on PSDR) F3, Fuse Open
2K/3K:D16, D17, REC02
1K:D10, D11, REC1
Diode Short or open
PFC converter
2K/3K:Q09, 1K:Q14 IGBT C-E short or open
2K/3K:Q04, Q05, Q06, Q07
1K:Q4, Q6, Q10Q11
MOSFET D-S short or open
Push-Pull Booster
2K/3K:D05, D06, D07, D08
1K:D12, D13, D14, D15
Power Diode Short or open
Inverter
2K/3K:Q13, Q14, Q15, Q16
1K:Q12, Q13
IGBT C-E short or open
Q2 MOSFET D-S short or open
Charger module
D10, D11, D12, D13, D15
Power Diode Short or open
Q201 MOSFET D-S short or open
SPS module
D202, D203 Power Diode Short or open
!
If the fuse is open, replacing fuse only DOES NOT mean you have solved the problem. In
most case, open of fuse is caused by other failure of components; therefore, before restart
that UPS, you must find the real failure components and replace them!
34