Service manual
Possible Cause 3: DC/DC circuit fails.
Solution: Refer to DC/DC circuit failure analysis.
Possible Cause 3: Bus voltage feedback circuit problem.
Solution: Refer to bus feedback loop problem.
Transfer to Bypass Due to Inverter Failure
Possible Cause 1: O/P short circuit. (In this situation, no power will be transfer to O/P socket.)
Solution: Remove short circuit condition, turn off the UPS then turn on again.
Possible Cause 2: Inverter circuit failed.
Solution: Refer to Inverter Circuit failure analysis.
Fault Due to Battery Over-Voltage
Possible Cause: Charger circuit fail
Solution: Refer to charger circuit analysis.
30